to chemicals, including carbon monoxide
and benzene, which are known to the State
of California to cause cancer and birth
defects or other reproductive harm.
For more information go to
www.P65warnings.ca.gov
Kohler strongly recommends
that only factory-authorized
distributors or dealers install
and service the generator.
Product Identification Information
Product identification numbers determine service parts.
Record the product identification numbers in the spaces
below immediately after unpacking the products so that
the numbers are readily available for future reference.
Record field-installed kit numbers after installing the
kits.
Generator Set Identification Numbers
Record the product identification numbers from the
generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory NumberAccessory Description
Controller Identification
Record the controller description from the generator set
operation manual, spec sheet, or sales invoice.
Controller Description
Engine Identification
Record the product identification information from the
engine nameplate.
Appendix A Abbreviations71................................................................
TP-7092 8/18Table of Contents
Page 6
Notes
TP-7092 8/186
Page 7
Safety Precautions and Instructions
IMPORTANTSAFETY INSTRUCTIONS.
Electromechanicalequipment,
includinggenerator sets,transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threateningdangerwhen
improperlyinstalled, operated,or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions.SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazardthatwillcausesevere
personal injury, death,orsubstantial
property damage.
WARNING
Warning indicates the presence of a
hazardthatcancausesevere
personal injury, death, or substantial
property damage.
CAUTION
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
workingon thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Press the generator set off/reset
button to shut down the generator set.
(2) Disconnect the power to the battery
charger, if equipped. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolate the battery charger from
explosive fumes.
Battery electrolyte is a diluted
sulfuric acid. Battery acid can cause
severe injury or death. Battery acid
can cause blindness and burn skin.
Alwayswearsplashproofsafety
goggles, rubber gloves, and boots
when servicing the battery.Do not
open a sealed battery or mutilate the
battery case. If battery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid in the case
of eye contact. Never add acid to a
battery after placing the battery in
service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
container with 4 L (1 gal.) of water and
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemicalreaction(foaming)has
ceased. Flush the resulting liquid with
water and dry the area.
TP-7092 8/187Safety Precautions and Instructions
Page 8
Battery gases. Explosion can cause
severe injury or death. Battery gases
can cause an explosion. Do not smoke
or permit flames or sparks to occur near
a battery at any time, particularly when
it is charging.Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove all jewelry before servicing the
equipment. Discharge static electricity
from yourbody beforetouching
batteries by first touching a grounded
metal surface away from the battery. To
avoid sparks, do not disturb the battery
charger connections while the battery
is charging. Always turn the battery
charger off before disconnecting the
battery connections.Ventilate the
compartments containing batteries to
prevent accumulation of explosive
gases.
Battery short circuits.Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/orequipmentdamage.
Disconnectthebatterybefore
generatorsetinstallationor
maintenance.Remove all jewelry
before servicing the equipment. Use
tools with insulated handles. Remove
the negative (--) lead first when
disconnecting the battery. Reconnect
the negative (--) lead last when
reconnecting the battery.Never
connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.
Engine Backfire/Flash
Fire
WARNING
Risk of fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner removed.
Servicing the fuel system. A flash
fire can cause severe injury or death.
Do not smoke or permit flames or
sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when removing the fuel line or
carburetor.
Combustible materials. A fire can
causesevere injuryor death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BCforelectricalfiresoras
recommended by the local fire code or
an authorized agency.Train all
personnelonfireextinguisher
operationandfireprevention
procedures.
Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
Theexhaustsystemmust be
leakproof and routinely inspected.
Generator set operation.Carbon
monoxide can cause severe nausea,
fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Avoid
breathing exhaust fumes when working
on or near the generator set. Never
operate the generator set inside a
building. Never operate the generator
set where exhaust gas could seep
inside or be drawn into a potentially
occupied building through windows, air
intake vents, or other openings.
Carbonmonoxidedetectors.
Carbon monoxide can cause severe
nausea, fainting, or death.Install
carbon monoxide detectors on each
level of any building adjacent to the
generator set. Locate the detectors to
adequatelywarnthebuilding’s
occupants of the presence of carbon
monoxide.Keepthedetectors
operational at all times. Periodically
test and replace the carbon monoxide
detectorsaccordingtothe
manufacturer’s instructions.
Carbonmonoxidesymptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,colorless,tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.Alert others to the
possibilityofcarbonmonoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.
TP-7092 8/188Safety Precautions and Instructions
Page 9
Fuel System
Hazardous Noise
WARNING
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system.Explosive fuel
vapors can cause severe injury or
death.Vaporized fuels are highly
explosive.Use extreme care when
handling and storing fuels. Store fuels
in a well-ventilated area away from
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.Use flexible
sections to avoid fuel line breakage
caused by vibration. Do not operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
Gas fuel leaks.Explosive fuel
vapors can cause severe injury or
death.Fuel leakage can cause an
explosion. Check the LPG vapor or
natural gas fuel system for leakage by
using a soap and water solution with
the fuel system test pressurized to
6--8 ouncespersquareinch
(10--14 inches water column). Do not
use a soap solution containing either
ammonia or chlorine because both
prevent bubble formation. Asuccessful
test depends on the ability of the
solution to bubble.
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Engine noise. Hazardous noise can
cause hearing loss. Generator sets
not equipped with sound enclosures
can produce noise levels greater than
105 dBA. Prolonged exposure to noise
levels greater than 85 dBA can cause
permanent hearing loss. Wear hearing
protection when near an operating
generator set.
Hazardous Voltage/
Moving Parts
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
servicedbyqualifiedelectrical
personnel.
DANGER
Hazardous voltage. Moving parts.
Will cause severe injury or death.
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
If the generator set is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnectionofstandbyand
normal sources of supply.
CAUTION
Welding the generator set.
Cancausesevereelectrical
equipment damage.
Never weld components of the
generatorsetwithoutfirst
disconnecting the battery, controller
wiring harness, and engine electronic
control module (ECM).
Grounding electricalequipment.
Hazardous voltage will cause severe
injury or death.Electrocution is
possiblewheneverelectricityis
present. Ensure you comply with all
applicablecodesandstandards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turn off the main
circuit breakers of all power sources
before servicing the equipment. Never
contact electrical leads or appliances
when standing in water or on wet
ground becausethese conditions
increase the risk of electrocution.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
TP-7092 8/189Safety Precautions and Instructions
Page 10
Welding on the generator set. Can
cause severe electrical equipment
damage.Before welding on the
generator set perform the following
steps: (1) Remove the battery cables,
negative (--) lead first. (2) Disconnect
all engine electronic control module
(ECM) connectors. (3) Disconnect all
generator set controller and voltage
regulator circuit board connectors.
(4) Disconnect the engine batterychargingalternatorconnections.
(5) Attach the weld ground connection
close to the weld location.
Hot Parts
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Notice
NOTICE
Canadian installations only.For
standby service connect the output of
the generator set to a suitably rated
transfer switch in accordance with
Canadian Electrical Code, Part 1.
Connecting the battery and the
battery charger. Hazardous voltage
will cause severe injury or death.
Reconnectthebatterycorrectly,
positive to positive and negative to
negative, to avoid electrical shock and
damage to the battery charger and
battery(ies).Haveaqualified
electrician install the battery(ies).
Shortcircuits.Hazardous
voltage/current will cause severe
injury or death.Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove all jewelry before servicing the
equipment.
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death. Install
a transfer switch in standby power
installations to prevent the connection
of standby and other sources of power.
Electricalbackfeedinto autility
electrical system can cause severe
injury or death to utility personnel
working on power lines.
Servicing the exhaust system. Hot
parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
Servicing the engine heater.Hot
parts can cause minor personal
injury or property damage. Install the
heater before connecting it to power.
Operating the heater before installation
can cause burns and component
damage.Disconnect power to the
heater and allow it to cool before
servicing the heater or nearby parts.
Heavy Equipment
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
TP-7092 8/1810 Safety Precautions and Instructions
Page 11
Introduction
This manual provides operation and maintenance
instructionsforresidential/commercialmodel
14/20RCA/RCAL generator sets equipped with the
RDC2 generator set/transfer switch controller.See
Figure 1.
Kohler strongly recommends that only factoryauthorized distributors or dealers install and
service the generator.
Have the generator set installed by an authorized
distributor/dealer or service technician. Refer to the
Installation Manual for installation instructions.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment service requirements are very important
to safe and efficient operation. Inspect the parts often
and perform required service at the prescribed intervals.
Obtain service from an authorized service distributor/
dealer to keep equipment in top condition.
List of Related Literature
Figure 2 identifies literature available for the generator
sets covered in this manual and related accessories.
Only trained and qualified personnel should install or
service the generator set.
Generator Set LiteraturePart Number
Specification Sheet, 14RCAG4-270
Specification Sheet, 14RCALG4-271
Specification Sheet, 20RCAG4-272
Specification Sheet, 20RCALG4-273
Installation Manual, Generator SetTP-7091
Service Manual, Generator SetTP-7093
Transfer Switch Literature
Operation/Installation Manual,
Model RXT Automatic Transfer Switch
Operation/Installation Manual,
Model RDT Automatic Transfer Switch
The following illustration shows a typical generator set
nameplate. Copy the model, serial, and specification
numbers from the nameplate into the spaces provided in
the product information section on the inside front cover
of this manual. See the service views in Section 1.8 for
the nameplate location.
Genset Model
Spec Number
Serial Number
Material Number
Service Duty
Voltage
Alt Model
Insulation
MFG Da te
Amps
Phase
RPM
Battery
Fuel
kW
kVA
PF
Hz
GM12070
Emission Information
The Kohlerr Model CH740 engine used on the
14RCA/RCAL generator set is certified to operate using
natural gas or propane fuel.
The Kohlerr Model CH1000 engine used on the
20RCA/RCAL generator sets is certified to operate
using natural gas or propane fuel for emergency
standby use only. This generator set is certified by the
U.S. EPA for emergency standby operation backing up a
reliable utility source.Operation outside these
guidelines is a violation of national EPA regulations.
The Emission Compliance Period referred to on the
Emission Control or Air Index label indicates the number
of operating hours for which the engine has been shown
to meet CARB or EPA emission requirements. Figure 3
provides the engine compliance period (in hours)
associated with the category descriptor, which may be
found on the certification label.
Emission Compliance Period
EPA
CARB
Category C
250 hours
Moderate
125 hours
Category B
500 hours
Intermediate
250 hours
Category A
1000 hours
Extended
500 hours
Figure 3Emission Compliance Period
Refer to the certification label for engine displacement.
The exhaust emission control system for the CH740
engines (14RCA/RCAL) is EM for U.S. EPA, California,
and Europe.
The exhaust emission control system for the CH1000
engine (20RCA/RCAL) is EM for U.S. EPA, California,
and Europe.
Generator Set Application
Kohlerr Co. ensures that all Kohlerr generator sets are
certified to applicable standards for their intended
application. It is the owner/operator’s responsibility to
operate Kohlerr generator sets exclusively according to
the directions provided in the accompanying operation
manuals.
Kohlerr generator sets designated as Stationary
Standby, Emergency or Emergency Standby may only
be operated for emergency power generation and for
maintenance/testing. Emergency power generation is
limited to power production when electric power from a
local utility (or the normal power source, if the facility
runs on its own power production) is interrupted.
Stationary non-emergency application of a Standby,
Emergency, or Emergency Standby rated generator set
is not allowed.
The U.S. Clean Air Act explicitly prohibits using
Emergency Standby generator sets as a primary
electric power source regardless of whether a site is
connected to the electrical grid. Emergency Standby
generators may NOT be used to power sites which are
not connected to an electric utility.
Owners/operators must ensure that the generator is
operated, exercised, and maintained according to this
operation manual. Owners/operators must retain
maintenance records.
TP-7092 8/1812 Introduction
Page 13
Service Assistance
For professional advice on generator set power
requirements and conscientious service, please contact
your nearest Kohler distributor or dealer.
D Visit the Kohler Co. website at KOHLERPower.com.
D Look at the labels and decals on your Kohler product
or review the appropriate literature or documents
included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
Kohler Asia Pacific Headquarters
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax:(65) 6264-6455
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax:(86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax:(86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax:(91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
TP-7092 8/1813Service Assistance
Page 14
Notes
TP-7092 8/1814 Service Assistance
Page 15
Section 1 Descriptions and Service Views
1.1Introduction
The generator set specification sheets provide specific
generator and engine information. Refer to the spec
sheet for data not supplied in this manual. Consult the
generator set service manual, engine operation manual,
and engine service manual for additional specifications.
Obtain copies of the latest spec sheets, manuals,
diagrams, and drawings from your local distributor/
dealer.
1.2Engine
The generator set has a four-cycle, twin cylinder, aircooled Kohlerr engine. The engine operates on cleanburning natural gas or LPG. Engine features include:
D Efficient overhead valve design and full pressure
lubrication for maximum power, torque, and reliability
under all operating conditions.
D Dependable, maintenance-free electronic ignition.
D Precision-formulated cast iron construction of parts
subjected to the most wear and tear.
D Field-convertible multi-fuel systems that allow fuel
changeover from natural gas to LPG (and vice- versa)
while maintaining emissions certification.
D Digital spark advance optimizes ignition timing for the
selected fuel.
1.3Alternator
To open the roof, insert the key provided with the
enclosure and turn counterclockwise 1/4 turn. Then just
raise the roof. The roof stays open until you are ready to
close it.
Be sure to close and lock the enclosure, and keep the
key in a secure location.
1.5Transfer Switch
The RDC2 controller is designed to interface with and
control the Kohler Model RXT Automatic Transfer
Switch (ATS).
If the power system uses a different model transfer
switch, the RDC2 controller will not control the transfer
switch. An ATS other than the Model RXT must be
equipped with a transfer switch controller and engine
start contacts that connect to the remote engine start
terminals on the generator set.
1.6Controller
RCA and RCAL models are equipped with the RDC2
controller. See Figure 1-1.
The controller provides integrated control for the
generator set, Kohlerr Model RXT transfer switch,
programmable interface module (PIM) and load
management devices.
