Engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
Product Identification Information
Product identification numbers determine service parts.
Record the product identification numbers in the spaces
below immediately after unpacking the products so that
the numbers are readily available for future reference.
Record field-installed kit numbers after installing the
kits.
Generator Set Identification Numbers
Record the product identification numbers from the
generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory NumberAccessory Description
Controller Identification
Record the controller description from the generator set
operation manual, spec sheet, or sales invoice.
Controller Description
Engine Identification
Record the product identification information from the
engine nameplate.
Appendix A Abbreviations69..................................................................
TP-6804 12/11Table of Contents
Notes
TP-6804 12/116
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS.
Electromechanicalequipment,
including generator sets, transfer
switches, switchgear, and accessories,
can cause bodily harm and pose
life-threateningdangerwhen
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely.Read and follow all safety
precautions and instructions. SAVE
THESE INSTRUCTIONS.
This manual has several types of safety
precautions and instructions: Danger,
Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a
hazardthatwillcausesevere
Caution indicates the presence of a
hazard that will or can cause minorpersonal injury or property damage.
NOTICE
Noticecommunicatesinstallation,
operation, or maintenance information
that is safety related but not hazard
related.
Safety decals affixed to the equipment
in prominent places alert the operator
or service technician to potential
hazards and explain how to act safely.
The decals are shown throughout this
publicationtoimproveoperator
recognition.Replace missing or
damaged decals.
Accidental Starting
WARNING
Accidental starting.
Can cause severe injury or death.
Disconnect the battery cables before
working on thegenerator set.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last
when reconnecting the battery.
Disablingthegeneratorset.
Accidentalstartingcancause
severe injury or death.Before
working on the generator set or
equipment connected to the set,
disable the generator set as follows:
(1) Press the generator set off/reset
button to shut down the generator set.
(2) Disconnect the power to the battery
charger, if equipped. (3) Remove the
battery cables, negative (--) lead first.
Reconnect the negative (--) lead last
when reconnecting the battery. Follow
these precautions to prevent the
starting of the generator set by the
remote start/stop switch.
Battery
WARNING
Sulfuric acid in batteries.
Can cause severe injury or death.
Wearprotectivegogglesand
clothing.Battery acid may cause
blindness and burn skin.
WARNING
Explosion.
Can cause severe injury or death.
Relays in the battery charger
cause arcs or sparks.
Locate the battery in a well-ventilated
area. Isolatethe battery charger from
explosive fumes.
Battery electrolyte is a diluted
sulfuric acid. Battery acid can cause
severe injury or death. Battery acid
can cause blindness and burn skin.
Alwayswearsplashproofsafety
goggles, rubber gloves, and boots
when servicing the battery. Do not
open a sealed battery or mutilate the
battery case. Ifbattery acid splashes in
the eyes or on the skin, immediately
flush the affected area for 15 minutes
with large quantities of clean water.
Seek immediate medical aid in the case
of eye contact. Never add acid to a
battery after placing the battery in
service, as this may result in hazardous
spattering of battery acid.
Battery acid cleanup. Battery acid
can cause severe injury or death.
Battery acid is electrically conductive
and corrosive. Add 500 g (1 lb.) of
bicarbonate of soda (baking soda) to a
containerwith4L(1gal.)ofwaterand
mix the neutralizing solution. Pour the
neutralizing solution on the spilled
battery acid and continue to add the
neutralizing solution to the spilled
battery acid until all evidence of a
chemicalreaction(foaming)has
ceased. Flush the resulting liquid with
water and dry the area.
TP-6804 12/117Safety Precautions and Instructions
Battery gases. Explosion can cause
severe injury or death. Battery gases
can cause an explosion. Do not smoke
or permit flames or sparks to occur near
a battery at any time, particularly when
it is charging. Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove all jewelry before servicing the
equipment. Discharge static electricity
from your body before touching
batteries by first touching a grounded
metal surface away from the battery. To
avoid sparks, do not disturb the battery
charger connections while the battery
is charging. Always turn the battery
charger off before disconnecting the
battery connections.Ventilate the
compartments containing batteries to
prevent accumulation of explosive
gases.
