Kohler 14-20RESAL, 14-20RESA User Manual

Residential/Commercial Generator Sets
Models:
14/20RESA
14/20RESAL
Controllers:
RDC2
DC2
TP-6804 12/11
California Proposition 65
WARNING
Engine exhaust from this product contains chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm.
Product Identification Information
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Controller Identification
Record the controller description from the generator set operation manual, spec sheet, or sales invoice.
Controller Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
Table of Contents
Product Identification Information 2............................................................
Safety Precautions and Instructions 7........................................................
Introduction 11...............................................................................
Service Assistance 13........................................................................
Section 1 Descriptions and Service Views 15..................................................
1.1 Introduction 15..........................................................
1.2 Engine 15...............................................................
1.3 Generator Set Enclosure 15...............................................
1.4 Alternator 15............................................................
1.5 Transfer Switch 15.......................................................
1.6 Controllers 15...........................................................
1.7 Accessories 18..........................................................
1.7.1 Carburetor Heater 18.............................................
1.7.2 Fuel Regulator Heater (20RESA and RESAL only) 18.................
1.7.3 OnCue Home Generator Management System 18....................
1.7.4 Programmable Interface Module (PIM) 18...........................
1.7.5 Load Control Module (LCM) 18....................................
1.8 Service Views 19........................................................
Section 2 Generator Set Operation 21.........................................................
2.1 Prestart Checklist 21.....................................................
2.2 Exercising the Generator Set 21...........................................
2.3 Generator Set Operation 21...............................................
2.3.1 Local Starting and Stopping 21....................................
2.3.2 Automatic Starting and Stopping 21................................
2.3.3 Remote Starting and Stopping 21..................................
2.3.4 Engine Start Crank Cycle 21.......................................
2.3.5 Engine Cooldown 21.............................................
2.3.6 Automatic Operation with Model RXT Transfer Switch 22..............
2.3.7 Automatic Operation with Model RDT or RSB Transfer Switches 22.....
2.4 Exercise 23.............................................................
2.4.1 Setting the Exerciser 23...........................................
2.4.2 Unloaded Cycle Exercise with Complete System Diagnostics 23........
2.4.3 Unloaded Full-Speed Exercise 24..................................
2.4.4 Loaded Full-Speed Exercise (with RXT only) 24......................
2.4.5 Power Failure During Exercise Cycle 24.............................
2.5 Faults 24...............................................................
2.5.1 Warnings 24.....................................................
2.5.2 Shutdowns 24...................................................
2.5.3 ATS Communication Errors 24.....................................
2.5.4 Resetting the Controller after a Fault Shutdown 25....................
Section 3 RDC2 Controller Operation 29.......................................................
3.1 RDC2 Generator Set/ Transfer Switch Controller 29..........................
3.2 Controls and Indicators 29................................................
3.2.1 Controller Keypad 30.............................................
3.2.2 LED Indicators 30................................................
3.2.3 LCD Display 31..................................................
3.3 Controller Power 32......................................................
3.4 Battery Charging 32......................................................
3.5 Changing Settings 32.....................................................
3.6 Setting the Exerciser 34..................................................
3.6.1 Setting the Exerciser at Controller Powerup 34.......................
3.6.2 Changing the Exercise Settings 34.................................
TP-6804 12/11 Table of Contents
Table of Contents, continued
3.7 RDC2 Controller Menus 36................................................
3.8 Main Menu 36...........................................................
3.9 Overview Menu 37.......................................................
3.10 Engine Metering Menu 37.................................................
3.11 Generator Metering Menu 38..............................................
3.12 Generator Set Information Menu 39........................................
3.13 Genset Run Time Menu 39................................................
3.14 Genset System Menu 40..................................................
3.15 ATS Status Menu 41.....................................................
3.16 ATS Configuration Menu 42...............................................
3.17 Date and Time Menu 43..................................................
3.18 Networking Information Menus 43..........................................
3.18.1 Networking Status Submenu 44....................................
3.18.2 Networking Configuration Submenu (OnCue Password) 45............
3.18.3 RBUS Information 46.............................................
3.18.4 Remote Devices Submenu 47.....................................
3.19 Programmable Interface Module (PIM) Status Menu 48.......................
3.20 Load Control Module (LCM) Menus 49......................................
3.21 Event Log 50............................................................
Section 4 DC2 Controller Operation 51........................................................