The controller’s 2-line LCD screen displays status
messages and system settings that are clear and easy
to read, even in direct sunlight or low light.
The generator uses Kohler’s unique PowerBoostt
voltage regulation system, which provides instant
response to load changes.
PowerBoosttensures reliable motor starting and
consistent voltage levels. PowerBoosttutilizes a
voltage excitation system that employs a winding
independent of the main output windings to provide
excitation voltage.
1.4Generator Set Enclosure
The generator set is housed in an aluminum enclosure
with our fade-, scratch-, and corrosion-resistant Kohlerr
Power Armort automotive-grade textured cashmere
finish. The enclosure has a hinged, locking roof that
allows easy access to the generator set controller when
required, but locks securely to prevent unauthorized
access.
TP-7092 8/1815Section 1 Descriptions and Service Views
Figure 1-1RDC2 Generator Set Controller
Page 16
RDC2 Controller Features
D Six-button keypad
d OFF, AUTO, and RUN pushbuttons
d Select and arrow buttons for access to system
configuration and adjustment menus
D LED indicators for OFF, AUTO, and RUN modes
D LED indicators for utility power and generator set
source availability and ATS position (Model RXT
transfer switch required)
D LCD display
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for
excellent visibility in all lighting conditions
D Scrolling system status display
d Generator set status
d Voltage and frequency
d Engine lube oil temperature
d Oil pressure
d Battery voltage
d Engine runtime hours
D Date and time displays
D Smart engine cooldown senses engine temperature
D Digitalisochronousgovernortomaintain
steady-state speed at all loads
D Front-access mini USB connector for Kohlerr
SiteTecht connection
D Integral Ethernet connector for the Kohlerr OnCuer
Plus Generator Management System
D Built-in battery charger
D Remote two-wire start/stop capability for connection
of Model RDT or other transfer switches
D Diagnostic messages
d Displays diagnostic messages for the engine,
generator, Model RXT transfer switch,
programmable interface module (PIM), and load
management device
d Over 70 diagnostic messages can be displayed
D Maintenance reminders
D System settings
d System voltage, frequency, and phase
d Voltage adjustment
d Measurement system, English or metric
D ATS status (Model RXT ATS required)
d Source availability
d ATS position (normal/utility or
emergency/generator)
d Source voltage and frequency
D ATS control (Model RXT ATS required)
D Digital voltage regulation: ±0.5% RMS no-load to
full-load
D Automatic start with programmed cranking cycle
D Programmable exerciser can be set to start
automatically on any future day and time, and run
every week or every two weeks
D Exercise modes
d Unloaded cycle exercise with complete system
diagnostics
d Unloaded full-speed exercise
d Loaded full-speed exercise (Model RXT ATS
required)
d Source voltage and frequency settings
d Engine start time delay
d Transfer time delays
d Voltage calibration
d Fixed pickup and dropout settings
D ProgrammableInterfaceModule(PIM)status
displays
d Input status (active/inactive)
d Output status (active/inactive)
D Load control menus
d Load status
d Test function
TP-7092 8/1816 Section 1 Descriptions and Service Views
Page 17
1.7Accessories
The following optional accessories are offered for the
generator sets.
1.7.1Heater Kits
Optional carburetor heaters and a cold starting package
are available.Heater kits are recommended for
improved cold starting in locations where the ambient
temperature drops below 0_C(32_F).
The cold starting package includes:
D Alternator brush cover
D Battery heater
D Breather tube heater
D Fuel regulator heater
D Oil heater
D Oil pressure sensor cover
D 3-way extension cord for power connection
The carburetor heater kits are sold separately. The fuel
regulator heater and battery heater kits are also
available separately.
The heaters require a continuous source of AC power.
See the generator set Installation Manual and the
installation instructions provided with the kits for more
information.
1.7.2OnCue Plus Generator
Management System
The Kohlerr OnCuer Plus Generator Management
System allows monitoring and control of your generator
set from your home or other location with Internet
accessusingacomputerormobiledevice.
OnCuer Plus can be configured to send email or text
message notifications in the event of a generator set
fault.
1.7.3Programmable Interface Module
(PIM)
The PIM is mounted in a NEMA 3R aluminum enclosure,
which can be mounted indoors or outdoors. See the
installation instructions provided with the PIM.
1.7.4Load Management
Two optional load management devices are available
for use with single-phase generator sets and a model
RXT or RDT transfer switch.
D The optional Load Shed Kit mounts inside a model
RDT or RXT transfer switch.
D The combined interface/load management board is
available for the Model RXT transfer switch.
The load management devices provide an automatic
load management system to comply with Section 702.5
of NEC 2008. The installer is responsible for ensuring
that the power system installation complies with all
applicable state and local codes.
Note: Theload managementdevicesareonly
compatible with single-phase generator sets.
The load management device automatically manages
up to six residential loads. Two relays are provided to
control two independent air conditioner loads. Upto four
powerrelaymodulescanbeconnectedfor
management of non-essential secondary loads.
The load management device is controlled by the RDC2
controller. The load on the generator set is monitored,
and loads are added or shed in the order of their priority.
See the installation instructions provided with the load
shed kit or the Model RXT Operation and Installation
Manual for more information.
1.7.5Concrete Mounting Pads
Kohler offers optional concrete mounting pads that are
custom-designedforModel14RCA/RCALand
20RCA/RCAL generator sets. Three-inch and four-inch
thick pads are available.Four-inch pads are
recommended for storm-prone areas.
The optional Programmable Interface Module (PIM)
providestwoprogrammableinputsandsix
programmable dry contact outputs for connection to
customer-supplied equipment.The outputs are
controlled by the RDC2 controller, and can also be
controlled remotely using OnCue Plus.
TP-7092 8/1817Section 1 Descriptions and Service Views
1.7.6Battery Heater Kit
The battery heater kit includes a thermostaticallycontrolled battery heating wrap to warm the battery in
cold weather. Battery heater kits are recommended for
generator installed in regions where the temperature
regularly falls below 0_C(32_F).
TP-7092 8/1818 Section 1 Descriptions and Service Views
Page 19
Section 2 Generator Set Operation
2.1Prestart Checklist
To ensure continued satisfactory operation, perform the
following checks or inspections before or at each
startup, as designated, and at the intervals specified in
the service schedule. In addition, some checks require
verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner
element to prevent unfiltered air from entering the
engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding
battery care and maintenance.
Exhaust System.Check for exhaust leaks and
blockages. Check the muffler condition.
D Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust system
connections.
D Check for corroded or broken metal parts and replace
them as needed.
2.3Generator Set Operation
DANGER
Hazardous voltage. Moving parts.
Will cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
Theexhaustsystemmust be
leakproof and routinely inspected.
D Check that the exhaust outlet is unobstructed.
Oil Level.Check the oil level before starting the
generator set and at the intervals given in Section 4,
Scheduled Maintenance. Maintain the oil level at or
near, not over, the full mark on the dipstick.
Operating Area.Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.
2.2Exercising the Generator Set
Operate the generator set once each week for 20
minutes. See Section 2.4 for information about loaded
and unloaded exercise modes. For instructions to set
the exerciser, see Section 3.6, Setting the Exerciser.
Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Avoid breathing exhaust
fumes when working on or near the generator set. Never
operate the generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawn into a potentially occupied building through windows, air
intake vents, or other openings.
Carbon monoxide symptoms. Carbon monoxide can
cause severe nausea, fainting, or death. Carbon monoxide
is a poisonous gas present in exhaust gases.Carbon
monoxide is an odorless, colorless, tasteless, nonirritating gas
that can cause death if inhaled for even a short time. Carbon
monoxide poisoning symptoms include but are not limited to
the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide
poisoning is possible, seek fresh air immediately and remain
active. Do not sit, lie down, or fall asleep. Alert others to the
possibility of carbon monoxide poisoning.Seek medical
attention if the condition of affected persons does not improve
within minutes of breathing fresh air.
TP-7092 8/1819Section 2 Generator Set Operation
Page 20
2.3.1Local Starting and Stopping
Start: Press the RUN button to immediately start the
generator set.
Stop: Press the OFF button. The engine stops.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
If a transfer switch other than the Model RXT is used, an
additional engine cooldown time delay may be
programmed on the transfer switch. To allow the smart
engine cooldown on the RDC2 controller to operate
most efficiently, set the cooldown time on the transfer
switch controller to zero or the minimum time allowed.
Refer to the instructions provided with the transfer
switch for more information.
2.3.2Automatic Operation
An automatic transfer switch monitors the utility power
and signals the generator set to start when utility power
is lost. The ATS then transfers the load to the generator
set.
When utility power is restored, the transfer switch
transfers the load back to utility, runs the generator set
with no load to cool down the engine, and then stops the
generator set.
See Sections 2.3.6 and 2.3.7 for more information about
automatic operation.
2.3.3Remote Starting and Stopping
A remote switch connected to terminals 3 and 4 can be
used to start and stop the generator set. Close the
switch to start and run the generator set. Open the
switch to stop the generator set.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
2.3.4Engine Start Crank Cycle
2.3.6Automatic Operation with Model
RXT Transfer Switch
The Model RXT transfer switch connects to the RDC2
controller through the ATS interface board on the
transfer switch.Also see the Model RXT Transfer
SwitchOperation/InstallationManualformore
information about transfer switch operation.
The controller must be in AUTO mode for automatic
transfer switch operation.
Automatic Start
The RDC2 controller receives utility source voltage
sensing data from the Model RXT transfer switch.
1. If the utility source voltage falls below an
acceptable level, the controller starts the engine
start time delay.
2. If the utility source is not restored before the time
delay expires, the generator set starts.
3. After the Normal-to-Emergency time delay, the
ATS is signaled to transfer the load to the
emergency source.
The controller attempts to start the generator set three
times (three crank cycles, 15 seconds crank and
15 seconds off). If the generator set does not start in
three attempts, the system shuts down on an overcrank
fault. See Section 2.5.
Cranking 1, 2, and 3 are displayed during the crank
cycle. Pressing the OFF button during the crank cycle
stops the cranking. No other buttons are acknowledged
during the crank cycle.
2.3.5Engine Cooldown
The engine cooldown time delay allows the engine to
run after the loads have been removed.
The engine cooldown time delay is set to 5 minutes. The
engine stops before the cooldown time delay expires if
thetemperaturedrops belowthecooled-down
temperature level, or if the temperature rises above the
high limit during the cooldown cycle.
Automatic Stop with Engine Cooldown
1. Whentheu tilitysourceisrestored,the
Emergency-to-Normal time delay starts.
2. Whenthe Emergency-to-Normaltime delay
expires, the load is transferred to the utility.
3. The generator set runs through the engine
cooldown cycle and then stops.
2.3.7Automatic Operation with Other
Transfer Switches
If a transfer switch other than the Model RXT (such as a
Kohler Model RDT) is used, the engine start contacts
from the ATS must be connected to engine start leads 3
and 4 on the generator set.
The controller must be in AUTO mode to respond to
remote start/stop signals from an ATS or remote switch.
TP-7092 8/1820 Section 2 Generator Set Operation
Page 21
Press the AUTO button to put the controller into
automatic mode.
2.4.2Unloaded Cycle Exercise with
Complete System Diagnostics
Automatic Start
The engine start contacts on the ATS close to signal the
generator set to start, and remain closed while the
generator set is running.
Automatic Stop
The engine start contacts on the ATS open to signal the
generator set to stop.
2.4Exercise
The RDC2 controller can be set to automatically run the
generator set at the same time and day each week.
Exercising the generator set weekly or every two weeks
is required to keep the engine and alternator in good
operating condition.
Three exercise modes are available: unloaded cycle,
unloaded full speed, and loaded full speed.See
Sections 2.4.2 through 2.4.4 for information about the
exercise modes. A loaded exercise can be set at the
RDC2 controller only if a Model RXT transfer switch is
connected.
An unloaded exercise runs the generator set without
signalling the transfer switch to transfer the electrical
load from the utility source to the generator set. The
Unloaded Cycle exercise with diagnostics is the
recommended exercise mode and is the default
exercise setting.
The Unloaded Cycle exercise runs the engine for 20
minutes in the cycle shown in Figure 2-1 and described
below.
D Runs at reduced speed for 10 minutes to warm up
and exercise the engine.
D Ramps up and runs at full speed for 3 minutes.
Engine diagnostics are performed during this
full-speed portion of the cycle, which provides the
best test of engine and alternator power backup
capability. Diagnostic tests at full speed can identify
potential problems with the power output and alert the
operator before an emergency event.
D Ramps down and runs at reduced speed for 5
minutes to cool down the engine before shutting down
automatically.
Note: With transfer switches other than the Model RXT,
it is possible to have two exercise settings (one
unloaded exercise set at the generator set
controller, and another exercise set at the ATS
controller). If the exercise times overlap, the ATS
exercise setting takes priority.
If a transfer switch other than the Model RXT is used,
refer to the instructions provided with the transfer switch
to set a loaded exercise at the ATS, if desired.
2.4.1Setting the Exerciser
When power is applied to the RDC2 controller (that is,
when the battery is connected), you will be prompted to
set the date and time, select a language, and then to set
the exerciser.
The first setting will flash. Press the Up and Down arrow
buttons to change the setting. Press Select to save the
setting and move on to the next. See Section 3.5 for
more detailed instructions to change settings on the
RDC2. See Section 3.6 for more detailed instructions to
set the exerciser or change the exercise settings.
3min.
1min.
Engine Speed, RPM
10 min.5 min.
Engine
Exercise
Full-Speed
Diagnostics
1min.
Cooldown
Figure 2-1Unloaded Exercise Cycle
System Diagnostics
During the unloaded exercise, the controller monitors
the following data. The controller display indicates that
the generator set is running, unless a fault is detected as
described below.
D ATS connection. The controller verifies that the
Model RXT ATS interface board is connected.
TP-7092 8/1821Section 2 Generator Set Operation
Page 22
D Battery voltage. Battery voltage is checked before
exercise to verify engine starting capability. Battery
voltage provides a measurement of battery health. If
the controller detects low battery voltage, the
condition is indicated on the display.
