Kohler 13EKOZD, 15EKOZD, 11EFKOZD, 13EFKOZD, 16.5EFKOZD Installation Instructions Manual

...
Page 1
Original Issue Date: 6/15
Model: 13EKOZD/11EFKOZD, 15EKOZD/13EFKOZD, 16.5/17.5/19.5/20EFKOZD
Market: Marine
Subject: Siphon Break Kit GM94002 -KP1 for Sound Shielded Units with Front
Connection Panel
TT-1664 6/15
INSTALLATION INSTRUCTIONS
Introduction
Read the entire installation procedure. Perform the steps in the order shown.
Note: Install this siphon break kit on generator sets
equipped with the sound shield kits specified in Figure 1. Do not install these siphon break kits on generator sets without sound shields.
Factory
Model
13EKOZD/11EFKOZD GM93548-KA1 GM93548-KP1
15EKOZD/13EFKOZD GM93548-KA4 GM93548-KP4
17.5/16.5EFKOZD GM93548-KA2 GM93548-KP2
20/19.5EFKOZD GM93548-KA3 GM93548-KP3
Installed Kit
Figure 1 Sound Shield Kits
Field
Installed Kit
Safety Precautions
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before working on the
generator set or equipment connected to the set, disable the generator set as follows: (1) Press the generator set off/reset button to shut down the generator set. (2) Disconnect the power to the battery charger, if equipped. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent the starting of the generator set by the remote start/stop switch.
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death. Keep
hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Moving parts.
Page 2
Installation Procedure
1. Remove the generator set from service.
1.1 Press the generator set master control OFF/RESET button.
1.2 Disconnect the power to the battery charger, if equipped.
1.3 Disconnect the generator set engine starting battery, the negative (--) lead first.
2. Remove the sound shield door and roof.
2.1 Remove the sound shield’s engine-end (front) door and roof (if necessary) to gain access to the generator set hoses inside. See Figure 2.
1
2
2
2
GM89517
4
3
2
1
1. Engine-end (front) door
2. Customer connection panel
3. Button plugs (qty. 2)
4. Roof
Figure 2 Sound Shield
2.2 Open the service doors.
2.3 Release/untighten the three wing nuts located underneath the roof. See Figure 3.
2.4 Lift up the roof.
2.5 Slide the roof towards the service side of the unit for removal.
2.6 Open the front, rear, and non-service side doors as needed.
1. Sound shield roof
2. Wing nut
3. Service door
3
Figure 3 Sound Shield Roof Removal
3. Install the siphon break.
3.1 Remove the 2 button plugs from the customer connection panel. See Figure 2.
3.2 Install the 2 grommets (X-284-42) and 2 hose connectors (344934) to the openings in the customer connection panel. See Figure 8.
3.3 Find and remove the hose (X-312-49) located between the heat exchanger end cap and the exhaust mixer. Save the hose clamps, tee, and pressure switch. Keep the elbow in position on the exhaust mixer.
Nonservice-Side
View
1
2
3
1. Elbow on exhaust mixer (elbow not shown)
2. Tee, pressure switch, and hose clamps
3. Hose (X-312-49)
Figure 4 Hose Removal
2
TT-1664 6/15
Page 3
3.4 Secure the molded hose (276206) to the existing elbow on the exhaust mixer using an existing hose clamp. See Figure 7.
Note: Cuthosetofit.
3.5 Secure the other end of the molded hose to the existing tee/pressure switch assembly using an existing hose clamp.
3.6 Secure the molded hose (276206) to the tee/pressure switch assembly using an existing hose clamp.
Note: Cuthosetofit.
3.7 Route the other end of the molded hose to the left hole in the sound shield’s customer connection panel. Secure the hose with an existing hose clamp.
3.8 Secure the hose (X-312-51) to the heat exchanger end cap. Secure the hose using a hose clamp (X-426-12). See Figure 7.
3.12 Use customer-supplied hose clamps to connect the siphon break (GM32985) to the hoses. Locate the hose clamps 12.7 mm (1/2 in.) from each end of the hose and tighten the clamps.
3.13 Mount the siphon break to the engine stringer or other rigid structure. Keep the siphon break reed valve in a vertical position.
Note: Correct functioning of the reed valve
requires clean operating conditions. Locate the top of the siphon break (reed valve) away from possible accumulated dirt and other contaminants.
Note: Toprevent water leakage on the generator
set, do not mount the siphon break over the generator set.
3.14 Connect the clear flexible plastic tubing (GM34883) to the siphon break cap using a hose clamp (X-426-9) to secure. Route the tubing to a convenient location. This allows the seawater to drip into the bilge and not on the generator set.