4.1 DC2 Generator Set/ Transfer Switch Controller 51............................
4.2 Controls and Indicators 51................................................
4.2.1 Controller Keypad 52.............................................
4.2.2 LED Indicators 52................................................
4.2.3 LCD Display 53..................................................
4.3 Controller Power 53......................................................
4.4 Battery Charging 53......................................................
4.5 Exercise 54.............................................................
4.5.1 Exercise Modes 54...............................................
4.5.2 Setting the Exerciser 54...........................................
4.5.3 Exerciser Reset 54...............................................
4.6 Event Log 54............................................................
4.7 Maintenance Timer 55....................................................
4.8 OnCue Password 55.....................................................
Section 5 Scheduled Maintenance 57..........................................................
5.1 Scheduled Maintenance 57...............................................
5.1.1 Service Schedule, 14RESA/RESAL Models 58......................
5.1.2 Service Schedule, 20RESA/RESAL Models 59......................
5.2 Lubrication System 60....................................................
5.2.1 Low Oil Pressure Shutdown 60....................................
5.2.2 Oil Check 60....................................................
5.2.3 Engine Oil Recommendation 60....................................
5.2.4 Oil Change Procedure 60.........................................
5.2.5 Resetting the Maintenance Timer 61................................
5.2.6 Oil Cooler 20RESA/RESAL 61.....................................
5.3 Spark Plugs 62..........................................................
5.4 Air Cleaner Service 62....................................................
5.4.1 Air Cleaner, 14RESA/RESAL Models 62............................
5.4.2 Air Cleaner, 20RESA/RESAL Models 63............................
5.5 Cooling System 64.......................................................
5.6 Exhaust System 64......................................................
5.7 Battery 65...............................................................
TP-6804 12/11Table of Contents
Table of Contents, continued
5.8 Storage Procedure 66....................................................
5.8.1 Lubricating System 66............................................
5.8.2 Fuel System 66..................................................
5.8.3 Cylinder Lubrication 66...........................................
5.8.4 Exterior Preparation 66...........................................
5.8.5 Battery 66.......................................................
Section 6 Troubleshooting 67.................................................................
6.1 Introduction 67..........................................................
6.2 Fault Messages 67.......................................................
6.3 Circuit Protection 67......................................................
6.3.1 Controller Internal Circuit Protection 67.............................
6.3.2 Line Circuit Breaker 67...........................................
6.3.3 Auxiliary Winding Circuit Breaker 67................................
6.4 Controller Service Access 67..............................................
6.5 Troubleshooting 68.......................................................
Appendix A Abbreviations 69..................................................................
TP-6804 12/11 Table of Contents
Notes
TP-6804 12/116
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,or substantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
WARNING
Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks.
Locate the battery in a well-ventilated area. Isolatethe battery charger from explosive fumes.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. Ifbattery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a containerwith4L(1gal.)ofwaterand mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
TP-6804 12/11 7Safety Precautions and Instructions
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner removed.
Servicing the fuel system. A flash fire can cause severe injury or death.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.
Carbon monoxide detectors. Carbon monoxide can cause severe nausea, fainting, or death. Install
carbon monoxide detectors on each level of any building adjacent to the generator set. Locate the detectors to adequately warn the building’s occupants of the presence of carbon monoxide. Keep the detectors operational at all times. Periodically test and replace the carbon monoxide detectors according to the manufacturer’s instructions.
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
TP-6804 12/118 Safety Precautions and Instructions
Fuel System
Hazardous Noise
WARNING
WARNING
Explosive fuel vapors. Can cause severe injury or death.
Use extreme care when handling, storing, and using fuels.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels inawell-ventilatedareaawayfrom spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Donot operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Gas fuel leaks. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Check the LP vapor gas or natural gas fuel system for leakage by using a soap and water solution with the fuel system test pressurized to 6--8 ounces per square inch (10--14 inches water column). Do not use a soap solution containing either ammonia or chlorine because both prevent bubble formation. A successful test depends on the ability of the solution to bubble.