D Communication integrity tests.J1939, RBUS,
Ethernet, and USB are monitored for messages
indicating that the controller and wiring are reliable.
2.4.4Loaded Full-Speed Exercise (with
RXT only)
A loaded exercise starts the generator set, ramps up to
full speed, and then transfers the electrical load from the
utility source to the generator set. After 20 minutes, the
load is transferred back to the utility source. The engine
runs without load for 5 minutes or until cool, and then
shuts down automatically.
D Engine speed.Engine speed is measured at
reduced speed and full speed.An overspeed or
underspeed condition will result in a fault condition
and shutdown.
D Generator outputfrequency andvoltage.
Operating the generator at full speed allows the
RDC2 controller to check the output power for correct
voltage, frequency, and stability. When the engine is
running at full speed, the controller verifies that the
voltage and frequency are within acceptable limits. A
fault message is displayed if the voltage or frequency
is out of range.
D Oil pressure.Oil pressure is verified to ensure
proper lubrication of critical engine components.
Pressure is monitored at both reduced and full
speeds. Ifthe oil pressure is low,the Low Oil Pressure
message is displayed and the generator set shuts
down.
2.4.3Unloaded Full-Speed Exercise
The unloaded full-speed exercise runs the generator set
at full speed for 20 minutes without transferring the load.
To set an unloaded full-speed exercise, follow the
procedure in Figure 3-8 and select Exercise Mode:
Unloaded Full.
Note: With a loaded exercise, power to the building is
lost for up to 10 seconds during load transfer.
For a loaded exercise controlled by the RDC2 controller,
a Model RXT transfer switch must be connected to the
generator set.To set a loaded exercise, follow the
procedure in Figure 3-8 and select Exercise Type:
Loaded.
For a loaded exercise with a transfer switch other than a
Kohlerr Model RXT, program the exercise at the
transfer switch controller. Refer to the transfer switch
operation manual for instructions.
2.4.5Power Failure During Exercise
Cycle
If the utility power is lost during an unloaded exercise,
the ATS transfers to the emergency source, the exercise
is ended and the control remains in the AUTO mode.
If the utility power is lost during a loaded exercise, the
exercise is ended. The ATS remains in the emergency
position and the control goes into the AUTO mode.
The generator set continues to run and supply power to
the load for the duration of the utility power outage.
When Utility power is restored, the ATSwill re-transfer to
the utility source through normal timing sequences.
TP-7092 8/1822 Section 2 Generator Set Operation
Page 23
2.5Faults
The RDC2 controller displays fault messages for
generator set warnings and shutdowns. Selected fault
messages are shown in Figure 2-3.Contact an
authorized distributor/dealer for service, if necessary.
2.5.1Warnings
The controller displays a fault message but the
generator set does not shut down on a warning. The
controller resets automatically after a warning condition
is corrected.
2.5.4Resetting the Controller after a
Fault Shutdown
Always identify and correct the cause of a fault
shutdown before resetting the controller. Check the
fault message displayed on the controller and refer to
Figure 2-3 to identify and correct the fault condition
beforeproceeding.Contactanauthorized
distributor/dealer for service, if necessary.
RDC2 Controller Reset Procedure
Press the OFF button to reset the controller,or follow the
procedure below. See Figure 2-2.
2.5.2Shutdowns
Under a fault shutdown condition, the generator set
shuts down automatically and the controller displays a
fault message. The OFF LED flashes. In some cases,
the engine cooldown cycle runs before the engine shuts
down. See Figure 2-3.
Shutdown switches (such as the low oil pressure switch
or high engine temperature switch) on the generator set
will automatically reset when the problem is corrected.
However, the fault condition at the controller does not
clear until the controller is reset.
The generator set cannot be restarted until the fault
condition is corrected and the controller is reset. See
Section 2.5.4 for instructions to reset the controller after
a fault shutdown.
2.5.3ATS Communication Errors
When a Model RXT transfer switch is used, an ATS fault
indicates that the connection to the interface board on
the transfer switch has been lost. Check the connection
to the ATS interface board.
1. While the fault message is displayed, press the
Select button to go to the Overview menu.
2. Press Select again. The active fault message is
displayed.
3. Press Select.Confirm Clear Fault: NO is
displayed.
4. Press the Up arrow button. Confirm Clear Fault:
YES is displayed.
5. Press the Select button to enter YES and clear the
fault.
6. Press the Select button to return to the overview
menu. The controller changes to OFF mode.
7. Press AUTO to put the generator set into automatic
mode.
Fault Message
Overview -- -->
1.2 h
Fault Message
Press Up arrow button.
Confirm Clear
Fault: NO
Confirm Clear
Fault: YES
Figure 2-2Clearing a Fault on the RDC2 Controller
TP-7092 8/1823Section 2 Generator Set Operation
tp6809
Page 24
Warning (W) or
Fault Message
AC Sens LossW(1sec.)
Shutdown (SD)
SD (3 sec.) *
ConditionCheck
AC sensing lost. In Auto mode, generator output
AC sensing is lost. Detection begins10 seconds
after crank disconnect.
Warning: after 1 second if no output detected
after crank disconnect.
Shutdown: after 3 seconds if voltage was
present and then lost.
Accy PwrOver
Warning
WAccessory Power Overload. An over current
fault (short circuit) on the accessory controller
power output.
ATS ComErrorWATS communication error. Warning is displayed
if ATS interface connection is lost.
See Section 2.5.3.
ATS PhaseRotWATS phase rotation mismatch. Transfer switch
phase rotation does not match, ATS will not
transfer.
Aux InputSD *Auxiliary input. An optional customer-connected
input is closed. (Digital input from optional PIM.)
Batt Chg FltWBattery charger fault. Input to PIM from an
external battery charger (not the built-in battery
charger).
Battery CrLo
Warning
WEngine starting battery voltage falls below
1 1 VDC for more than 10 seconds. Inhibited
during the engine crank cycle.
Clears when the battery voltage returns to an
acceptable level.
Battery HighWEngine starting battery voltage rises above 16
VDC for more than 10 seconds. Inhibited during
the engine crank cycle.
Clears when the battery voltage returns to an
acceptable level.
Battery Voltage
Low
WEngine starting battery voltage falls below 12.5
VDC for more than 90 seconds when the engine
is not running. Not operative during the engine
crank cycle.
Clears when the battery voltage returns to an
acceptable level.
Eng Speed
High
SD *Engine speed exceeds 115% of the normal
running speed for more than 0.3 seconds.
Eng Speed LowSD *Engine speed drops below 85% of the normal
running speed for more than 3 seconds.
Exer Not SchWExercise not scheduled. No exercise is
scheduled on the controller.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Check communication wiring between
transfer switch interface board and
generator set.
Correct the ATS connection. Refer to
the ATS Installation manual, wiring
diagrams, and labels on the transfer
switch.
Check customer-supplied equipment.
Check external battery charger.
Check the battery rating and
condition.
Check the battery charger operation.
Charge or replace the battery.
Check the battery rating and
condition.
Check the battery charger operation.
Check the battery rating and
condition.
Check the battery charger operation.
Charge or replace the battery.
Contact an authorized
distributor/dealer for service.
Reduce the load.
Model 20RCA/20RCAL only: Check
enclosure thermostat and reset if
tripped. See Section 5.5.
Contact an authorized
distributor/dealer for service.
See Section 3.6 for instructions to set
the exerciser.
Frequency HighSD *Governed frequency exceeds 110% of the
system’s frequency setpoint for more than 10
seconds. Function becomes active 10 seconds
after engine start (10 second inhibit).
* Engine cooldown runs before shutting down.
Contact an authorized
distributor/dealer for service.
TP-7092 8/1824 Section 2 Generator Set Operation
Page 25
Warning (W) or
Fault
Shutdown (SD)
ConditionCheck
Frequency LowSD *Governed frequency falls below 90% of the
system frequency setting for more than
10 seconds, or 1 Hz below the system frequency
setting for more than 60 seconds.
Function becomes active 10 seconds after
engine start (10 second inhibit).
Lo Crank VltWLow cranking voltage. Battery voltage dropped
below 3.5 VDC during engine cranking.
Locked RotorSDNo engine rotation is sensed during cranking.
Shuts down 3 seconds after the fault is detected.
MainPwrOverLSDMain power overload. An over current fault on
the 70 controller power output (short circuit).
Not in AutoWThe generator set is not in Automatic (standby)
mode. Remote start and stop commands from a
transfer switch or remote switch will be ignored.
Reduce the load and restart the
generator set.
Model 20RCA/20RCAL only: Check
enclosure thermostat and reset if
tripped. See Section 5.5.
Contact an authorized
distributor/dealer for service.
Charge or replace the battery.
Check the battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
Press AUTO to place the generator
set in Automatic mode, when
appropriate.
more than 5 seconds. Function becomes active
30 seconds after crank disconnect (30 second
inhibit).
Note: The low oil pressure shutdown does not
protect against low oil level. Check the engine
oil level regularly as recommended in Section 4.
Check for leaks in the lubrication
system.
Check the oil level and add oil if the
level is low.
Check the oil pressure switch and
wiring.
Over CrankSDThree unsuccessful starting attempts.Check the fuel supply, spark plug,
and battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service.
Spd Sens FltSDEngine speed sensor has failed or engine
stalled.
Volts L1-L2
High
SD *Generator voltage high. Output voltage exceeds
120% of the system nominal voltage for more
Contact an authorized
distributor/dealer for service.
Contact an authorized
distributor/dealer for service.
than 2 seconds.
Volts L1-L2 LowSD *Generator voltage low. Output voltage falls
below 80% of the nominal system voltage for
more than 10 seconds.
Reduce the load and restart the
generator set.
Model 20RCA/20RCAL only: Check
enclosure thermostat and reset if
tripped. See Section 5.5.
Contact an authorized
distributor/dealer for service.
* Engine cooldown runs before shutting down.
Figure 2-3Controller Fault Messages
TP-7092 8/1825Section 2 Generator Set Operation
Page 26
2.5.5Faults Related to Paralleling
If the PowerSyncr Automatic Paralleling Module (APM)
is used with two 14 kw or two 20 kW generator sets,
additional faults and events related to the paralleling
system may be displayed on the controller and/or in
OnCue Plus. This section lists those faults and events.
See the installation instructions provided with the APM
for additional paralleling information.
Note: Contact an authorized distributor or dealer for
parallelingsysteminstallation,startup,
troubleshooting, or service.
Fault TextDescription
Current A High WarningOver CurrentParalleled10Press AUTO or OFF *
Frequency High WarningOver FrequencyParalleled10Press AUTO or OFF *
Frequency Low WarningUnder FrequencyParalleled10Press AUTO or OFF *
Reactive Power Low WarningLoss of FieldParalleled10Press AUTO or OFF *
Real Power High WarningOver PowerParalleled10Press AUTO or OFF *
Real Power Low WarningReverse PowerParalleled10Press AUTO or OFF *
Voltage L1-L2 High WarningOver VoltageParalleled10Press AUTO or OFF *
Voltage L1-L2 Low WarningUnder VoltageParalleled10Press AUTO or OFF *
BusDeadLiveThe bus is measured to be dead when one of the
generators is supposed to be supplying voltage to the
bus (closed contactor)
BusLiveDeadThe bus is measured to be live when no generators
are connected to it (both contactors open).
CfgModelNumThe two generators that are intended to be paralleled
have incompatible model numbers.
CfgSysVoltThe system voltage of the two generators intended to
be paralleled is not the s ame. Because the system
does not know which voltage is correct, the generators
will not be allowed to start.
ChkngMeterThis generator has paralleled to the other generator
and is verifying that the metering is connected and
establishing the connection direction.
ConCheckFailFailure to Auto-Discover APM connections.Wires 9A and 9B crossed between the
ConCheckingPerforming APM connection auto-discovery.This generator has started in RUN, the
ConNotDetermAPM connection auto-discovery is not complete. This
means that the generator does not know which
contactor is connected to it.
ContactorOkSuccessful auto-discovery of APM connections.Auto-discovery was activated by placing
Bus metering V9A and V9B connections
to V9 of paralleling protection harness are
connected incorrectly.
Bus metering V9A and V9B connections
to V9 of paralleling protection harness
connected incorrectly.
Incorrect configuration of one of the
generators. Different generator types.
The paralleled generator sets must be the
same kW model. (i.e. two 14 kW or two
20 kW models.)
One of the two generators is incorrectly
configured.
Intermittent connections on RBUS network
wiring.
Status message appears the first time the
two generators are paralleled.
generators.
Wires 9A or 9B not connected
other generator is in OFF.
Generators not yet started in RUN with
other generator in OFF. See the APM
instruction sheet for instructions to
perform the auto-discovery procedure.
other generator in OFF and this generator
in RUN.
TP-7092 8/1826 Section 2 Generator Set Operation
Page 27
Fault TextDescriptionPossible Causes *
ErraticSigThe power metering on this controller gives a signal
that is not consistent with the system configuration.
Reversing the power direction does not resolve the
problem.
LossOfComAPMThe Automatic Paralleling Module has stopped
communicating on RBUS. (An APM was detected on
the RBUS network but is no longer communicating.)
LossOfComm2The primary controller has lost communication with the
secondary controller. (A secondary controller was
detected, then communication was lost.)
LossOfFieldThis generator has absorbed more than 25% reactive
power (magnetic excitation current) for 20 seconds
MeteringOkThe generator has verified that the metering is
connected correctly and that the direction is consistent
with expected power direction.
MeterUnknownThis generator does not know if the metering is
connected or the orientation of the connection. This
means that the generators can’t share load accurately
until this information is known.
NoCurrentThe generator has applied load (using the other
generator) and has observed no current on the power
sensing inputs.
SyncFailureThe generator has been attempting to synchronize for
over 2 minutes without success.
* For paralleling system troubleshooting and service, contact an authorized distributor or dealer.
BadwiringtotheCT.
ToomuchtensiononwiresfromtheCTto
the controller.
APM is unplugged.
Primary controller is powered down.
Check the battery connections. See
previous page for more information.
Intermittent connections on RBUS network
wiring. Check RBUS communication
connections.