Battery short circuits.Explosion
can cause severe injury or death.
Short circuits can cause bodily injury
and/orequipmentdamage.
Disconnectthebatterybefore
generatorsetinstallationor
maintenance.Remove all jewelry
before servicing the equipment. Use
tools with insulated handles. Remove
the negative (--) lead first when
disconnecting the battery. Reconnect
the negative (--) lead last when
reconnecting the battery.Never
connect the negative (--) battery cable
to the positive (+) connection terminal
of the starter solenoid. Do not test the
battery condition by shorting the
terminals together.
Engine Backfire/Flash
Fire
WARNING
Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.
Servicing the air cleaner. A sudden
backfire can cause severe injury or
death. Do not operate the generator
set with the air cleaner removed.
Servicing the fuel system. A flash
fire can cause severe injury or death.
Do not smoke or permit flames or
sparks near the carburetor, fuel line,
fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors.
Catch fuels in an approved container
when removing the fuel line or
carburetor.
Combustible materials. A fire can
cause severe injuryor death.
Generator set engine fuels and fuel
vapors are flammable and explosive.
Handle these materials carefully to
minimize the risk of fire or explosion.
Equip the compartment or nearby area
with a fully charged fire extinguisher.
Select a fire extinguisher rated ABC or
BCforelectricalfiresoras
recommended by the local fire code or
an authorized agency.Train all
personnelonfireextinguisher
operationandfireprevention
procedures.
Exhaust System
WARNING
Carbon monoxide.
Cancauseseverenausea,
fainting, or death.
Theexhaust systemmustbe
leakproof and routinely inspected.
Generator set operation.Carbon
monoxide can cause severe nausea,
fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Avoid
breathing exhaust fumes when working
on or near the generator set. Never
operate the generator set inside a
building. Never operate the generator
set where exhaust gas could seep
inside or be drawn into a potentially
occupied building through windows, air
intake vents, or other openings.
Carbonmonoxidedetectors.
Carbon monoxide can cause severe
nausea, fainting, or death. Install
carbon monoxide detectors on each
level of any building adjacent to the
generator set. Locate the detectors to
adequatelywarnthebuilding’s
occupants of the presence of carbon
monoxide.Keepthe detectors
operational at all times. Periodically
test and replace the carbon monoxide
detectorsaccordingtothe
manufacturer’s instructions.
Carbonmonoxidesymptoms.
Carbon monoxide can cause severe
nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in
exhaust gases. Carbon monoxide is an
odorless,colorless,tasteless,
nonirritating gas that can cause death if
inhaled for even a short time. Carbon
monoxide poisoning symptoms include
but are not limited to the following:
D Light-headedness, dizziness
D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms
and carbon monoxide poisoning is
possible, seek fresh air immediately
and remain active. Do not sit, lie down,
or fall asleep.Alert others to the
possibilityofcarbonmonoxide
poisoning. Seek medical attention if
the condition of affected persons does
not improve within minutes of breathing
fresh air.
TP-6804 12/118Safety Precautions and Instructions
Fuel System
Hazardous Noise
WARNING
WARNING
Explosive fuel vapors.
Can cause severe injury or death.
Use extreme care when handling,
storing, and using fuels.
The fuel system.Explosive fuel
vapors can cause severe injury or
death.Vaporized fuels are highly
explosive. Use extreme care when
handling and storing fuels. Store fuels
inawell-ventilatedareaawayfrom
spark-producing equipment and out of
the reach of children. Never add fuel to
the tank while the engine is running
because spilled fuel may ignite on
contact with hot parts or from sparks.
Do not smoke or permit flames or
sparks to occur near sources of spilled
fuel or fuel vapors. Keep the fuel lines
and connections tight and in good
condition. Do not replace flexible fuel
lines with rigid lines.Use flexible
sections to avoid fuel line breakage
caused by vibration. Donot operate the
generator set in the presence of fuel
leaks, fuel accumulation, or sparks.