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Hazardous Voltage/ Moving Parts
DANGER
Hazardous voltage. Will cause severe injury or death.
This equipment must be installed and serviced by qualified electrical personnel.
WARNING
Hazardous voltage. Can cause severe injury or death.
Moving parts.
Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury, or death.
If the generator set is used for standby power, install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply.
CAUTION
Welding the generator set. Can cause severe electrical equipment damage.
Never weld components of the generator set without first disconnecting the battery, controller wiring harness, and engine electronic control module (ECM).
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Ensure you comply with all applicable codes and standards. Electrically ground the generator set, transfer switch, and related equipment and electrical circuits. Turn off the main circuit breakers of all power sources before servicing the equipment. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Operate the generator set only when all guards and electrical enclosures areinplace.
TP-6804 12/11 9Safety Precautions and Instructions
Welding on the generator set. Can cause severe electrical equipment damage. Before welding on the
generator set perform the following steps: (1) Remove the battery cables, negative (--) lead first. (2) Disconnect all engine electronic control module (ECM) connectors. (3) Disconnect all generator set controller and voltage regulator circuit board connectors. (4) Disconnect the engine battery­charging alternator connections. (5) Attach the weld ground connection close to the weld location.
Hot Parts
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Notice
NOTICE
Canadian installations only.For standby service connect the output of the generator set to a suitably rated transfer switch in accordance with Canadian Electrical Code, Part 1.
Connecting the battery and the battery charger. Hazardous voltage can cause severe injury or death.
Reconnect the battery correctly, positive to positive and negative to negative, to avoid electrical shock and damage to the battery charger and battery(ies). Have a qualified electrician install the battery(ies).
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death. Install
a transfer switch in standby power installations to prevent the connection of standby and other sources of power. Electrical backfeed into a utility electrical system can cause severe injury or death to utility personnel working on power lines.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Servicing the engine heater. Hot parts can cause minor personal injury or property damage. Installthe
heater before connecting it to power. Operating the heater before installation can cause burns and component damage. Disconnect power to the heater and allow it to cool before servicing the heater or nearby parts.
Heavy Equipment
WARNING
Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage.
Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid.
TP-6804 12/1110 Safety Precautions and Instructions
Introduction
This manual provides operation and maintenance instructions for residential/commercial model 14/20RESA and RESAL generator sets equipped with Kohler RDC2 or DC2 generator set/transfer switch controllers. See Figure 1. The RDC2 and DC2 controllers control the generator set and the optional Model RXT transfer switch.
This generator set is approved for use in stationary applications in locations served by a reliable utility power source. Have the generator set installed by an authorized distributor/dealer or service technician. Refer to TP-6803, Installation Manual, for installation instructions.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Obtain service from an authorized service distributor/ dealer to keep equipment in top condition.
List of Related Literature
Figure 2 identifies related literature available for the generator sets covered in this manual. Only trained and qualified personnel should install or service the generator set.
Literature Type Part Number
Installation Manual, Model 14/20RESA/RESAL Generator Set
Operation/Installation Manual, Model RXT Automatic Transfer Switch
Operation/Installation Manual, Model RDT Automatic Transfer Switch
Installation Manual, Model RSB Automatic Transfer Switch
Operation Manual, Model RSB Automatic Transfer Switch
Service Manual, 14/20RESA/RESAL Generator Set
Operation Manual, OnCuer Software TP-6796
Operation Manual, SiteTecht Software TP-6701
Installation Instructions, Load Control Module (LCM)
Installation Instructions, Programmable Interface Module (PIM)
Figure 2 Related Literature
TP-6803
TP-6807
TP-6345
TP-6486
TP-6487
TP-6735
TT-1574
TT-1584
Figure 1 RESA/RESAL Generator Set
TP-6804 12/11 11Introduction
Nameplate
The following illustration shows a typical generator set nameplate. Copy the model, serial, and specification numbers from the nameplate into the spaces provided in the product information section on the inside front cover of this manual. See the service views in Section 1.8 for the nameplate location.