RBUS disconnected, secondary controller
battery disconnected, updating firmware in
secondary controller, or intermittent RBUS
connections.
Generator voltage on this generator is not
calibrated correctly.
Generator voltage on other generator is
not calibrated correctly.
Bus voltage on this generator is not
calibrated correctly.
Bus voltage on the other generator is not
calibrated correctly.
Status message indicates that the CT is
connected to the generator correctly.
System commissioning and startup not yet
complete. See the APM instructions.
The CT is not connected to the controller.
The output leads from the generator do
not go through the CT in the correct
direction. See the APM instructions.
Generator is hunting.
Advanced speed control settings need
adjustment.
Load is changing frequently to disturb the
online generator.
Figure 2-5Events Related to Paralleling
Generator Set StateDescription
Generator Management OffThis generator has been stopped by generator management because it is not
ProtectiveRelayTrippedContactorThe contactor has been forced to open to protect one of the generators or the
SynchronizingThe generator is actively trying to match frequency, voltage and phase with that of the
UnloadingThe generator is actively trying to transfer load from itself to the other generator.
presently needed to supply the load. The generator is available and will start if it is
needed again.
customer’s load.
paralleling bus.
Figure 2-6Generator Set States Related to Paralleling
TP-7092 8/1827Section 2 Generator Set Operation
Page 28
Notes
TP-7092 8/1828 Section 2 Generator Set Operation
Page 29
Section 3 RDC2 Controller Operation
3.1RDC2 Generator Set/Transfer
Switch Controller
Model RCA and RCAL generator sets are equipped with
the RDC2 generator set/transfer switch controller. See
Figure 3-1 for controller illustrations.
The RDC2 controls the following power system
components:
D Model RCA or RCAL generator set
D Model RXT Automatic Transfer Switch (ATS)
D Load management device
1
D Programmable Interface Module (PIM)
The RDC2 controller features include:
D Two-line x 16 character backlit digital display with
adjustable contrast
D OFF, AUTO, and RUN generator set master control
buttons
D Generator set status indicating LEDs (OFF, AUTO,
RUN)
D Up, Down, and Select buttons for navigation through
menus and adjustments
D Power system indicator LEDs to show utility and
generator source status, and to show which source
(utility or generator) is supplying power to the load
(Model RXT automatic transfer switch is required for
operation of these LEDs.)
3.2Controls and Indicators
Figure 3-1 illustrates the RDC2 controller.See
Figure 3-2 for details of the controller’s user interface.
GM90304
1. User Interface; see Figure 3-2
Figure 3-1RDC2 Controls and Indicators
1
11
10
9
1. 2-line LCD display
2. Up button
3. Select button
4. Down button
5. RUN button and LED
6. Generator power available LED*
7. Building on generator power LED*
8. Building on utility power LED*
9. Utility power available LED*
10. OFF button and LED
11. AUTO button and LED
* These LEDs operate only if a Model RXT automatic transfer
switch is connected.
687
GM77569
2
3
4
5
Figure 3-2RDC2 User Interface
TP-7092 8/1829Section 3 RDC2 Controller Operation
Page 30
3.2.1Controller Keypad
3.2.2LED Indicators
The RUN, OFF, and AUTO buttons control the generator
set as described in Figure 3-3.
Use the Select, Up arrow, and Down arrow buttons to
navigate through the menus and change settings, if
necessary. See Section 2.3 for operation instructions.
LEDs above the RUN, OFF, and AUTO buttons indicate
the mode of operation as shown in Figure 3-4.
Power System LEDs indicate the status of the utility
power and the generator set, and indicate which source
is supplying power to the building (based on the position
of the RXT transfer switch).See Figure 3-2 and
Figure 3-4.
Note: The power system LEDs operate only if a Model
RXT transfer switch is connected.
ButtonButton Function
RUNStarts the generator set. The engine start time delay is ignored.
OFFStops the generator set. The cooldown time delay is ignored.
During the engine crank cycle, pressing OFF will stop the crank cycle.
Press OFF to clear faults and reset the controller.
AUTOPlaces the generator set in Automatic (standby) mode.
Down arrow
Select
Up arrow
Use to navigate through menus and change settings. This manual contains instructions to navigate the
controller menus and adjust settings on the RDC2 controller.
Figure 3-3RDC2 Controller Pushbutton Operation
LEDLED Operation
RUNLights when the generator set has been started locally by pressing the RUN button.
OFF
AUTOLights when the generator is in automatic (standby) mode. Generator set will respond to
Utility Power Available *Lights when utility power is available.
Building on Utility Power *Lights when the building load is connected to utility power through the RXT transfer
Generator Power A vailable *Lights when generator power is available.
Building on Generator Power *Lights when the building load is connected to generator power through the RXT transfer
* These LEDs operate only if a Model RXT transfer switch is connected.
Remote start and stop commands are ignored.
Lights for 2 seconds, then flashes every 2 seconds when the generator set and
controller are off. Remote start/stop commands have no effect. The exercise cycle will
not run.
In Auto mode, OFF LED flashes quickly to indicate a fault shutdown. Attention required.
Identify and correct the fault condition before resetting the controller.
engine start and stop commands from the controller (for example, exercise start and
stop commands) or an ATS. Time delays operate as described in Section 2.3.
The controller is equipped with a two-line x 16 character
backlit digital display with adjustable contrast. Whenthe
generator is running, the controller automatically scrolls
through the displays shown in Figure 3-5. When the
system is in AUTO, the screens shown in Figure 3-6 are
displayed.
When a fault or warning condition exists, the controller
will show the corresponding message. See Section 2.5
for more information about faults.
The display contrast is adjustable.Navigate to the
Genset System menu and step down to the Contrast
screen. Press the Select button, and then use the up
and down arrow buttons to adjust the contrast. See
Section 3.5, Changing Settings, and Section 3.14,
Genset System Menu.
The display backlight turns off after about a minute of no
activity. The backlight turns on when a button is pressed
or when the generator set starts.
Controller menus display power system information,
including status information for the engine, generator,
and optional RBUS accessories, exercise settings, and
event history.Some menus allow changes to the
controller settings. See Sections 3.7 through 3.21 for
menu diagrams.
Active Alert
Genset Status
Running
Voltage: 240V
Freq:60.0Hz
Engine: 72.0 F
Oil Pressure: OK
Active Alert
Genset Status
Standby
Battery
12.3V
Engine Runtime:
24.5 h
Date:02DEC2011
Time: HR:MNpm
Next Exercise:
09:00p 09Dec2011
Battery
12.3V
Engine Runtime:
24.5 h
Date:02DEC2011
Time: HR:MNpm
Figure 3-6Autopaging Displays, Automatic Mode
Sample data shown.
tp6804
Next Maintenance:
150 h or Mar2012
Sample data shown.
Figure 3-5Autopaging Displays, Generator Running
TP-7092 8/1831Section 3 RDC2 Controller Operation
tp6804
Page 32
3.3Controller Power
The RDC2 controller is powered by the generator set
engine starting battery and the built-in battery charger.
Note: To disconnect controller power, disconnect the
utility power to the generator set and disconnect
the battery.
If controller power is disconnected and reconnected,
you will be prompted to set the language, time, date, and
exerciser. The first setting will flash. Press the Up and
Down arrow buttons to change the setting. Press Select
to save the setting and move on to the next. Repeat until
all settings are saved and the controller returns to the
main menu.See Section 3.5 for more detailed
instructions to change settings on the RDC2.See
Section 3.6 for more detailed instructions to set the
exerciser or change the exercise settings.
3.4Battery Charging
The controller includes a built-in battery charger to
maintain the engine starting battery.The RDC2
controller monitors the battery voltage and provides a
constant 13.4 ±2% VDC voltage and maximum 2.5
amps to charge the battery.
The installer must connect utility power provided from
the building on a breaker-protected circuit for the built-in
battery chargeras describedin the generator
Installation Manual.
3.5Changing Settings
The following procedure explains how to change
settings. See Figure 3-7 for an example using the Date
and Time settings.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select
button can enable editing of the controller
settings.Changing the settings to incorrect
values can adversely affect generator set
operation or render the unit inoperable.
Procedure to Change Settings
1. Press the Select button to enter the main menu.
2. Press the down arrow button until the desired menu
is displayed. The Genset System menu is used for
this example. See Figure 3-9.
3. Press the Select button to enter the genset system
displays. See Figure 3-7.
4. Press the down arrow button to step through the
generator set system settings.
5. To change any of the genset system settings, press
the Select button. The selected setting flashes.
6. Press the up or down arrow buttons to increase or
decrease the setting.
7. When the desired setting is shown, press Select.
The value stops flashing. If there are additional
adjustable settings on the screen, the next setting
flashes. For example, in the date menu, the day,
month, and year can be adjusted.
Some settings can be changed from the controller
keypad.The controller settings and generator set
output are factory-set and should not require field
adjustment under normal circumstances. Check and
adjust the settings and/or output when:
D The controller has been replaced.
D The voltage requires adjustment for a particular
application.
D Troubleshooting generator set problems.
Have controller setup and adjustment performed only by
anauthorizeddistributor/dealerorauthorized
representative.
8. Repeat steps 6 and 7 for each setting on the
screen.
9. Press the down arrow to step to the next screen.
10. To exit, press the down arrow button until Return is
displayed.Press the Select button to exit the
menu.
11. Press the AUTO or OFF button to exit the main
menu.
Note: If no buttons are pushed, the controller exits the
menus and returns to the generator set status
display after 5 minutes.
1. Press the Select button to enter the main menu.
Press:Display:
Overview -- -->
1.2 h
2. Press the down arrow button until the desired
menu is displayed. See Figure 3-9. Date and Time
are used for this example.
Press:
Display:
D a t e-- -- >
and Time
3. Press the Select button to enter the Date and Time
menu.
Press:Display:
Date:
05Dec2011
4. To change the date and time settings, press the
Select button again. The year will flash.
8. When the correct date is shown, press the Select
button. The saved date is shown.
Press:Display:
Date:
03Jan2012
9. Press the down arrow button to step to the next
menu.
Press:Display:
Time:
01:49pm
10. Repeat steps 5 and 6, using the arrow and select
buttons to set and save the time.
Note: To change from am to pm, press the up arrow
key to increase the hour until the correct hour
and pm is displayed.
11. In the time format menu, press Select and then
press the up or down arrow button to change the
format, 12 hr. or 24 hr. Press Select to save the
displayed format.
Press:Display:
Date:
05Dec2011
5. Press the up or down arrow buttons to change the
year.
Press:
OR
Display:
Date:
05Dec2012
6. When the correct year is shown, press the Select
button. The year is saved and the next setting
(month) flashes.
Press:Display:
Date:
05Dec2012
7. Repeat steps 5 and 6, using the arrow and select
buttons to set the month and the date.
Figure 3-7Changing Settings
12. Press the down arrow button.Return is
displayed.
Press:Display:
<---- Return
13. Press Select to return to the Date and Time
menu.
Press:Display:
Date---->
and Time
14. Press the Up or Down arrow buttons to step to a
different menu.
15. Press Auto to signal the controller to exit the
menus and return to the generator set status
display.
Press:
Display:
AUTO
Genset State
Standby
Note: If no buttons are pressed, the controller returns
to the status display after 5 minutes.
TP-7092 8/1833Section 3 RDC2 Controller Operation
Page 34
3.6Setting the Exerciser
Set the exerciser to automatically run the generator set
for 20 minutes every week or every two weeks.
3.6.1Setting the Exerciser at Controller
Power-up
When battery power is connected to the controller, you
will be prompted to set the language, date and time, and
then to set the exerciser.
The first setting will flash. Press the Up and Down arrow
buttons to change the setting. Press Select to save the
setting and move on to the next. See Section 3.5 for
more detailed instructions to change settings on the
RDC2.
If the battery is disconnected and reconnected during
generator set maintenance or service, the time, date,
and exercise settings will need to be re-entered.
3.6.2Changi ng the Exercise Settings
This section explains how to change the exercise
settings after the initial setup.
Follow the procedure below and see the flowchart in
Figure 3-8 to set the exercise time and date, mode, and
frequency.
7. Press the Select button. The setting flashes to
show that it can be changed. For example, HR
flashes to show that the hour can be changed.
8. Press the Up or Down arrow buttons to change the
setting.
9. Press the Select button to save the setting and
move to the next. For example, save HR setting
and move to MN.
10. Repeat steps 5 through 9 to change the next item
on the line until the desired settings are displayed.
11. Press Select to save after all settings have been
selected. Settings will stop flashing.
12. If the generator set is connected to a Kohlerr Model
RXT transfer switch, the exercise can be changed
to a loaded exercise. Set the Exercise Mode to
Unloaded Cycle, Unloaded Full, or Loaded Full
(RXT ATS required) as shown in Figure 3-8.
Unloaded Cycle is recommended. See Sections
2.4.2 through 2.4.4 for information about the
exercise modes.
13. Set the exercise frequency (weekly or every two
weeks). Weekly exercises are recommended.
14. Press the down arrow button to step to the Return
menu. Press the Select button to return to the main
menu.
Procedure to Set the Exerciser
1. Press the AUTO button on the controller.
2. Press the Select button to go to the main menu.
SeeFigure3-9.
3. Press the down arrow button to step to the Genset
System menu.
4. Press the Select button to enter the Genset system
menu. See Figure 3-8.
5. Use the down arrow button to step to the Next
Exercise menu.If the exerciser is not set, No
Exercise Scheduled will be displayed.
6. Press and HOLD the Select button to enable
editing.
After a scheduled exercise run, the next exercise time
and date will be updated automatically based on the
Exercise Frequency setting.
Other transfer switches: For a loaded exercise with a
transfer switch other than a Kohlerr Model RXT ATS,
refer to the transfer switch operation manual for
instructions.
Exerciser Reset
To reset the exerciser to run at a different day and/or
time or to change the exercise mode, follow the
procedure in Section 3.6.2 to change the exerciser
settings.
* If the exerciser has not been set, No Exercise Sch will be displayed.