Repair fuel systems before resuming
generator set operation.
Gas fuel leaks.Explosive fuel
vapors can cause severe injury or
death. Fuel leakage can cause an
explosion. Check the LP vapor gas or
natural gas fuel system for leakage by
using a soap and water solution with
the fuel system test pressurized to
6--8 ouncespersquareinch
(10--14 inches water column). Do not
use a soap solution containing either
ammonia or chlorine because both
prevent bubble formation. A successful
test depends on the ability of the
solution to bubble.
CAUTION
Hazardous noise.
Can cause hearing loss.
Never operate the generator set
without a muffler or with a faulty
exhaust system.
Engine noise. Hazardous noise can
cause hearing loss. Generator sets
not equipped with sound enclosures
can produce noise levels greater than
105 dBA. Prolonged exposure to noise
levels greater than 85 dBA can cause
permanent hearing loss. Wear hearing
protection when near an operating
generator set.
Hazardous Voltage/
Moving Parts
DANGER
Hazardous voltage.
Will cause severe injury or death.
This equipment must be installed and
servicedbyqualifiedelectrical
personnel.
WARNING
Hazardous voltage.
Can cause severe injury or death.
Moving parts.
Hazardous voltage.
Backfeed to the utility system can
cause property damage, severe
injury, or death.
If the generator set is used for
standby power, install an automatic
transfer switch to prevent inadvertent
interconnection ofstandby and
normal sources of supply.
CAUTION
Welding the generator set.
Cancausesevereelectrical
equipment damage.
Never weld components of the
generatorsetwithoutfirst
disconnecting the battery, controller
wiring harness, and engine electronic
control module (ECM).
Grounding electrical equipment.
Hazardousvoltagecancause
severe injury or death. Electrocution
is possible whenever electricity is
present. Ensure you comply with all
applicablecodes andstandards.
Electrically ground the generator set,
transfer switch, and related equipment
and electrical circuits. Turn off the main
circuit breakers of all power sources
before servicing the equipment. Never
contact electrical leads or appliances
when standing in water or on wet
ground because these conditions
increase the risk of electrocution.
Operate the generator set only when
all guards and electrical enclosures
areinplace.
TP-6804 12/119Safety Precautions and Instructions
Welding on the generator set. Can
cause severe electrical equipment
damage.Before welding on the
generator set perform the following
steps: (1) Remove the battery cables,
negative (--) lead first. (2) Disconnect
all engine electronic control module
(ECM) connectors. (3) Disconnect all
generator set controller and voltage
regulator circuit board connectors.
(4) Disconnect the engine batterychargingalternatorconnections.
(5) Attach the weld ground connection
close to the weld location.
Hot Parts
WARNING
Hot engine and exhaust system.
Can cause severe injury or death.
Do not work on the generator set until
it cools.
Notice
NOTICE
Canadian installations only.For
standby service connect the output of
the generator set to a suitably rated
transfer switch in accordance with
Canadian Electrical Code, Part 1.
Connecting the battery and the
battery charger. Hazardous voltage
can cause severe injury or death.
Reconnectthebatterycorrectly,
positive to positive and negative to
negative, to avoid electrical shock and
damage to the battery charger and
battery(ies).Haveaqualified
electrician install the battery(ies).
Shortcircuits.Hazardous
voltage/current can cause severe
injury or death. Short circuits can
cause bodily injury and/or equipment
damage.Do not contact electrical
connections with tools or jewelry while
makingadjustmentsorrepairs.
Remove all jewelry before servicing the
equipment.
Electrical backfeed to the utility.
Hazardous backfeed voltage can
cause severe injury or death. Install
a transfer switch in standby power
installations to prevent the connection
of standby and other sources of power.
Electrical backfeedinto a utility
electrical system can cause severe
injury or death to utility personnel
working on power lines.
Servicing the exhaust system. Hot
parts can cause severe injury or
death. Do not touch hot engine parts.
The engine and exhaust system
components become extremely hot
during operation.