3.9 Route the hose from the heat exchanger end cap to the right hole in the sound shield’s customer connection panel. Secure the hose with a hose clamp (X-426-12).
Note: Because of the variety of possible
installations, this kit does not include hoses to connect to the siphon break. See Figure 5 for an ID-size hose selection. Use coolant hoses (SAE 20R1, class B or equivalent) and hoses suitable for marine use. Use corrosion-resistant or stainless steel hose clamps on all fittings.
Kit Number ID-Size Hose, mm (in.)
GM94002-KP1 15.9 (5/8) or 19 (3/4)
Figure 5 Hose Selection
3.10 Determine the required length of hose from each hose connector to the siphon break. Cut two pieces of the customer-supplied hose to the determined length. See Figure 8.
Note: The siphon break must be at least 30 cm
(12 in.) above the waterline during maximum load and generator shutdown condition.
3.15 Siphon break mounting varies with each application. Generally, use brass or stainless steel screws and mount the siphon break using the mounting tabs. Otherwise, use a nylon (conduit-type) pipe clamp.
Note: Mount the siphon break in a location easily
accessable for inspection and servicing.
Note: Ensure that the siphon break cap is tight
before operating the generator set.
4. Restore the generator set to service.
4.1 Check that the generator set is OFF.
4.2 Reconnect the generator set engine starting battery, the negative (--) lead last.
4.3 Reconnect the power to the battery charger, if equipped.
4.4 Start the generator set and check for water leaks.
4.5 Stop the generator set.
4.6 Replace the sound shield’s door and roof.
3.11 Use the customer-supplied hose clamps to connect the hoses to the hose connectors. Locate the hose clamps 12.7 mm (1/2 in.) from each end of the hose and tighten the clamps. See Figure 8.
TT-1664 6/15
3
Page 4
Inspection/Maintenance
1
Service the siphon break during regular exhaust system component inspection. See the generator set operation manual for the service schedule.
Note: The generator set must not be running during the
siphon break inspection.
1. Remove the generator set from service.
1.1 Press the generator set master control OFF/RESET button.
1.2 Disconnect the power to the battery charger, if equipped.
1.3 Disconnect the generator set engine starting battery, the negative (--) lead first.
2. Inspect the siphon break.
2.1 Remove the retaining cap and remove the reed valve for inspection. See Figure 6.
2.2 Use a mild detergent to remove residue and oxidation from the reed valve.
2.3 Clear blockage from the reed valve opening.
2
3
1. Cap
2. Siphon reed valve
3. Mounting base
Figure 6 Siphon Break
3. Restore the generator set to service.
3.1 Check that the generator set is OFF.
3.2 Reconnect the generator set engine starting battery, the negative (--) lead last.
3.3 Reconnect the power to the battery charger, if equipped.
2.4 Replace the siphon break if the reed valve is cracked or if the reed valve material has hardened or deteriorated.
2.5 Install the reed valve into the mounting base with the valve downward. See Figure 6, item 2.
2.6 Install and only finger tighten the retaining cap. Do not overtighten it.
4
TT-1664 6/15
Page 5
Engine-End View
12
Top View
Engine-End View
3
6
4
5
4
2
1
Service-Side View
3
1. Round grommets (X-284-42 qty. 2)
2. Hose connectors (344934 qty. 2)
3. Hose (X-312-51) and hose clamps (X-426-12 qty. 2)
4. Use existing elbow on exhaust mixer.
5. Molded hoses (276206 qty. 2). Cut to fit.
4
5
Figure 7 Hose Locations
GM94002-
1. Customer connection panel
2. Hose connectors, qty. 2
3. Grommets, qty. 2
4. Customer-supplied hose clamps
5. Customer-supplied hoses
6. Siphon break valve
Figure 8 Siphon Break, Installed
Parts List
Siphon Break Kit
Kit: GM94002-KP1
Qty. Description Unique Parts
2 Grommet, round X-284-42 2 Hose, 0.63 in. ID (10 in.) 276206 1 Hose, 0.63 in. ID (34 in.) X-312-51 2 Clamp, hose (0.69/1.25 in.) X-426-12 1 Valve, siphon break GM32985 2 Connector, hose 344934 1 Tubing, clear flexible plastic GM34883 1 Clamp, hose (0.25/0.70 in.) X-426-9
TT-1664 6/15
5
Page 6
Notes
6
TT-1664 6/15
Page 7
Notes
TT-1664 6/15
7
Page 8
KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohlerr generator set distributor for availability.
2015 by Kohler Co. All rights reserved.
8
TT-1664 6/15
Loading...