Figure 3-8Procedure to Set the Exerciser on the RDC2 Controller
TP-7092 8/1835Section 3 RDC2 Controller Operation
tp6804
Page 36
3.7RDC2 Controller Menus
Controller menus display power system information,
including status information for the engine, generator,
and optional RBUS accessories, exercise settings, and
event history.Some menus allow changes to the
controller settings. Status information, including the
engine runtime, cannot be changed by the operator.
Diagrams in the following sections show how to navigate
through the menus.The diagrams show sample
settings. Settings for your application may vary.
If a setting on the controller display is flashing, edit mode
has been enabled. Press the OFF or AUTO button to
exit the edit mode.
3.8Main Menu
Press the Select button once to bring up the main menu.
Overview is displayed. See Figure 3-9. Press the down
arrow button to step to the next menu, Engine Metering.
Use the UP and DOWN arrow buttons to step up and
down through the menus shown in Figure 3-9.
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select
button can enable editing of the controller
settings.Changing the settings to incorrect
values can adversely affect generator set
operation or render the unit inoperable.
The controller will exit the main menu after 5 minutes if
no buttons are pressed.To exit the main menu
immediately, press the controller’s OFF or AUTO
button.
Press the Up and Down arrow buttons
to move between menus.
Press OFF or AUTO to exit the menus.
Engine---->
Metering
Generator---- >
Metering
Genset---->
Information
Genset---->
Run Time
Genset---->
System
ATS-- -->
Status
ATS- -- ->
Configuration *
D a t e-- -- >
and Time
Network ---->
Information
PIM-- -->
Status [
Load---->
Control ]
Event Log---->
* ATS Configuration appears only if a Model RXT transfer switch is connected.
[ PIM Status appears only if a programmable interface module is connected.
] Load Control appears only if a load management device is connected.
Figure 3-9RDC2 Main Menu
tp6804
TP-7092 8/1837Section 3 RDC2 Controller Operation
Page 38
3.9Overview Menu
Overview -- -->
1.2 h
Active Alert
(if any)
3.10 Engine Metering Menu
The engine metering menu displays engine status
information as shown in Figure 3-11.This menu
displays status information only. No settings can be
changed from this menu.
The generator metering menu displays the generator
voltage and frequency. See Figure 3-12.
Generator ---->
Metering
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
servicedbyqualifiedelectrical
personnel.
The voltage calibration mode can be entered from the
Generator Metering menu. Contact a Kohler-authorized
distributor/dealerdealer for service.
The Reset Calibration menu allows you to set the
voltage reading back to the original value after
calibration, if necessary. See Figure 3-12.
Three-phase
Volts L1--L2:
Volts L2--L3:
Volts L3--L1:
Frequency:
240 V
240 V
240 V
60.0 Hz
Volts:
Frequency:
Reset
Calibration
<---- Return
Single-phase
Note: Actual settings may vary.
240 V
60.0 Hz
Reset
Calib? No
Reset
Calib? Yes
Figure 3-12 Generator Metering Menu
TP-7092 8/1839Section 3 RDC2 Controller Operation
tp6810
Page 40
3.12 Generator Set Information
Menu
The generator set model number and serial numbers
are displayed. No changes are allowed from this menu.
Model and serial numbers are factory set and should not
require changes in the field, except in the event that the
controller is being replaced.A personal computer
running Kohler SiteTech software is required to enter the
generator set model number and serial numbers on a
replacement controller. Contact an authorized Kohler
distributor/dealer for service.
Genset ---->
Information
Genset M/N:
20RCA
Genset S/N:
########
3.13 Genset Run Time Menu
The data shown in Figure 3-14 are displayed.No
changes are allowed from this menu.
Eng Runtime displays the total number of hours that the
generator set engine has run.The runtime is not
resettable.
The Next Maintenance menu shows the number of
hours of generator set operation until maintenance is
required. The e stimated date for the next scheduled
maintenance is also displayed.The maintenance
reminderintervalsarebasedontheengine
manufacturer’s recommendation for changing the oil.
Refer to Section 4, Scheduled Maintenance, for
maintenance instructions.
Afterchangingtheoilandperformingother
recommended maintenance, go to the Overview menu
to reset the maintenance timer. See Section 4.2.5 for
instructions to reset the maintenance timer.
The genset system menu displays the system
information shown in Figure 3-15. Generator sets are
factory set and should not require changes to the system
settings in the field.
A Kohler authorized distributor or dealer can adjust
these settings, if necessary. If the generator set is
reconnected to a different voltage or the system settings
require adjustment for some other reason, see Section
3.5 for instructions to enable editing and change the
system settings.
adjust the contrast. Press the Select button to save the
contrast setting.
Genset---->
System
System Voltage:
240 V
System Freq:
60 Hz
Note: Use caution when navigating the controller
menus. In some menus, pressing the Select
button can enable editing of the controller
settings.Changing the settings to incorrect
values can adversely affect generator set
operation or render the unit inoperable.
Voltage Regulator (VR) Voltage Adj
The generator set voltage is factory set and typically
does not require adjustment in the field. If voltage
adjustment is required, contact a Kohler authorized
distributor or dealer for service. Refer to the generator
set Installation Manual for instructions to adjust the
voltage.
Fuel Type
The fuel type, LP or natural gas, is shown. Do not
change the fuel type in this menu unless the generator’s
fuel system has been converted by an authorized
distributor or dealer.
Setting the Exerciser
Use the Genset System menus to set the generator set
exerciser. Refer to Section 2.4 for instructions to set the
exerciser and for more information about exercising the
generator set.
VR Voltage Adj:
240.0V
System Phase:
Single
System Battery:
12 V
Fuel Type
LP
Next Exercise
06:30p 15Dec2011
Exercise Mode:
Unloaded Variable
Exercise Freq:
Weekly
Language:
English
After a scheduled exercise run, the Next Exercise time
and date will be updated automatically based on the
Exercise Frequency setting.
Language
Controllers can be set for the following languages:
Meas System:
English
Contrast:
50
English, French, Spanish, Dutch, or German.
Adjusting the Display Contrast
To adjust the display contrast, use the down arrow
button to step to the Contrast menu. Press the Select
button, and then use the up and down arrow buttons to
TP-7092 8/1841Section 3 RDC2 Controller Operation
Note: Actual settings may vary.
Figure 3-15 Genset System Menu
<---- Return
tp6804
Page 42
3.15 ATS Status Menu
ATS menus appear if a Model RXT transfer switch is
connected to the generator set. If no transfer switch is
connected, or another model ATS is connected to the
engine start connections, Remote ATS is displayed on
the ATS Status screen.
The ATS Status menu displays Model RXT transfer
switch and source information.
The voltage shown in these menus can be calibrated.
Follow the safety precautions at the beginning of this
manuals. Use a voltmeter to measure the line-to-line
voltage and follow the instructions in Figure 3-16 to
calibrate the voltage readings.
ATS- --->
Status
ATS Position:
Normal
Normal Status:
Not/Acceptable
Emerg. Status:
Standby
Single-phase
Normal Volts:
Normal Freq.:
Emerg Volts:
240.0 V
60.0 Hz
240.0 V
Note: If there is no Model RXT transfer
switch connected to the generator set,
Remote ATS is displayed and the other
screens on this page do not appear.
Note: The ATS Configuration menu appears only if a
Model RXT transfer switch is connected.
Use the ATSConfiguration submenu to check the Model
RXT transfer switch system settings and time delays,
and change the settings, if necessary.
Changing ATS Configuration Settings
To enable editing, press the select button. The value
flashes to indicate that it can be changed. Press the up
and down arrow buttons to change the value. Press the
Select button to save the value shown.
Use the up and down arrow buttons to move to the next
value to be changed. Repeat the adjustment process
until all values are correct.
Press the down arrow until Return is displayed. Press
the select button to return to the main menu.
ATS - -- ->
Configuration
Normal Freq:
60 Hz
Normal Voltage:
240 V
Emerg. Freq:
60 Hz
Emerg. Voltage:
240 V
Emergency Start:
3sec
Xfer frm Normal
3sec
Xfer from Emerg:
120 sec
<---- Return
Note: Actual settings may vary.
Figure 3-17 ATS Configuration Menu
tp6810
TP-7092 8/1843Section 3 RDC2 Controller Operation
Page 44
3.17 Date and Time Menu
The date and time will typically be set at controller
power--up. To change the date, time, o r time format
(12 hour or 24 hour), use the Date and Time menu.
See Figure 3-18.
3.18 Networking Information Menus
Date and
Time
Date:
02Dec2011
Time:
12:34pm
Use the networking menus to view and adjust
communication settings for systems with remote RBUS
devices such as a PIM or load shed kit, and for systems
thatusetheKohlerOnCuerPlusGenerator
Management System.
RBUS is a proprietary RS-485 communications
protocol.
The Networking Information menu leads to submenus
for network and RBUS communication settings.
Networking---->
Information
Networking---->
Status
Networking---->
Configuration
RBUS---->
Information
Time Format:
12hr|24hr
<---- Return
To change the date and time, press the Select button
See Figure 3-7 for instructions.
The Networking Status submenu contains settings for
OnCuer. Changes to these settings are not typically
required.
If DHCP is enabled, IP parameters are not displayed. If
DHCP is disabled (i.e., if a static IP address is used), the
IP parameters are displayed.
To enable or disable DHCP and change the IP settings,
go to the Networking Configuration menu.See
Section 3.18.2.
Networking---->
Information
Networking---->
Status
OnCue Status:
Connected
DHCP:
Enabled
IP Address:
123.456.789.123
Subnet Mask:
123.456.789.123
Gateway:
123.456.789.123
DNS 1:
123.456.789.123
DNS 2:
123.456.789.123
Ethernet Status:
Disconnected
OnCue Server:
123.456.789.123
<---- Return
Figure 3-20 Network Status Submenu
TP-7092 8/1845Section 3 RDC2 Controller Operation
tp6804
Page 46
3.18.2Networking Configuration
Submenu (OnCue Password)
The Networking Configuration menu includes settings
used for communication with the Kohler OnCuer Plus
Generator Management System.
Password
Note: Use the OnCue password shown on the
controller display for OnCue or OnCue Plus
applications.
For the initial OnCue Plus setup, you will be required to
reset the OnCue password on the RDC2 controller, and
then enter it into the OnCue Plus application. To reset
the password, follow the instructions in Figure 3-21.
reset after the OnCue Plus system has been set up, the
connection will be lost. Disconnect the battery power to
the controller, wait a minute, then reconnect power.
DHCP Submenu
For most applications, the Dynamic Host Configuration
Protocol (DHCP) is enabled and the IP settings cannot
be changed from the controller keypad. If DHCP is
enabled, IP parameters are not displayed.
If DHCP is disabled (i.e., if a static IP address is
required), then the IP parameters can be modified. For
applications that require a static IP address, press and
hold the select button to enable editing, press the down
arrow to disable DHCP, and then step to the next
parameters and enter the information. See Figure 3-21.
Note: The password is displayed for only 10 seconds.
Be sure to write down the password and serial
number.
A new password is generated each time the reset
password procedure is performed. If the password is
If an error occurs while setting a parameter, an error
message is displayed and then the controller exits the
edit mode. Previous settings are preserved.
Press Select to enter YES
or NO as displayed. New
password is displayed for
approximately 10 seconds.
S/N: 1234567
New PW: 12345
HOLD
DHCP:
Disabled
UP arrow to enable,
Down arrow to disable.
IP Address:
123.456.789.123
<---- Return
Figure 3-21 Networking Configuration Submenu
Subnet Mask:
123.456.789.123
Gateway:
123.456.789.123
DNS 1:
123.456.789.123
DNS 2:
123.456.789.123
tp6804
TP-7092 8/1847Section 3 RDC2 Controller Operation
Page 48
3.18.3RBUS Information
D Model RXT transfer switch
The RBUS Information menu contains settings for
remote modules that communicate with the RDC2
controller using RBUS protocol.This includes the
following optional modules:
Check the status of remote devices communicating
through RBUS. Device types can include:
D Model RXT ATS
D Programmable Interface Module (PIM)
D Loadshedkitorcombinedinterface/load
management board on a Model RXT transfer switch
D PowerSyncr Automatic Paralleling Module (APM)
From Figure 3-22:
R e m o t e-- -- >
Devices
The serial number for the RBUS module is shown on the
circuit board inside the module enclosure.
S/N: XXXXXXXXX
<<*DeviceType*>>
Module Status:
Connected
Comm. Errors:
12345
Comm. Timeouts:
12345
Module ID:
12
Firmware Ver.:
4.07
(Dis)Connected:
MM/DD/YY 12:12
S/N: XXXXXXXXX
<<*DeviceType*>>
Connected: Displays the date and time that the
device was connected.
Disconnected: Displays the last date and time of
successful communication.
<---- Return
R e t u r n-- -- >
Figure 3-23 Remote Devices Submenu
TP-7092 8/1849Section 3 RDC2 Controller Operation
tp6804
Page 50
3.19 Programmable Interface
Module (PIM) Status Menu
The PIM status menu displays the status of inputs and
outputs connected to the programmable interface
module (PIM).this menu appears only if a PIM is
connected. Thisis a status display menu only. Input and
output settings cannot be changed from the RDC2
controller’s user interface.
A personal computer running Kohler SiteTecht
software is required to change the input and output
settings. Contact an authorized distributor or dealer for
service.
The Kohlerr OnCuer Plus Generator Management
System can be used to turn outputs on and off. See the
OnCue Plus Operation Manual for instructions.
PIM
Status:
P I M 1-- -- >
<---- Return
Input 1
In/Active
Input 2
In/Active
Output 1:
In/Active
Output 2:
In/Active
Output 3:
In/Active
Output 4:
In/Active
Output 5:
In/Active
Output 6:
In/Active
<---- Return
Figure 3-24 Programmable Interface Module (PIM) Status Menu
The Load Control menu displays the status of the load
management device inputs and outputs, and allows a
test of the load control output relays. This menu appears
only if a load management device (load shed kit or
Model RXT transferswitch with thecombined
interface/load management board) is connected.
Generator current is displayed as a percent of the
maximum generator capacity. The load control module
adds and sheds loads based on the generator current.