Servicing the engine heater. Hot
parts can cause minor personal
injury or property damage. Installthe
heater before connecting it to power.
Operating the heater before installation
can cause burns and component
damage.Disconnect power to the
heater and allow it to cool before
servicing the heater or nearby parts.
Heavy Equipment
WARNING
Unbalanced weight.
Improper lifting can cause severe
injury or death and equipment
damage.
Do not use lifting eyes.
Lift the generator set using lifting bars
inserted through the lifting holes on
the skid.
TP-6804 12/1110 Safety Precautions and Instructions
Introduction
This manual provides operation and maintenance
instructionsforresidential/commercialmodel
14/20RESA and RESAL generator sets equipped with
Kohler RDC2 or DC2 generator set/transfer switch
controllers.See Figure 1.The RDC2 and DC2
controllers control the generator set and the optional
Model RXT transfer switch.
This generator set is approved for use in stationary
applications in locations served by a reliable utility
power source. Have the generator set installed by an
authorized distributor/dealer or service technician.
Refer to TP-6803, Installation Manual, for installation
instructions.
Information in this publication represents data available
at the time of print. Kohler Co. reserves the right to
change this publication and the products represented
without notice and without any obligation or liability
whatsoever.
Read this manual and carefully follow all procedures
and safety precautions to ensure proper equipment
operation and to avoid bodily injury. Read and follow the
Safety Precautions and Instructions section at the
beginning of this manual. Keep this manual with the
equipment for future reference.
The equipment service requirements are very important
to safe and efficient operation. Inspect the parts often
and perform required service at the prescribed intervals.
Obtain service from an authorized service distributor/
dealer to keep equipment in top condition.
List of Related Literature
Figure 2 identifies related literature available for the
generator sets covered in this manual. Only trained and
qualified personnel should install or service the
generator set.
Literature TypePart Number
Installation Manual, Model
14/20RESA/RESAL Generator Set
Operation/Installation Manual, Model
RXT Automatic Transfer Switch
Operation/Installation Manual, Model
RDT Automatic Transfer Switch
Installation Manual, Model RSB
Automatic Transfer Switch
Operation Manual, Model RSB
Automatic Transfer Switch
Service Manual, 14/20RESA/RESAL
Generator Set
Operation Manual, OnCuer SoftwareTP-6796
Operation Manual, SiteTecht SoftwareTP-6701
Installation Instructions, Load Control
Module (LCM)
The following illustration shows a typical generator set
nameplate. Copy the model, serial, and specification
numbers from the nameplate into the spaces provided in
the product information section on the inside front cover
of this manual. See the service views in Section 1.8 for
the nameplate location.
GM12070
The Emission Compliance Period referred to on the
Emission Control or Air Index label indicates the number
of operating hours for which the engine has been shown
to meet CARB or EPA emission requirements. Figure 3
provides the engine compliance period (in hours)
associated with the category descriptor, which may be
found on the certification label.
Emission Compliance Period
EPA
CARB
Category C
250 hours
Moderate
125 hours
Category B
500 hours
Intermediate
250 hours
Category A
1000 hours
Extended
500 hours
Figure 3Emission Compliance Period
Refer to the certification label for engine displacement.
The exhaust emission control system for the CH740
engines (14RESA/RESAL) is EM for U.S. EPA,
California, and Europe.
The exhaust emission control system for the CH1000
engine (20RESA/RESAL) is EM for U.S. EPA,
California, and Europe.
Emission Information
The Kohlerr Model CH740 engine used on the
14RESA/RESAL generator set is certified to operate
using natural gas or propane fuel.
The Kohler Model CH1000 engine used on the
20RESA/RESAL generator set is certified to operate
using propane fuel. The CH1000 engine used on the
20RESA/RESAL may be operated on natural gas fuel
because it is excluded from the requirements of
40 CFR 1048 as a stationary engine.
The engine used in the Model 20RESA/RESAL
generator set is certified for emergency standby use
only.