GM12070
The Emission Compliance Period referred to on the Emission Control or Air Index label indicates the number of operating hours for which the engine has been shown to meet CARB or EPA emission requirements. Figure 3 provides the engine compliance period (in hours) associated with the category descriptor, which may be found on the certification label.
Emission Compliance Period
EPA
CARB
Category C
250 hours
Moderate 125 hours
Category B
500 hours
Intermediate
250 hours
Category A 1000 hours
Extended 500 hours
Figure 3 Emission Compliance Period
Refer to the certification label for engine displacement.
The exhaust emission control system for the CH740 engines (14RESA/RESAL) is EM for U.S. EPA, California, and Europe.
The exhaust emission control system for the CH1000 engine (20RESA/RESAL) is EM for U.S. EPA, California, and Europe.
Emission Information
The Kohlerr Model CH740 engine used on the 14RESA/RESAL generator set is certified to operate using natural gas or propane fuel.
The Kohler Model CH1000 engine used on the 20RESA/RESAL generator set is certified to operate using propane fuel. The CH1000 engine used on the 20RESA/RESAL may be operated on natural gas fuel because it is excluded from the requirements of 40 CFR 1048 as a stationary engine.
The engine used in the Model 20RESA/RESAL generator set is certified for emergency standby use only.
TP-6804 12/1112 Introduction
Service Assistance
For professional advice on generator set power requirements and conscientious service, please contact your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D Visit the Kohler Power Systems website at
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa (EMEA)
Kohler Power Systems 3 rue de Brennus 93200 Saint Denis France Phone: (33) 1 49 178300 Fax: (33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office Singapore, Republic of Singapore Phone: (65) 6264-6422 Fax: (65) 6264-6455
China
North China Regional Office, Beijing Phone: (86) 10 6518 7950
(86) 10 6518 7951 (86) 10 6518 7952
Fax: (86) 10 6518 7955
East China Regional Office, Shanghai Phone: (86) 21 6288 0500 Fax: (86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80 3366208
(91) 80 3366231
Fax: (91) 80 3315972
Japan, Korea
North Asia Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, USA Phone: (863) 619-7568 Fax: (863) 701-7131
TP-6804 12/11 13Service Assistance
Notes
TP-6804 12/1114 Service Assistance
Section 1 Descriptions and Service Views
1.1 Introduction
The generator set specification sheets provide specific generator and engine information. Refer to the spec sheet for data not supplied in this manual. Consult the generator set service manual, engine operation manual, and engine service manual for additional specifications. Obtain copies of the latest spec sheets, manuals, diagrams, and drawings from your local distributor/ dealer.
1.2 Engine
The generator set has a four-cycle, twin cylinder, air­cooled Kohlerr engine. The engine operates on clean­burning natural gas or propane (LP) vapor. Engine features include:
D Efficient overhead valve design and full pressure
lubrication for maximum power, torque, and reliability under all operating conditions.
D Dependable, maintenance-free electronic ignition.
D Precision-formulated cast iron construction of parts
subjected to the most wear and tear.
1.4 Alternator
The generator uses Kohler’s unique PowerBoostt voltage regulation system, which provides instant response to load changes.
PowerBoostt ensures reliable motor starting and consistent voltage levels. PowerBoostt utilizes a voltage excitation system that employs a winding independent of the main output windings to provide excitation voltage.
1.5 Transfer Switch
The RDC2 and DC2 controllers are designed to interface with and control the Kohler Model RXT Automatic Transfer Switch (ATS). Do not use the Kohler Model RRT transfer switch with the RDC2 or DC2 controller.
If the power system uses a different model transfer switch, the RDC2 and DC2 controllers will not control the transfer switch. An ATS other than the Model RXT must be equipped with a transfer switch controller and engine start contacts that connect to the remote engine start terminals on the generator set.
D Field-convertible multi-fuel systems that allow fuel
changeover from natural gas to LP vapor (and vice­versa) while maintaining CARB emission certification.
D Digital spark advance optimizes ignition timing for the
selected fuel.
1.3 Generator Set Enclosure
The generator set is housed in an exclusive engineered composite enclosure that is corrosion-proof, even in harsh seaside environments, and impact-resistant, even in cold weather. The enclosure has a hinged, locking roof that allows easy access to the generator set controller when required, but locks securely to prevent unauthorized access.