The test function cycles the relays in the order of their
priority. For detailed information, refer to the instructions
provided with the load shed kit. For the RXT combined
interface/load management board, refer to the RXT
automatic transfer switch Operation and Installation
Manual.
Load---->
Control
Generator
Current:123 %
Load---->
Control 1
<---- Return
Test Outputs
Push Select
Input 1:
In/Active
Input 2:
In/Active
Output 1:
Add/Shed
Output 2:
Add/Shed
Output 3:
Add/Shed
Output 4:
Add/Shed
(blinking)
Output 5:
Add/Shed
Output 6:
Add/Shed
<---- Return
Figure 3-25 Load Control Status Menu
TP-7092 8/1851Section 3 RDC2 Controller Operation
tp6810
Page 52
3.21 Event Log
The event log displays up to 1000 controller faults and
notices, starting with the most recent event. Events are
numbered 1--1000, with 1 being the most recent. Each
event is displayed with the date and time of the event,
the number of the event, a code to indicate whether the
eventwas awarning ( W),shutdown(S), or
informational notice (I ), the engine hours at the time of
the event, and the event description.
The time and date for notices (I) are not stored in the
controller.
Procedure to View Event History
1. Press Select to enter the main menu.
2. Press the down arrow to step down to the event log.
3. Press Select to display the most recent event.
4. Press the down arrow to step to the next event.
5. Use the up and down arrow buttons to view events.
Date MO/DA/YEAR
Event Log ---->
Press UP and Down arrow
buttons to scroll through events
Press Select button at any time to
return to the main menu.
time HR:MN
event number, W/S/I, engine hours
event name
Date MO/DA/YEAR
time HR:MN
event number, W/S/I, engine hours
event name
Figure 3-26 Event Log
tp6810
6. Press the Select button to exit the event log.
To stop viewing the event history before the last event,
press the select button to return to the main menu.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
workingon thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
DANGER
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the exhaust system.Hot parts can cause
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
4.1Scheduled Maintenance
Refer to the following service schedules and the runtime
hours displayed on the controller to schedule routine
maintenance. Intervals are shown in hours of operation
and/or time intervals (i.e. weekly, monthly, quarterly,
etc.) Have an authorized dist ributor/dealer service the
generator set at the designated intervals in the service
schedule for the life of the generator set. Service units
subject to extreme weather, long operating hours, or
dusty or dirty conditions more frequently.
Hazardous voltage. Moving parts.
Will cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
Contact an authorized distributor/dealer for parts.
TP-7092 8/1853Section 4 Scheduled Maintenance
Page 54
4.1.1Service Schedule, 14 kW Models
Procedure
See
System Component or Procedure
Section
Fuel
Flexible lines and connectionsXRQuarterly
Main tank supply levelXWeekly
Fuel pipingXYearly
Lubrication
Oil level
Crankcase breather hoseXYearly or 500 hours
Change oilXYearly or 100 hours
Replace filterXYearly or 200 hours
Cooling
Air ducts, louversXXYearly
Exhaust Line
LeakageXXWeekly
Insulation, fire hazardsXYearly
Obstructions or combustible materials near exhaust
outlet
DC Electrical System
Check battery charger operation, charge rateXMonthly
Remove corrosion, clean and dry battery and rackXXYearly
Clean and tighten battery terminals and inspect
boots
Battery electrolyte level and specific gravity *XYearly
4.2
4.5
4.6
4.7
AC Electrical System
Tighten control and power wiring connectionsXYearly
Remote control system, if equippedXMonthly
Visible wear or damageXQuarterly
Wire abrasions where subject to motionXXSix Months
Wire-cable insulation conditionX3 Years or 500 hours
Engine and Mounting
Visible wear or damageXWeekly
Air cleaner service [
Spark plugs4.3
Replace stepper motor coupling and bushingD500 hours
4.4
Generator
Visible wear or damageXQuarterly
Exercise generator setXWeekly
Brushes and collector ringDDYearly or 300 hours
Measure and record resistance readings of
windings with insulation tester (Meggerr,with
SCR assembly or rectifier and load leads
disconnected) *
General Condition of Equipment
Evidence of vibration, leakage, excessive noise,
temperature, or deterioration
Interior of sound enclosureXXQuarterly
* Not necessary for maintenance-free batteries.
[ Service more frequently under extremely dusty/dirty conditions.
Meggerr is a registered trademark of Biddle Instruments.
Visually
Inspect
XAction
D Authorized distributor/dealer only
R Replace as necessary
Remove corrosion, clean and dry battery and rackXXYearly
Clean and tighten battery terminals and inspect
boots
Battery electrolyte level and specific gravity *XYearly
4.2
4.5
4.6
4.7
AC Electrical System
Tighten control and power wiring connectionsXYearly
Remote control system, if equippedXMonthly
Visible wear or damageXQuarterly
Wire abrasions where subject to motionXXSix Months
Wire-cable insulation conditionX3 Years or 500 hours
Engine and Mounting
Visible wear or damageXWeekly
Air cleaner service [
Spark plugs4.3150300
Replace stepper motor coupling and bushingD500 hours
4.4150300
Generator
Visible wear or damageXQuarterly
Exercise generator setWWeekly
Brushes and collector ringDDYearly or 300 hours
Measure and record resistance readings of
windings with insulation tester (Meggerr,with
SCR assembly or rectifier and load leads
disconnected)
General Condition of Equipment
Evidence of vibration, leakage, deterioration,
unusual or excessive noise or temperature
Interior of sound enclosureXXQuarterly
* Not necessary for maintenance-free batteries.
[ Service more frequently under extremely dusty/dirty conditions.
Meggerr is a registered trademark of Biddle Instruments.
Visually
Inspect
Check ChangeCleanTest
X
XX
D3 Years
XXXWeekly
XAction
DAuthorized distributor/dealer
only
RReplace as necessary
Frequency
engine operation
Yearly or hours
Weekly
Yearly
shown
TP-7092 8/1855Section 4 Scheduled Maintenance
Page 56
4.2Lubrication System
4.2.2Oil Check
See the service schedules in Section 4.1 for oil change
and oil filter replacement intervals. See the service
views in Section 1.8 for the oil drain, oil check, oil fill, and
oil filter locations.
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
workingon thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
WARNING
The generator set is shipped with oil. Before operating
the generator set, check the engine oil in the crankcase.
To check the oil level, shut down the generator set and
wait several minutes. Remove the dipstick and wipe the
end clean, reinsert, and remove.See Figure 4-1.
Maintain the oil level between the Add and Full marks on
the dipstick. Add 5W-30 or 10W-30 synthetic oil when
the oil level is low.
Check the oil level before each use. For extended
operation, check the oil level every 8 hours. Do not
check the oil level when the generator set is running.
6515
Figure 4-1Oil Check (typical)
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
4.2.1Low Oil Pressure Shutdown
The low oil pressure (LOP) shutdown feature protects
the engine against internal damage if the oil pressure
drops below a minimum pressure because of oil pump
failure or other malfunction.
Note: The LOP shutdown feature does not protect
against damage caused by operating when the
oil level is low; it is not a low oil level shutdown.
Check the oil level regularly, and add oil as
needed.
4.2.3Engine Oil Recommendation
Use 5W-30 or 10W-30 API (American Petroleum
Institute) Service Class SG, SH, or SJ synthetic oil.
Synthetic oil oxidizes and thickens less than other oils
and leaves the engine intake valves and pistons cleaner.
TP-7092 8/1856 Section 4 Scheduled Maintenance
Page 57
4.2.4Oil Change Procedure
3. Fill with oil.
Note: Dispose of all waste materials (engine oil, fuel,
filter, etc.) in an environmentally safe manner.
Drain the oil while it is still warm.
1. Drain the oil.
a. Press the OFF button on the generator set
controller.
b. Disconnect the utility power to the generator
set.
c. Disconnect the generator set engine starting
battery, negative (--) lead first.
d. Remove the end panels from the enclosure by
lifting the panels up and out. Then lift off the
service-side panel to access the oil drain valve
and hose.
e. Clean the area around the dipstick and oil fill
cap.
f. Remove the oil drain hose from its retaining
clip. Remove the cap from the oil drain hose
and lower the hose into an oil collection
container.
Note: When the oil is drained, some oil remains in the
engine. The amount of oil needed to refill the
engine may be less than the capacity shown in
Figure 4-2. Use the dipstick shown in Figure 4-1
to check the oil level during the fill. Do not fill past
the full mark on the dipstick.
Note: See Section 4.2.3 for the recommended oil type.
Generator Set ModelOil Capacity, L (qt.)
14 kW1.8 (1.9)
20 kW1.9 (2.0)
Figure 4-2Engine Oil Capacity
a. Add oil through the oil fill port; see Figure 4-3.
b. Use the dipstick to check the oil level before
starting to add the final quart of oil. Fill the
engine to the F mark on the dipstick.
c. Reinstall the dipstick and the oil fill cap.
1
g. Open the oil drain valve on the engine.
h. Remove the dipstick and oil fill cap. Allow time
for the engine oil to drain completely.
i. Close the oil drain valve. Replace the cap on
the oil drain hose. Replace the oil drain hose in
its retaining clip.
j. Replace the dipstick.
2. Replace the oil filter.
a. Clean the area around the oil filter.
b. Loosentheoilfilterbyrotatingit
counterclockwise with an o il filter wrench. On
20 kW models, allow the oil to drain from the
filter. Then remove the o il filter.
c. Clean the gasket sealing surface of the oil filter
adapter.
d. Apply a light coat of clean oil to the rubber seal
of the new oil filter.
e. Install the new oil filter following the instructions
provided with the filter.
3
2
Note: 20 kW model shown; 14 kW model is similar
1. Dipstick
2. Oil cooler located under shroud (20 kW only)
3. Oil fill location
Figure 4-3Oil Fill Components
img1062
TP-7092 8/1857Section 4 Scheduled Maintenance
Page 58
d. Reconnect the generator set engine starting
battery, negative (--) lead last.
e. Reconnect the utility power to the generator
set.
4.2.6Oil Cooler (20RCA/RCAL only)
Inspect and clean the oil cooler at the intervals indicated
in the service schedule. The oil cooler must be kept free
of debris.
f. Press the RUN button on the generator set
controller. The generator set will start.
g. Run the generator set for a minute to allow the
oil pressure to reach operating range.
h. Stop the generator set, wait 1 minute, and then
recheck the oil level. Add oil to bring the level
up to the F mark on the dipstick.
4. Check for leaks.
a. Check for oil leaks.
b. Fix leaks and recheck the oil level.
c. Reinstall the housing side panel.
5. Reset the maintenance timer on the controller.
4.2.5Resetting the Maintenance Timer
1. From the Overview menu, step down to the Genset
Run Time menu.
2. Press the Select button and then step down to the
Next Maintenance screen.
3. Press the Select button.
See Figure 4-3 and Figure 4-4for the oil cooler location.
The oil cooler is located under the No. 2 cylinder shroud.
Remove the top mounting screw and loosen the two side
screws, then lift off the cylinder shroud.
Clean the outside of the oil cooler fins with a brush or
with compressed air.
Note: See Figure 4-3 for location.
1. Oil cooler
1
62 590 01
Figure 4-4Oil Cooler
4. Press the Up arrow button so that “Reset Maint
Timer? Yes” is displayed.
5. Press the Select button.After about twominutes, the new maintenance interval and date
are displayed.
TP-7092 8/1858 Section 4 Scheduled Maintenance
Page 59
4.3Spark Plugs
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
workingon thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
3. Check the spark plug gap using a wire feeler
gauge.See Figure 4-5 for the recommended
spark plug gap. Adjust the gap by carefully bending
the ground electrode.See Figure 4-6 and
Figure 4-7.
4. Reinstall the spark plug into the cylinder head.
Torquethesparkplugto24.4--29.8 Nm
(18--22 ft. lb.)
Generator Set ModelSpark Plug Gap
14 and 20 kW models0.76 mm (0.030 in.)
Figure 4-5Spark Plug Gap
1--514
Figure 4-6Checking the Spark Plug Gap
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Reset the spark plug gap or replace the plugs with new
plugs as necessary.
1. Clean the area around the base of the spark plug to
keep dirt and debris out of the engine.
2. Remove the spark plug and check its condition.
Replace the spark plug if it is worn or if its reuse is
questionable.
1--511
Figure 4-7Adjusting the Spark Plug Gap
TP-7092 8/1859Section 4 Scheduled Maintenance
Page 60
4.4Air Cleaner Service
WARNING
Risk of fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden backfire can cause
severe injury or death. Do not operate the generator set with
the air cleaner removed.
Air Cleaner Service
Use the following procedure to replace the paper
element at the intervals specified in the service
schedule. Replace the paper element more often under
extremely dusty or dirty conditions.
1. Press the OFF button on the generator set
controller.
2. Disconnect the utility power to the generator set.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Loosen the cover retaining knob and remove the
cover.
4.4.1Air Cleaner, 14 kW Models
The engine has a replaceable high-density paper air
cleaner element. See Figure 4-8.
1
2
3
4
5
6
586536
1. Cover knob
2. Air cleaner cover
3. Element cover nut
4. Element cover
5. Air cleaner element
6. Air cleaner base
5. Remove the element cover nut, element cover,and
the paper element.
Note: Do not wash the paper element or clean it
with pressurized air, as this will damage the
element.
6. Replace the element if it is dirty, bent, or damaged.
7. Check the air cleaner base. Make sure it is secure
and not bent or damaged. Also check the element
cover for damage and fit. Replace all damaged air
cleaner components. Remove any loose dirt or
debris from the air cleaner base. Wipe the base
carefully so that no dirt drops into the intake throat.
Check the condition of the rubber seal on the air
cleaner stud and replace the seal if necessary.
8. Reinstall the paper element, element cover,
element cover nut, and the air cleaner cover.
Secure the cover with the cover retaining knob.
9. Reconnect the utility power to the generator set.
10. Reconnect the generator set engine starting
battery, negative (--) lead last.
Figure 4-8Air Cleaner Components
Check for a buildup of dirt and debris around the air
cleaner system. Keep this area clean. Also check for
loose or damaged components. Replace all bent or
damaged air cleaner components.