TP-6804 12/1112 Introduction
Service Assistance
For professional advice on generator set power
requirements and conscientious service, please contact
your nearest Kohler distributor or dealer.
D Consult the Yellow Pages under the heading
Generators—Electric.
D VisittheKohlerPower Systemswebsiteat
KohlerPower.com.
D Look at the labels and stickers on your Kohler product
or review the appropriate literature or documents
included with the product.
D Call toll free in the US and Canada 1-800-544-2444.
D Outside the US and Canada, call the nearest regional
office.
Headquarters Europe, Middle East, Africa
(EMEA)
Kohler Power Systems
3 rue de Brennus
93200 Saint Denis
France
Phone: (33) 1 49 178300
Fax:(33) 1 49 178301
Asia Pacific
Power Systems Asia Pacific Regional Office
Singapore, Republic of Singapore
Phone: (65) 6264-6422
Fax:(65) 6264-6455
China
North China Regional Office, Beijing
Phone: (86) 10 6518 7950
(86) 10 6518 7951
(86) 10 6518 7952
Fax:(86) 10 6518 7955
East China Regional Office, Shanghai
Phone: (86) 21 6288 0500
Fax:(86) 21 6288 0550
India, Bangladesh, Sri Lanka
India Regional Office
Bangalore, India
Phone: (91) 80 3366208
(91) 80 3366231
Fax:(91) 80 3315972
Japan, Korea
North Asia Regional Office
Tokyo, Japan
Phone: (813) 3440-4515
Fax:(813) 3440-2727
Latin America
Latin America Regional Office
Lakeland, Florida, USA
Phone: (863) 619-7568
Fax:(863) 701-7131
TP-6804 12/1113Service Assistance
Notes
TP-6804 12/1114 Service Assistance
Section 1 Descriptions and Service Views
1.1Introduction
The generator set specification sheets provide specific
generator and engine information. Refer to the spec
sheet for data not supplied in this manual. Consult the
generator set service manual, engine operation manual,
and engine service manual for additional specifications.
Obtain copies of the latest spec sheets, manuals,
diagrams, and drawings from your local distributor/
dealer.
1.2Engine
The generator set has a four-cycle, twin cylinder, aircooled Kohlerr engine. The engine operates on cleanburning natural gas or propane (LP) vapor. Engine
features include:
D Efficient overhead valve design and full pressure
lubrication for maximum power, torque, and reliability
under all operating conditions.
D Dependable, maintenance-free electronic ignition.
D Precision-formulated cast iron construction of parts
subjected to the most wear and tear.
1.4Alternator
The generator uses Kohler’s unique PowerBoostt
voltage regulation system, which provides instant
response to load changes.
PowerBoosttensures reliable motor starting and
consistent voltage levels.PowerBoostt utilizes a
voltage excitation system that employs a winding
independent of the main output windings to provide
excitation voltage.
1.5Transfer Switch
The RDC2 and DC2 controllers are designed to
interface with and control the Kohler Model RXT
Automatic Transfer Switch (ATS). Do not use the Kohler
Model RRT transfer switch with the RDC2 or DC2
controller.
If the power system uses a different model transfer
switch, the RDC2 and DC2 controllers will not control the
transfer switch. An ATS other than the Model RXT must
be equipped with a transfer switch controller and engine
start contacts that connect to the remote engine start
terminals on the generator set.
D Field-convertible multi-fuel systems that allow fuel
changeover from natural gas to LP vapor (and viceversa)whilemaintainingCARBemission
certification.
D Digital spark advance optimizes ignition timing for the
selected fuel.
1.3Generator Set Enclosure
The generator set is housed in an exclusive engineered
composite enclosure that is corrosion-proof, even in
harsh seaside environments, and impact-resistant,
even in cold weather. The enclosure has a hinged,
locking roof that allows easy access to the generator set
controller when required, but locks securely to prevent
unauthorized access.
To open the roof, insert the tool provided with the
enclosure and turn counterclockwise 1/4 turn. Then just
raise the roof. The roof stays open until you are ready to
close it.