To open the roof, insert the tool provided with the enclosure and turn counterclockwise 1/4 turn. Then just raise the roof. The roof stays open until you are ready to close it.
Be sure to close and lock the enclosure, and keep the tool in a secure location.
1.6 Controllers
RESA models are equipped with the Residential Digital Control (RDC2). RESAL models use the Digital Control (DC2). See Figure 1-1.
The controller provides integrated control for the generator set, Kohlerr Model RXT transfer switch, programmable interface module (PIM), and load control module (LCM).
RDC2 (RESA) DC2 (RESAL)
Figure 1-1 Controllers
TP-6804 12/11 15Section 1 Descriptions and Service Views
The controller’s 2-line LCD screen displays status messages and system settings that are clear and easy to read, even in direct sunlight or low light.
D Front-access mini USB connector for SiteTecht
connection
D Front access mini-breaker protects the alternator
RDC2 Controller Features
D Six-button keypad
d OFF, AUTO, and RUN pushbuttons
d Select and arrow buttons for access to system
configuration and adjustment menus
D LED indicators for OFF, AUTO, and RUN modes
D LED indicators for utility power and generator set
source availability and ATS position (Model RXT transfer switch required)
D LCD display
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for
excellent visibility in all lighting conditions
D Scrolling system status display
d Generator set status
d Voltage and frequency
d Engine temperature
d Oil pressure
d Battery voltage
d Engine runtime hours
D Date and time displays
D Smart engine cooldown senses engine temperature
D Digital isochronous governor to maintain
steady-state speed at all loads
D Digital voltage regulation: ±0.5% RMS no-load to
full-load
D Automatic start with programmed cranking cycle
D Programmable exerciser can be set to start
automatically on any future day and time, and run every week or every two weeks
D Exercise modes
D Integral Ethernet connector for Kohlerr OnCuet
D Built-in 2.5 amp battery charger
D Remote two-wire start/stop capability for optional
connection of Model RDT or RSB transfer switches
D Diagnostic messages
d Displays diagnostic messages for the engine,
generator, Model RXT transfer switch, programmable interface module (PIM), and load control module (LCM)
d Over 70 diagnostic messages can be displayed
D Maintenance reminders
D System settings
d System voltage, frequency, and phase
d Voltage adjustment
d Measurement system, English or metric
D ATS status (Model RXT ATS required)
d Source availability
d ATS position (normal/utility or
emergency/generator)
d Source voltage and frequency
D ATS control (Model RXT ATS required)
d Source voltage and frequency settings
d Engine start time delay
d Transfer time delays
d Voltage calibration
d Fixed pickup and dropout settings
D Programmable Interface Module (PIM) status
displays
d Input status (active/inactive)
d Output status (active/inactive)
d Unloaded weekly exercise with complete system
diagnostics
d Unloaded full-speed exercise
d Loaded full-speed exercise (Model RXT ATS
required)
D Load control module (LCM) menus
d Load status
d Test function
TP-6804 12/1116 Section 1 Descriptions and Service Views
DC2 Controller Features
D Automatic start with programmed cranking cycle
D Four-button keypad: OFF, AUTO, RUN, and
EXERCISE pushbuttons
D LED indicators for OFF, AUTO, and RUN modes
D LCD display:
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for
excellent visibility
D Scrolling system status display
d Generator set status
d Voltage and frequency
d Engine temperature
d Oil pressure
d Battery voltage
d Engine runtime hours
d Maintenance reminders
d OnCue status (connected/disconnected)
D Date and time displays
D Smart engine cooldown senses engine temperature
D Exercise modes
d Unloaded weekly exercise with complete system
diagnostics
d Unloaded full-speed exercise
d Loaded full-speed exercise (Model RXT ATS
required)
D Front-access mini USB connector for SiteTecht
connection
D Front access mini-breaker protects the alternator
D Integral Ethernet connector for Kohlerr OnCuet
D Built-in 2.5 amp battery charger
D Remote two-wire start/stop capability for optional
connection of Model RDT or RSB transfer switches
D Diagnostic messages
d Displays diagnostic messages for the engine,
generator set, model RXT transfer switch, and optional programmable interface module (PIM) and load control module (LCM)
d Over 70 diagnostic messages can be displayed
D Digital isochronous governor to maintain
steady-state speed at all loads
D Digital voltage regulation: ±0.5% RMS no-load to
full-load
D A laptop computer and Kohlerr SiteTech software
can be used to change system settings or upgrade controller firmware.