Note: Operating the engine with loose or damaged air
cleaner components could allow unfiltered air
into the engine causing premature wear and
failure.
TP-7092 8/1860 Section 4 Scheduled Maintenance
Page 61
4.4.2Air Cleaner, 20 kW Models
Air Cleaner Service
The engine is equipped with a replaceable, high density
paper air cleaner element. See Figure 4-9.
1
2
3
4
tp6515
1. Knobs (qty.2)
2. Cover
3. Paper element
4. Base
Figure 4-9Air Cleaner Components
Check the air cleaner daily or before starting the engine.
Check for a buildup of dirt and debris around the air
cleaner system. Keep this area clean. Also check for
loose or damaged components. Replace all bent or
damaged air cleaner components.
Note: Operating the engine with loose or damaged air
cleaner components could allow unfiltered air
into the engine causing premature wear and
failure.
Replace the paper element at the intervals indicated in
the service schedule. See Section 4.1.2 for the service
schedule.See Figure 4-9 for the air cleaner
components.
1. Loosen the two cover retaining knobs and remove
the cover.
2. Remove the paper element.
3. Do not wash the paper element or use pressurized
air, as this will damage the element. Replace a
dirty, bent, or damaged element.Handle new
elements carefully; do not use if the sealing
surfaces are bent or damaged.
4. When servicing the air cleaner, check the air
cleaner base. Make sure it is secured and not bent
or damaged. Also, check the element cover for
damage or improper fit. Replace all damaged air
cleaner components.
Note: If any loose dirt or debris fell on the air cleaner
base when the element was removed, carefully
remove it and wipe the base clean. Be careful that
none of it drops into the intake throat.
5. Reinstall the paper element onto the air cleaner
base. Make sure the element is flat and properly
seated.
6. Install the air cleaner cover and secure with the two
retaining knobs.
7. When element replacement is necessary, order
genuine Kohler parts.
TP-7092 8/1861Section 4 Scheduled Maintenance
Page 62
4.5Cooling System
The engine fan draws cooling air through the openings
in the sides and end near the battery. The alternator fan
draws cooling air through openings on the side walls of
the enclosure. The cooling air mixes with the engine
exhaust and is discharged at the exhaust outlet. See the
service view in Section 1.8 for air intake and exhaust
locations. To prevent generator set damage caused by
overheating, keep the housing cooling inlets and outlets
clean and unobstructed at all times.
4.7Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Note: Do not block the generator set cooling air inlets or
mount other equipment above them. Overheating
and severe generator damage may occur.
4.6Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
Theexhaustsystemmust be
leakproof and routinely inspected.
Remove all combustible materials from the exhaust
location.Combustiblematerialsinclude building
materials as well as natural surroundings. Keepdry field
grass, foliage, and combustible landscaping material a
minimum of 1.2 m (4 ft.) from the exhaust outlet.
Periodically inspect the exhaust system components for
cracks, leaks, and corrosion.
D Check for corroded or broken metal parts and replace
them as needed.
D Check that the exhaust outlet is clear.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid
can cause severe injury or death. Battery acid can cause
blindness and burn skin. Always wear splashproof safety
goggles, rubber gloves, and boots when servicing the battery.
Do not open a sealed battery or mutilate the battery case. If
battery acid splashes in the eyes or on the skin, immediately
flush the affected area for 15 minutes with large quantities of
clean water. Seek immediate medical aid in the case of eye
contact. Never add acid to a battery after placing the battery in
service, as this may result in hazardous spattering of battery
acid.
Battery acid cleanup. Battery acid can cause severe
injury or death. Battery acid is electrically conductive and
corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking
soda) to a container with4L(1gal.)ofwaterandmixthe
neutralizing solution. Pour the neutralizing solution on the
spilled battery acid and continue to add the neutralizing
solution to the spilled battery acid until all evidence of a
chemical reaction (foaming) has ceased. Flush the resulting
liquid with water and dry the area.
Battery gases. Explosion can cause severe injury or
death. Battery gases can cause an explosion. Do not smoke
or permit flames or sparks to occur near a battery at any time,
particularly when it is charging. Do not dispose of a battery in a
fire.To prevent burns and sparks that could cause an
explosion, avoid touching the battery terminals with tools or
other metal objects. Remove all jewelry before servicing the
equipment. Discharge static electricity from your body before
touching batteries by first touching a grounded metal surface
away from the battery. To avoid sparks, do not disturb the
battery charger connections while the battery is charging.
Always turn the battery charger off before disconnecting the
battery connections. Ventilate the compartments containing
batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury
or death.Short circuits can cause bodily injury and/or
equipment damage. Disconnect the battery before generator
set installation or maintenance. Remove all jewelry before
servicing the equipment. Use tools with insulated handles.
Remove the negative (--) lead first when disconnecting the
battery.Reconnect the negative (--) lead last when
reconnecting the battery. Never connect the negative (--)
battery cable to the positive (+) connection terminal of the
starter solenoid. Do not test the battery condition by shorting
the terminals together.
TP-7092 8/1862 Section 4 Scheduled Maintenance
Page 63
Refer to this section for general battery information and
maintenance. Also consult the battery manufacturer’s
instructions for battery maintenance.
All generator set models use a negative ground with a
12-volt engine electrical system. Consult the generator
set nameplate for the engine electrical system voltage.
Consult the generator spec sheet for battery size and
capacity recommendations for replacement purposes.
Wiringdiagramsprovidebatteryconnection
information.See Figure 4-10 for typical battery
connections.
1
2
4.7.3 Checking Specific Gravity
Use a battery hydrometer to check the specific gravity of
the electrolyte in each battery cell. While holding the
hydrometer vertically,read the number on the glass bulb
at the top of the electrolyte level or the number adjacent
to the pointer. If the hydrometer used does not have a
correctiontable,use thecorrectionfactorsin
Figure 4-13. Determine specific gravity and electrolyte
temperature of battery cells. Locate temperature in
Figure 4-13 and adjust the specific gravity by the
amount shown.
The battery is fully charged if the specific gravity is 1.260
at an electrolyte temperature of 80F (26.7C). The
difference between specific gravities of each cell should
not exceed 0.01. Charge the battery if the specific
gravity is below 1.215 at an electrolyte temperature of
80F (26.7C). See Figure 4-11.
EZ-273000-J
1. To positive (+) terminal on starter solenoid.
2. To ground (--) terminal on or near starter motor.
Figure 4-10 12-Volt Engine Electrical System Single
Starter Motor, Typical Battery Connection
4.7.1Cleaning the Battery
Clean the battery and cables and tighten battery
terminals using the service schedule recommendations.
To prevent corrosion, maintain tight, dry electrical
connections at the battery terminals.To remove
corrosion from battery terminals, disconnect the cables
from the battery and scrub the terminals with a wire
brush. Clean the battery and cables with a solution of
baking soda and water. After cleaning, flush the battery
and cables with clean water and wipe them with a dry,
lint-free cloth.
After reconnecting the battery cables, coat the battery
terminals with petroleum jelly, silicone grease, or other
nonconductive grease.
Specific Gravity,
Corrected to
Below 1.215Needs charging
80F (26.7C)
1.260Fully charged
Battery
Condition
Figure 4-11 Specific Gravity Interpretation
Some battery testers have four or five beads in the test
tube. Draw electrolyte into the tube as performed with
the battery hydrometer described previously. Use the
manufacturer’s instructions.Figure 4-12 interprets
typical test results.
Battery
Number of Floating Beads
5Overcharged
4Fully charged
3Good charge
1or2Low charge
0Dead battery
Condition
Figure 4-12 Bead-Type Test Interpretation
4.7.2 Checking Electrolyte Level
Check the electrolyte level of batteries with filler caps
monthly. Remove filler caps and verify that electrolyte
level reaches bottom of filler holes. Refill as necessary
with distilled water. DO NOT add fresh electrolyte.
Tighten all filler caps. If water is added during freezing
temperatures, run the generator set for 20--30 minutes
to mix the electrolyte and water to prevent battery
damage from freezing.
TP-7092 8/1863Section 4 Scheduled Maintenance
Page 64
Tem pe r a-
CF
71.1
65.6
60.0
54.4
48.9
43.3
37.8
32.2
26.7
21.1
15.6
10
4.4
-- 1 . 1
-- 6 . 7
-- 12.2
ture
160
150
140
130
120
110
100
Correction
+ .032
+ .030
+ .028
EXAMPLE NO. 1—
+ .026
Temperature below 80
+ .024
+ .022
Hydrometer Reading 1.250
+ .020
Acid Temperature 20
+ .018
+ .016
Subtract .024 Specific Gravity
Corrected Specific Gravity is 1.226
+ .014
+ .012
1.250 -- .024 = 1.226
+ .010
+ .008
+ .006
EXAMPLE NO. 2—
90
80
70
60
50
40
30
20
10
+ .004
Temperature above 80
+ .002
Hydrometer Reading 1.235
0
-- .002
Acid Temperature 100
-- .004
Add .008 Specific Gravity
--. 006
Corrected Specific Gravity is
-- .008
1.243
-- .010
1.235 + .008 = 1.243
-- .012
-- .014
-- .016
-- .018
-- .020
-- .022
-- .024
-- .026
-- .028
F (26.7C)
F(--6.7C)
F (26.7C)
F (37.8C)
The temperature correction amounts to about .004 (4 points) of
specific gravity for each 10F(5.5C) change in temperature.
1-787
Figure 4-13 Specific Gravity Temperature Correction
TP-7092 8/1864 Section 4 Scheduled Maintenance
Page 65
4.8Storage Procedure
4.8.3Cylinder Lubrication
Perform the following storage procedure before
removing the generator set from service for three
months or longer. Follow the engine manufacturer’s
recommendations for storage, if available.
Note: Run the generator set monthly whenever
possible.
4.8.1Lubricating System
1. Operate the generator set until it reaches operating
temperature, or about 15 minutes.
2. Stop the generator set.
3. While the engine is still warm, drain the engine
lubrication oil from the engine crankcase.
4. Refill engine crankcase with oil. See Section 4.2.3
for oil recommendations.
5. Run the generator set for a few minutes to
distribute the clean oil.
6. Stop the generator set.
1. Remove the spark plugs.
2. Pour one tablespoon of engine oil into each spark
plug hole. Install the spark plugs and ground the
spark plug leads. Do not connect the leads to the
plugs.
3. Crank the engine two or three revolutions to
lubricate the cylinders.
4.8.4Exterior Preparation
1. Clean the exterior surface of the generator set.
2. Seal all openings in the engine with nonabsorbent
adhesive tape.
3. Mask all areas to be used for electrical contact.
4. Spread a light film of oil over unpainted metallic
surfaces to prevent rust and corrosion.
4.8.5Battery
Perform battery storage last.
4.8.2Fuel System
1. Start the generator set.
2. With the generator set running, shut off the gas
supply.
3. Run the generator set until the engine stops.
4. Press the OFF button on the generator set
controller.
1. Press the OFF button on the generator set
controller.
2. Disconnect the battery, negative (--) lead first.
3. Clean the battery.
4. Place the battery in a warm, dry location.
5. Connect the battery to a float/equalize battery
charger, or charge the battery monthly using a
trickle charger.Follow the battery charger
manufacturer’s recommendations.
TP-7092 8/1865Section 4 Scheduled Maintenance
Page 66
Notes
TP-7092 8/1866 Section 4 Scheduled Maintenance
Page 67
Section 5 Troubleshooting
5.1Introduction
Use the troubleshooting charts in this section to
diagnose and correct common problems. Firstcheck for
simple causes such as a dead engine starting battery,
loose connections, or an open circuit breaker. The
charts include a list of common problems, possible
causes of the problem, and recommended corrective
actions.
If the procedures in this manual do not explain how to
correcttheproblem,contactanauthorized
distributor/dealer. Maintain a record of repairs and
adjustments performed on the equipment.Use the
record to help describe the problem and repairs or
adjustments made to equipment.
5.2Fault Messages
The controller displays fault messages to aid in
troubleshooting.Selectedfault messagesand
recommended checks are listed in Figure 2-3.
Identify and correct the cause of the fault condition.
Then reset the controller after a fault shutdown. See
Section 2.5.4.
5.4USB Port and Auxiliary
Winding Mini-Breaker
The USB port is located under a small rubber cover as
shown in Figure 5-1.The alternator winding circuit
breaker is located on the engine side of the bulkhead as
shown in Figure 5-1.
A personal computer (laptop) with Kohlerr SiteTecht
software can be used to view the event history and
adjust controller settings. Usea USB cable with a mini-B
connector to connect the controller’s USB port to your
PC.
See TP-6701, SiteTecht Software Operation Manual,
for software operation instructions.
1
2
5.3Circuit Protection
If the generator set circuit breaker trips repeatedly,
contact an authorized distributor/ dealer for service.
5.3.1Cont roller Internal Circuit
Protection
The controlleris equipped withinternal circuit
protection. A fault message, Accy PwrOver Warning or
MainPwrOverL Shutdown, is displayed if this internal
protection is activated. Press OFF to reset. Contact an
authorized Kohler distributor/dealer for service.
5.3.2Line Circuit Breaker
The line circuit breaker interrupts the generator output in
the event of a fault in the wiring between the generator
and the load. If the circuit breaker trips, reduce the load
and switch the breaker back to the ON position.
ADV-8928
1. Mini-breaker location (access through engine compartment)
2. USB port on RDC2 controller
Figure 5-1USB Port and Mini-Breaker Locations
TP-7092 8/1867Section 5 Troubleshooting
Page 68
5.5Thermostat
WARNING
Procedure to Reset the Thermostat
1. Disconnect the utility power to the generator by
opening (turning OFF) the corresponding circuit
breaker at the building’s distribution panel.
2. Open the enclosure roof and secure it with the roof
stay on the left side of the enclosure.
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
workingon thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disabling the generator set.Accidental starting can
cause severe injury or death.Before working on the
generator set or equipment connected to the set, disable the
generator set as follows: (1) Press the generator set off/reset
button to shut down the generator set. (2) Disconnect the
power to the battery charger, if equipped. (3) Remove the
battery cables, negative (--) lead first. Reconnect the negative
(--) lead last when reconnecting the battery. Follow these
precautions to prevent the starting of the generator set by the
remote start/stop switch.