Be sure to close and lock the enclosure, and keep the
tool in a secure location.
1.6Controllers
RESA models are equipped with the Residential Digital
Control (RDC2). RESAL models use the Digital Control
(DC2). See Figure 1-1.
The controller provides integrated control for the
generator set, Kohlerr Model RXT transfer switch,
programmable interface module (PIM), and load control
module (LCM).
RDC2 (RESA)DC2 (RESAL)
Figure 1-1Controllers
TP-6804 12/1115Section 1 Descriptions and Service Views
The controller’s 2-line LCD screen displays status
messages and system settings that are clear and easy
to read, even in direct sunlight or low light.
D Front-access mini USB connector for SiteTecht
connection
D Front access mini-breaker protects the alternator
RDC2 Controller Features
D Six-button keypad
d OFF, AUTO, and RUN pushbuttons
d Select and arrow buttons for access to system
configuration and adjustment menus
D LED indicators for OFF, AUTO, and RUN modes
D LED indicators for utility power and generator set
source availability and ATS position (Model RXT
transfer switch required)
D LCD display
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for
excellent visibility in all lighting conditions
D Scrolling system status display
d Generator set status
d Voltage and frequency
d Engine temperature
d Oil pressure
d Battery voltage
d Engine runtime hours
D Date and time displays
D Smart engine cooldown senses engine temperature
D Digitalisochronousgovernortomaintain
steady-state speed at all loads
D Digital voltage regulation: ±0.5% RMS no-load to
full-load
D Automatic start with programmed cranking cycle
D Programmable exerciser can be set to start
automatically on any future day and time, and run
every week or every two weeks
D Exercise modes
D Integral Ethernet connector for Kohlerr OnCuet
D Built-in 2.5 amp battery charger
D Remote two-wire start/stop capability for optional
connection of Model RDT or RSB transfer switches
D Diagnostic messages
d Displays diagnostic messages for the engine,
generator, Model RXT transfer switch,
programmable interface module (PIM), and load
control module (LCM)
d Over 70 diagnostic messages can be displayed
D Maintenance reminders
D System settings
d System voltage, frequency, and phase
d Voltage adjustment
d Measurement system, English or metric
D ATS status (Model RXT ATS required)
d Source availability
d ATS position (normal/utility or
emergency/generator)
d Source voltage and frequency
D ATS control (Model RXT ATS required)
d Source voltage and frequency settings
d Engine start time delay
d Transfer time delays
d Voltage calibration
d Fixed pickup and dropout settings
D ProgrammableInterfaceModule(PIM)status
displays
d Input status (active/inactive)
d Output status (active/inactive)
d Unloaded weekly exercise with complete system
diagnostics
d Unloaded full-speed exercise
d Loaded full-speed exercise (Model RXT ATS
required)
D Load control module (LCM) menus
d Load status
d Test function
TP-6804 12/1116 Section 1 Descriptions and Service Views
DC2 Controller Features
D Automatic start with programmed cranking cycle
D Four-button keypad:OFF, AUTO, RUN, and
EXERCISE pushbuttons
D LED indicators for OFF, AUTO, and RUN modes
D LCD display:
d Two lines x 16 characters per line
d Backlit display with adjustable contrast for
excellent visibility
D Scrolling system status display
d Generator set status
d Voltage and frequency
d Engine temperature
d Oil pressure
d Battery voltage
d Engine runtime hours
d Maintenance reminders
d OnCue status (connected/disconnected)
D Date and time displays
D Smart engine cooldown senses engine temperature
D Exercise modes
d Unloaded weekly exercise with complete system
diagnostics
d Unloaded full-speed exercise
d Loaded full-speed exercise (Model RXT ATS
required)
D Front-access mini USB connector for SiteTecht
connection
D Front access mini-breaker protects the alternator
D Integral Ethernet connector for Kohlerr OnCuet
D Built-in 2.5 amp battery charger
D Remote two-wire start/stop capability for optional
connection of Model RDT or RSB transfer switches
D Diagnostic messages
d Displays diagnostic messages for the engine,
generator set, model RXT transfer switch, and
optional programmable interface module (PIM)
and load control module (LCM)
d Over 70 diagnostic messages can be displayed
D Digitalisochronousgovernortomaintain
steady-state speed at all loads
D Digital voltage regulation: ±0.5% RMS no-load to
full-load
D A laptop computer and Kohlerr SiteTech software
can be used to change system settings or upgrade
controller firmware.