TP-6804 12/11 17Section 1 Descriptions and Service Views
1.7 Accessories
The following optional accessories are offered for the RESA and RESAL generator sets.
1.7.1 Carburetor Heater
An optional carburetor heater is recommended for improved cold starting in locations where the ambient temperature drops below 0_C (32_F). The carburetor heater prevents condensation and carburetor icing. The heater requires a continuous source of 120 VAC power.
See the generator set Installation manual for more information.
1.7.4 Programmable Interface Module (PIM)
The optional Programmable Interface Module (PIM) provides two programmable inputs and six programmable dry contact outputs for connection to customer-supplied equipment. The outputs are controlled by the RDC2 controller, and can also be controlled remotely using the OnCue program.
The PIM is mounted in a NEMA 3R aluminum enclosure, which can be mounted indoors or outdoors. See the installation instructions provided with the PIM.
1.7.5 Load Control Module (LCM)
1.7.2 Fuel Regulator Heater (20RESA and RESAL only)
An optional fuel regulator heater for the 20RESA/20RESAL is recommended for improved cold starting in locations where the ambient temperature drops below --18_C(0_F). The heater requires a continuous source of 120 VAC power.
See the generator set Installation manual for more information.
1.7.3 OnCue Home Generator Management System
The Kohlerr OnCuet Home Generator Management System allows monitoring and control of your RESA or RESAL generator set from a personal computer located in your home or at other remote locations. OnCuet can also be configured to send email or text message notifications in the event of a generator set fault.
Note: Be sure to obtain the correct version of the
OnCuet kit for the RDC2/DC2 controller.
The optional Load Control Module (LCM) provides an automatic load management system to comply with Section 702.5 of NEC 2008. The installer is responsible for ensuring that the power system installation complies with all applicable state and local codes.
The LCM automatically manages up to six residential loads. Four power relays are provided for management of non-essential secondary loads, and two relays are available to control two independent air conditioner loads.
The LCM is controlled by the RDC2/DC2 controller. The load on the generator set is monitored, and loads are added or shed in the order of their priority. See specification sheet G6-120 and the LCM installation instructions for more information.
OnCuet version 3.0 is required for RESA/RESAL generator sets equipped with the RDC2/DC2 controller. OnCuet versions numbered 1.x are not compatible with the RDC2/DC2 controller.
TP-6804 12/1118 Section 1 Descriptions and Service Views
1.8 Service Views
2
5
1
8
7
6
3
4
10
11
12
13
14
15
9
1. Hinged inner cover
2. Hinged roof
3. Air intake
4. Lock
5. Locking tool, provided with generator set
6. Exhaust outlet
7. Oil check (dipstick)
8. Oil fill
9. Lifting holes
10. Muffler
11. Air cleaner
12. Oil filter
13. Line circuit breaker
14. USB connector (for firmware updates)
26
16, 17
18
19
AIR INTAKE SIDE --PANEL
REMOVED TO SHOW DETAIL
20
21
25
24
15. RDC2 or DC2 controller
16. Field-connection terminal block (behind panel)
17. Digital spark advance ignition (DSAI) leads
18. Fuel block (14 kW models) or LP orifice location (20 kW models, inside hose fitting)
19. Fuel inlet
20. Fuel solenoid valve
21. Gas regulator assembly
22. 120 VAC receptacles for optional carburetor heater (not shown)
23. Engine starting battery location (battery purchasd separately)
24. Oil drain hose
25. Nameplate location
26. Oil drain valve
22
23
ADV-8424
Figure 1-2 Service View (Model 20RESA shown)
TP-6804 12/11 19Section 1 Descriptions and Service Views
Notes
TP-6804 12/1120 Section 1 Descriptions and Service Views
Section 2 Generator Set Operation
2.1 Prestart Checklist
To ensure continued satisfactory operation, perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. In addition, some checks require verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering the engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding battery care and maintenance.