WARNING
3. Remove the air intake panel. See Figure 5-2.
4. Press the button on the thermostat to reset it.
5. Replace the air intake panel.
6. Reconnect utility power to the generator set by
closing the circuit breaker in the distribution panel.
7. Reset the fault on the controller. Refer to Section
2.5 for instructions, if necessary.
1
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Servicing the exhaust system.Hot parts can cause
severe injury or death. Do not touch hot engine parts. The
engine and exhaust system components become extremely
hot during operation.
The generator sets include a resettable thermostat. See
Figure 5-2 for the thermostat location in the air intake
area, near the fuel system. The thermostat detects
excess heat inside the enclosure. If the thermostat trips,
the generator will shut down and the controller will
display a fault (underspeed, underfrequency, or
undervoltage). Check for blocked air inlets and exhaust
outlets. Then follow these steps to reset the thermostat.
2
1. Thermostat location
2. Thermostat reset button
Figure 5-2Thermostat
TP-7092 8/1868 Section 5 Troubleshooting
Page 69
5.6Troubleshooting
Figure 5-3 contains generator set troubleshooting,
diagnostic, and repair information.Check for loose
connections before replacing parts.
Troubleshooting Table
ProblemPossible CauseCorrective Action
Controller
display
backlight is off.
Controller
displayisoff.
The generator
set does not
crank.
The generator
set cranks but
does not start,
starts hard,
lacks power, or
operates
erratically.
No AC output.
Low output or
excessive drop
in voltage.
Backlight turns off after about 1 minute with no
activity.
Low or no battery voltage.Check connections.
Battery weak or dead.Recharge or replace the battery. Make sure that the AC
Battery connections reversed or poor.Check the connections.
Fault shutdown.Check the controller display for fault messages. See
Generator set in the OFF mode.Press the RUN button to start the engine or press AUTO
Generator thermostat tripped.Check for obstructed air inlets and outlets. Reset the
Air cleaner clogged.Clean and/or replace the air cleaner.
Battery weak or dead.Recharge or replace the battery.
Battery connection poor.Clean and tighten the battery connections.
Spark plug wire connection loose.Check the spark plug wires.
Low oil pressure shutdown.Check for oil leaks. Check the oil level and add oil if
Fuel pressure insufficient.Check the fuel supply and valves.
Engine malfunction.Contact an authorized distributor/dealer.
Line circuit breaker in the OFF position.Place the circuit breaker in the ON position.
Line circuit breaker tripping because of
overload.
Line circuit breaker tripping because of short
circuit.
Auxiliary winding circuit breaker tripped.Reset the circuit breaker (located in controller’s service
Generator set overloaded.Reduce the load by unplugging non-essential
Backlight will turn on when a button is pressed or the
generator set starts.
Check generator set battery. See Figure 5-3.
power to the generator set controller is backed up by the
generator set.
Section 2.5. Correct the fault condition and reset the
controller.
to allow remote starting.
thermostat. See Section 5.5.
necessary.
Reduce the load on the generator set by unplugging
non-essential appliances.
Contact an authorized distributor/dealer for service.
access area). Contact an authorized distributor/dealer
for service if breaker trips repeatedly.
appliances.
TP-7092 8/1869Section 5 Troubleshooting
Page 70
Troubleshooting Table
Generator set
stops suddenly.
Low oil pressure shutdown.Check for oil leaks. Check the oil level and add oil if
No fuel.Check fuel valves and fuel supply.
Overcrank shutdown.Reset the controller. If the overcrank fault occurs again,
Auxiliary winding circuit breaker tripped.Reset the auxiliary winding circuit breaker. Contact an
Fault shutdown.Check the controller display for fault messages. See
Generator set in the OFF mode.Press the RUN button to start the engine or press AUTO
Remote stop command received from a remote
switch, ATS, or OnCuerPlus.
Generator thermostat tripped.Check for obstructed air inlets and outlets. Reset the
Engine malfunction.Contact an authorized distributor/dealer.
Figure 5-3General Troubleshooting
Corrective ActionPossible CauseProblem
necessary.
Model 20RCA/20RCAL only: Check enclosure
thermostat and reset if tripped. See Section 5.5. Check
and clear air inlets and exhaust outlets.
contact an authorized distributor/dealer.
authorized distributor/dealer for service if breaker trips
repeatedly.
Section 2.5. Correct the fault condition and reset the
controller.
to allow remote starting.
Check the remote switch position. Check OnCuerPlus.
thermostat. See Section 5.5.
TP-7092 8/1870 Section 5 Troubleshooting
Page 71
Appendix A Abbreviations
The following list contains abbreviations that may appear in this publication.
A, ampampere
ABDCafter bottom dead center
ACalternating current
A/Danalog to digital
ADCadvanced digital control;
adj.adjust, adjustment
ADVadvertising dimensional
Ahamp-hour
AHWTanticipatory high water
AISIAmerican Iron and Steel
ALOPanticipatory low oil pressure
alt.alternator
Alaluminum
ANSIAmerican National Standards
AOanticipatory only
APDCAir Pollution Control District
APIAmerican Petroleum Institute
approx.approximate, approximately
APUAuxiliary Power Unit
AQMDAir Quality Management District
ARas required, as requested
ASas supplied, as stated, as
ASEAmerican Society of Engineers
ASMEAmerican Society of
assy.assembly
ASTMAmerican Society for Testing
ATDCafter top dead center
ATSautomatic transfer switch
auto.automatic
aux.auxiliary
avg.average
AVRautomatic voltage regulator
AWGAmerican Wire Gauge
AWMappliance wiring material
bat.battery
BBDCbefore bottom dead center
BCbattery charger, battery
BCAbattery charging alternator
BCIBattery Council International
BDCbefore dead center
BHPbrake horsepower
blk.black (paint color), block
blk. htr.block heater
BMEPbrake mean effective pressure
bpsbits per second
br.brass
BTDCbefore top dead center
BtuBritish thermal unit
Btu/min.British thermal units per minute
CCelsius, centigrade
cal.calorie
CANcontroller area network
CARBCalifornia Air Resources Board
CAT5Category 5 (network cable)
CBcircuit breaker
CCcrank cycle
cccubic centimeter
CCAcold cranking amps
ccw.counterclockwise
CECCanadian Electrical Code
cert.certificate, certification, certified
cfhcubic feet per hour
analog to digital converter
drawing
temperature
Institute
Institute (formerly American
Standards Association, ASA)
suggested
Mechanical Engineers
Materials
charging
(engine)
cfmcubic feet per minute
CGcenter of gravity
CIDcubic inch displacement
CLcenterline
cmcentimeter
CMOScomplementary metal oxide
cu. in.cubic inch
cw.clockwise
CWCcity water-cooled
cyl.cylinder
D/Adigital to analog
DACdigital to analog converter
dBdecibel
dB(A)decibel (A weighted)
DCdirect current
DCRdirect current resistance
deg., degree
dept.department
dia.diameter
DI/EOdual inlet/end outlet
DINDeutsches Institut fur Normung
exh.exhaust
ext.external
FFahrenheit, female
FHMflat head machine (screw)
fl. oz.fluid ounce
flex.flexible
freq.frequency
FSfull scale
ft.foot, feet
ft. lb.foot pounds (torque)
ft./min.feet per minute
ftpfile transfer protocol
ggram
ga.gauge (meters, wire size)
gal.gallon
gen.generator
gensetgenerator set
GFIground fault interrupter
GND,
gov.governor
gphgallons per hour
gpmgallons per minute
gr.grade, gross
GRDequipment ground
gr. wt.gross weight
H x W x D height by width by depth
HChex cap
HCHThigh cylinder head temperature
HDheavy duty
HEThigh exhaust temp., high
hexhexagon
Hgmercury (element)
HHhex head
HHChex head cap
HPhorsepower
hr.hour
HSheat shrink
hsg.housing
HVACheating, ventilation, and air
HWThigh water temperature
Hzhertz (cycles per second)
IBCInternational Building Code
ICintegrated circuit
IDinside diameter, identification
IECInternational Electrotechnical
IEEEInstitute of Electrical and
IMSimproved motor starting
in.inch
in. H
in. Hginches of mercury
in. lb.inch pounds
Inc.incorporated
ind.industrial
int.internal
int./ext.internal/external
I/Oinput/output
IPinternet protocol
ISOInternational Organization for
Jjoule
JISJapanese Industry Standard
kkilo (1000)
Kkelvin
kAkiloampere
KBkilobyte (2
kgkilogram
ground
engine temp.
conditioning
Commission
Electronics Engineers
Oinches of water
2
Standardization
10
bytes)
TP-7092 8/18Appendix 71
Page 72
2
kg/cm
kgmkilogram-meter
kg/m
kilograms per square
centimeter
3
kilograms per cubic meter
kHzkilohertz
kJkilojoule
kmkilometer
kOhm, k kilo-ohm
kPakilopascal
kphkilometers per hour
kVkilovolt
kVAkilovolt ampere
kVARkilovolt ampere reactive
kWkilowatt
kWhkilowatt-hour
kWmkilowatt mechanical
kWthkilowatt-thermal
Lliter
LANlocal area network
L x W x H length by width by height
lb.pound, pounds
3
lbm/ft
pounds mass per cubic feet
LCBline circuit breaker
LCDliquid crystal display
LEDlight emitting diode
Lphliters per hour
Lpmliters per minute
LOPlow oil pressure
LPliquefied petroleum
LPGliquefied petroleum gas
LSleft side
L
wa
LWLlow water level
sound power level, A weighted
LWTlow water temperature
mmeter, milli (1/1000)
Mmega (10
3
m
3
m
3
m
units), male
cubic meter
/hr.cubic meters per hour
/min.cubic meters per minute
bytes)
MCCBmolded-case circuit breaker
MCMone thousand circular mils
meggarmegohmmeter
MHzmegahertz
mi.mile
milone one-thousandth of an inch
min.minimum, minute
misc.miscellaneous
MJmegajoule
mJmillijoule
mmmillimeter
mOhm, mmilliohm
MOhm, Mmegohm
MOVmetal oxide varistor
MPamegapascal
mpgmiles per gallon
mphmiles per hour
MSmilitary standard
msmillisecond
m/sec.meters per second
mtg.mounting
MTUMotoren-und Turbinen-Union
MWmegawatt
mWmilliwatt
Fmicrofarad
N, norm. normal (power source)
NAnot available, not applicable
nat. gasnatural gas
NBSNational Bureau of Standards
Association
Nmnewton meter
NOnormally open
no., nos. number, numbers
NPSNational Pipe, Straight
NPSCNational Pipe, Straight-coupling
NPTNational Standard taper pipe
thread per general use
NPTFNational Pipe, Taper-Fine
NRnot required, normal relay
nsnanosecond
OCovercrank
ODoutside diameter
OEMoriginal equipment
manufacturer
OFoverfrequency
opt.option, optional
OSoversize, overspeed
OSHAOccupational Safety and Health
(screw)
PHHPhillipsr hex head (screw)
PHMpan head machine (screw)
PLCprogrammable logic control
PMGpermanent magnet generator
potpotentiometer, potential
ppmparts per million
PROMprogrammable read-only
memory
psipounds per square inch
psigpounds per square inch gauge
pt.pint
PTCpositive temperature coefficient
PTOpower takeoff
PVCpolyvinyl chloride
qt.quart, quarts
qty.quantity
Rreplacement (emergency)
power source
rad.radiator, radius
RAMrandom access memory
RBUSRS-485 proprietary
communications
RDOrelay driver output
ref.reference
rem.remote
Res/Coml Residential/Commercial
RFIradio frequency interference
RHround head
RHMround head machine (screw)
rly.relay
rmsroot mean square
rnd.round
ROread only
ROMread only memory
rot.rotate, rotating
rpmrevolutions per minute
RSright side
RTDsResistance Temperature
Detectors
RTUremote terminal unit
RTVroom temperature vulcanization
RWread/write
SAESociety of Automotive
Engineers
scfmstandard cubic f eet per minute
SCRsilicon controlled rectifier
s, sec.second
SISysteme international d’unites,
International System of Units
SI/EOside in/end out
sil.silencer
SMTPsimple mail transfer protocol
SNserial number
SNMPsimple network management
protocol
SPDTsingle-pole, double-throw
SPSTsingle-pole, single-throw
specspecification
specsspecification(s)
sq.square
sq. cmsquare centimeter
sq. in.square inch
SMSshort message service
SSstainless steel
std.standard
stl.steel
tach.tachometer
TBterminal block
TCPtransmission control protocol
TDtime delay
TDCtop dead center
TDECtime delay engine cooldown
TDENtime delay emergency to
normal
TDEStime delay engine start
TDNEtime delay normal to
emergency
TDOEtime delay off to emergency
TDONtime delay off to normal
temp.temperature
term.terminal
THDtotal harmonic distortion
TIFtelephone influence factor
tol.tolerance
turbo.turbocharger
typ.typical (same in multiple
locations)
UFunderfrequency
UHFultrahigh frequency
UIFuser interface
ULUnderwriter’s Laboratories, Inc.
UNCunified coarse thread (was NC)
UNFunified fine thread (was NF)
univ.universal
URLuniform resource locator
(web address)
USundersize, underspeed
UVultraviolet, undervoltage
Vvolt
VACvolts alternating current
VARvoltampere reactive
VDCvolts direct current
VFDvacuum fluorescent display
VGAvideo graphics adapter
VHFvery high frequency
Wwatt
WCRwithstand and closing rating
w/with
WOwrite only
w/owithout
wt.weight
xfmrtransformer
TP-7092 8/1872 Appendix
Page 73
Notes
TP-7092 8/1873
Page 74
Notes
TP-7092 8/1874
Page 75
Page 76
TP-70928/18
E 2018 by Kohler Co. All rights reserved.
KOHLER CO., Kohler, Wisconsin 53044
Phone 920-457-4441, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KOHLERPower.com