TP-6804 12/1117Section 1 Descriptions and Service Views
1.7Accessories
The following optional accessories are offered for the
RESA and RESAL generator sets.
1.7.1Carburetor Heater
An optional carburetor heater is recommended for
improved cold starting in locations where the ambient
temperature drops below 0_C (32_F). The carburetor
heater prevents condensation and carburetor icing. The
heater requires a continuous source of 120 VAC power.
See the generator set Installation manual for more
information.
1.7.4Programmable Interface Module
(PIM)
The optional Programmable Interface Module (PIM)
providestwoprogrammableinputsandsix
programmable dry contact outputs for connection to
customer-supplied equipment.The outputs are
controlled by the RDC2 controller, and can also be
controlled remotely using the OnCue program.
The PIM is mounted in a NEMA 3R aluminum enclosure,
which can be mounted indoors or outdoors. See the
installation instructions provided with the PIM.
1.7.5Load Control Module (LCM)
1.7.2Fuel Regulator Heater (20RESA
and RESAL only)
Anoptionalfuelregulatorheaterforthe
20RESA/20RESAL is recommended for improved cold
starting in locations where the ambient temperature
drops below --18_C(0_F).The heater requires a
continuous source of 120 VAC power.
See the generator set Installation manual for more
information.
1.7.3OnCue Home Generator
Management System
The Kohlerr OnCuet Home Generator Management
System allows monitoring and control of your RESA or
RESAL generator set from a personal computer located
in your home or at other remote locations. OnCuet can
also be configured to send email or text message
notifications in the event of a generator set fault.
Note: Be sure to obtain the correct version of the
OnCuet kit for the RDC2/DC2 controller.
The optional Load Control Module (LCM) provides an
automatic load management system to comply with
Section 702.5 of NEC 2008. The installer is responsible
for ensuring that the power system installation complies
with all applicable state and local codes.
The LCM automatically manages up to six residential
loads. Four power relays are provided for management
of non-essential secondary loads, and two relays are
available to control two independent air conditioner
loads.
The LCM is controlled by the RDC2/DC2 controller. The
load on the generator set is monitored, and loads are
added or shed in the order of their priority.See
specification sheet G6-120 and the LCM installation
instructions for more information.
OnCuet version 3.0 is required for RESA/RESAL
generator sets equipped with the RDC2/DC2 controller.
OnCuet versions numbered 1.x are not compatible
with the RDC2/DC2 controller.
TP-6804 12/1118 Section 1 Descriptions and Service Views
TP-6804 12/1119Section 1 Descriptions and Service Views
Notes
TP-6804 12/1120 Section 1 Descriptions and Service Views
Section 2 Generator Set Operation
2.1Prestart Checklist
To ensure continued satisfactory operation, perform the
following checks or inspections before or at each
startup, as designated, and at the intervals specified in
the service schedule. In addition, some checks require
verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner
element to prevent unfiltered air from entering the
engine.
Air Inlets. Check for clean and unobstructed air inlets.
Battery. Check for tight battery connections. Consult
the battery manufacturer’s instructions regarding
battery care and maintenance.
Exhaust System.Check for exhaust leaks and
blockages. Check the muffler condition.
D Inspect the exhaust system components for cracks,
leaks, and corrosion. Check for tight exhaust system
connections.
D Check for corroded or broken metal parts and replace
them as needed.
D Check that the exhaust outlet is unobstructed.
Oil Level.Check the oil level before starting the
generator set and at the intervals given in Section 5,
Scheduled Maintenance. Maintain the oil level at or
near, not over, the full mark on the dipstick.