Exhaust System. Check for exhaust leaks and blockages. Check the muffler condition.
D Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust system connections.
D Check for corroded or broken metal parts and replace
them as needed.
D Check that the exhaust outlet is unobstructed.
Oil Level. Check the oil level before starting the generator set and at the intervals given in Section 5, Scheduled Maintenance. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
2.2 Exercising the Generator Set
Operate the generator set without load once each week for 20 minutes. See Section 2.4 for information about loaded and unloaded exercise modes. For instructions to set the exerciser, see:
D Section 3.6 for the RDC2 controller
2.3 Generator Set Operation
2.3.1 Local Starting and Stopping
Start: Press the RUN button to immediately start the generator set.
Stop: Press the OFF button. The engine stops.
Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.
2.3.2 Automatic Starting and Stopping
An automatic transfer switch monitors the utility power and signals the generator set to start when utility power is lost. The ATS then transfers the load to the generator set.
When utility power is restored, the transfer switch transfers the load back to utility, runs the generator set with no load to cool down the engine, and then stops the generator set.
2.3.3 Remote Starting and Stopping
A remote switch connected to terminals 3 and 4 can be used to start and stop the generator set. Close the switch to start and run the generator set. Open the switch to stop the generator set.
Run the generator set with no load for at least 2 minutes to ensure adequate engine cooldown.
2.3.4 Engine Start Crank Cycle
The controller attempts to start the generator set three times (three crank cycles, 15 seconds crank and 15 seconds off). If the generator set does not start in three attempts, the system shuts down on an overcrank fault. See Section 2.5.
Cranking 1, 2, and 3 are displayed during the crank cycle. Pressing the OFF button during the crank cycle stops the cranking. No other buttons are acknowledged during the crank cycle.
D Section 4.5 for the DC2 controller
TP-6804 12/11 21Section 2 Generator Set Operation
2.3.5 Engine Cooldown
The engine cooldown time delay allows the engine to run after the loads have been removed.
The engine cooldown time delay is set to 5 minutes. The engine stops before the cooldown time delay expires if the temperature drops below the cooled-down
temperature level, or if the temperature rises above the high limit during the cooldown cycle.
If a transfer switch other than the Model RXT is used, an additional engine cooldown time delay may be programmed on the transfer switch. To allow the smart engine cooldown on the RDC2 controller to operate most efficiently, set the cooldown time on the transfer switch controller to zero or the minimum time allowed. Refer to the instructions provided with the transfer switch for more information.
2.3.6 Automatic Operation with Model RXT Transfer Switch
The Model RXT transfer switch connects to the RDC2 controller through the ATS interface board on the transfer switch. Also see the Model RXT Transfer Switch Operation/Installation Manual for more information about transfer switch operation.
The controller must be in AUTO mode for automatic transfer switch operation.
Automatic Stop with Engine Cooldown
1. When the utility source is restored, the Emergency-to-Normal time delay starts.
2. When the Emergency-to-Normal time delay expires, the load is transferred to the utility.
3. The generator set runs through the engine cooldown cycle and then stops.
2.3.7 Automatic Operation with Model RDT or RSB Transfer Switches
If a Kohler Model RDT or RSB transfer switch is used, the engine start contacts from the ATS must be connected to engine start leads 3 and 4 on the generator set.
The controller must be in AUTO mode to respond to remote start/stop signals from an ATS or remote switch. Press the AUTO button to put the controller into automatic mode.
Automatic Start
The RDC2 controller receives utility source voltage sensing data from the Model RXT transfer switch.
1. If the utility source voltage falls below an acceptable level, the controller starts the engine start time delay.
2. If the utility source is not restored before the time delay expires, the generator set starts.
3. After the Normal-to-Emergency time delay, the ATS is signaled to transfer the load to the emergency source.
Automatic Start
The engine start contacts on the ATS close to signal the generator set to start, and remain closed while the generator set is running.
Automatic Stop
The engine start contacts on the ATS open to signal the generator set to stop.
TP-6804 12/1122 Section 2 Generator Set Operation