Operating Area.Check for obstructions that could
block the flow of cooling air. Keep the air intake area
clean. Do not leave rags, tools, or debris on or near the
generator set.
2.2Exercising the Generator Set
Operate the generator set without load once each week
for 20 minutes. See Section 2.4 for information about
loaded and unloaded exercise modes. For instructions
to set the exerciser, see:
D Section 3.6 for the RDC2 controller
2.3Generator Set Operation
2.3.1Local Starting and Stopping
Start: Press the RUN button to immediately start the
generator set.
Stop: Press the OFF button. The engine stops.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
2.3.2Automatic Starting and Stopping
An automatic transfer switch monitors the utility power
and signals the generator set to start when utility power
is lost. The ATS then transfers the load to the generator
set.
When utility power is restored, the transfer switch
transfers the load back to utility, runs the generator set
with no load to cool down the engine, and then stops the
generator set.
2.3.3Remote Starting and Stopping
A remote switch connected to terminals 3 and 4 can be
used to start and stop the generator set. Close the
switch to start and run the generator set. Open the
switch to stop the generator set.
Run the generator set with no load for at least 2 minutes
to ensure adequate engine cooldown.
2.3.4Engine Start Crank Cycle
The controller attempts to start the generator set three
times (three crank cycles, 15 seconds crank and
15 seconds off). If the generator set does not start in
three attempts, the system shuts down on an overcrank
fault. See Section 2.5.
Cranking 1, 2, and 3 are displayed during the crank
cycle. Pressing the OFF button during the crank cycle
stops the cranking. No other buttons are acknowledged
during the crank cycle.
D Section 4.5 for the DC2 controller
TP-6804 12/1121Section 2 Generator Set Operation
2.3.5Engine Cooldown
The engine cooldown time delay allows the engine to
run after the loads have been removed.
The engine cooldown time delay is set to 5 minutes. The
engine stops before the cooldown time delay expires if
thetemperaturedropsbelowthecooled-down
temperature level, or if the temperature rises above the
high limit during the cooldown cycle.
If a transfer switch other than the Model RXT is used, an
additional engine cooldown time delay may be
programmed on the transfer switch. To allow the smart
engine cooldown on the RDC2 controller to operate
most efficiently, set the cooldown time on the transfer
switch controller to zero or the minimum time allowed.
Refer to the instructions provided with the transfer
switch for more information.
2.3.6Automatic Operation with Model
RXT Transfer Switch
The Model RXT transfer switch connects to the RDC2
controller through the ATS interface board on the
transfer switch.Also see theModel RXT Transfer
SwitchOperation/InstallationManualformore
information about transfer switch operation.
The controller must be in AUTO mode for automatic
transfer switch operation.
Automatic Stop with Engine Cooldown
1. Whentheutilitysourceisrestored,the
Emergency-to-Normal time delay starts.
2. When theEmergency-to-Normaltime delay
expires, the load is transferred to the utility.
3. The generator set runs through the engine
cooldown cycle and then stops.
2.3.7Automatic Operation with Model
RDT or RSB Transfer Switches
If a Kohler Model RDT or RSB transfer switch is used,
the engine start contacts from the ATS must be
connected to engine start leads 3 and 4 on the generator
set.
The controller must be in AUTO mode to respond to
remote start/stop signals from an ATS or remote switch.
Press the AUTO button to put the controller into
automatic mode.
Automatic Start
The RDC2 controller receives utility source voltage
sensing data from the Model RXT transfer switch.
1. If the utility source voltage falls below an
acceptable level, the controller starts the engine
start time delay.
2. If the utility source is not restored before the time
delay expires, the generator set starts.
3. After the Normal-to-Emergency time delay, the
ATS is signaled to transfer the load to the
emergency source.
Automatic Start
The engine start contacts on the ATS close to signal the
generator set to start, and remain closed while the
generator set is running.
Automatic Stop
The engine start contacts on the ATS open to signal the
generator set to stop.
TP-6804 12/1122 Section 2 Generator Set Operation