Kohler 40EOZ, 65EOZ, 50EOZ, 65COZ, 80EOZ Service Manual

...
Service
Marine Generator Sets
Models:
40COZ/33CFOZ, 40EOZ/33EFOZ 50COZ/40CFOZ, 50EOZ/40EFOZ 65COZ/50CFOZ, 65EOZ/55EFOZ
80EOZ/70EFOZ, 99EOZ/80EFOZ
125EOZ/100EFOZ, 150EOZ/125EFOZ
Controllers:
Decision-Makert 3+
Decision-Makert 1 Standard
TP-5737 5/01b
Product Identification Information
Product identification numbers determine service parts. Record the product identification numbers in the spaces below immediately after unpacking the products so that the numbers are readily available for future reference. Record field-installed kit numbers after installing the kits.
Generator Set Identification Numbers
Record the product identification numbers from the generator set nameplate(s).
Model Designation
Specification Number
Serial Number
Accessory Number Accessory Description
Engine Identification
Record the product identification information from the engine nameplate.
Manufacturer
Model Designation
Serial Number
Table of Contents
Product Identification Information Inside front cover............................................
Safety Precautions and Instructions I........................................................
Introduction i...............................................................................
Service Assistance i........................................................................
Section 1 Specifications 1...................................................................
1.1 Introduction 1..........................................................
1.2 Specifications 1.........................................................
1.3 Accessories 2..........................................................
1.3.1 Remote Annunciator Kit 2........................................
1.3.2 Safeguard Breaker 3............................................
1.3.3 Line Circuit Breaker 3...........................................
1.3.4 Run Relay Kit 3.................................................
1.3.5 FASTCHECK Diagnostic Tester (Microprocessor Controller Only) 4....
Section 2 Operation 5.......................................................................
2.1 Fast-Responset II Concepts 5...........................................
2.2 Short Circuit Performance 5..............................................
2.3 Prestart Checklist 6.....................................................
2.4 Marine Inspection 6.....................................................
2.5 Angular Operation 6.....................................................
2.6 Exercising the Generator Set 6...........................................
2.7 Decision-Makert 3+ 16-Light Microprocessor Controller Operation 7..........
2.7.1 Controls and Indicators 8........................................
2.7.2 Fuses and Terminal Strips 9......................................
2.7.3 Auxiliary Fault Lamp Conditions 10.................................
2.7.4 Starting the Generator Set 10......................................
2.7.5 Stopping the Generator Set 10.....................................
2.7.6 Prime Power Mode Operation 11...................................
2.7.7 Fault Shutdowns 11..............................................
2.7.8 Controller Resetting Procedure (Following Fault Shutdown) 12.........
2.7.9 Resetting the Emergency Stop Switch 12............................
2.8 Expanded Decision-Makert 1 Controller Operation 13........................
2.8.1 Controls and Indicators 13........................................
2.8.2 Starting the Generator Set 14......................................
2.8.3 Stopping the Generator Set 14.....................................
2.8.4 Fault Shutdowns 14..............................................
2.8.5 Controller Resetting Procedure (Following Fault Shutdown) 14.........
2.9 Standard Decision-Makert 1 Controller Operation 15.........................
2.9.1 Controls and Indicators 15........................................
2.9.2 Starting the Generator Set 15......................................
2.9.3 Stopping the Generator Set 15.....................................
2.9.4 Fault Shutdowns 16..............................................
2.9.5 Controller Resetting Procedure (Following Fault Shutdown) 16.........
Section 3 Scheduled Maintenance 17..........................................................
3.1 General Maintenance 17..................................................
3.2 Generator Bearing 18....................................................
3.3 Storage Procedure 18....................................................
3.3.1 Lubrication System 18............................................
3.3.2 Cooling System 18...............................................
3.3.3 Fuel System 18..................................................
3.3.4 Exterior 18......................................................
3.3.5 Battery 18.......................................................
Section 4 General Troubleshooting 19.........................................................
TP-5737 5/01 Table of Contents
Table of Contents, continued
Section 5 Decision-Makert 3+ Troubleshooting 23.............................................
5.1 Decision-Makert 3+ Controller 23.........................................
5.1.1 Decision-Maker 3+ Circuit Board Terminal/Connector Identification 25...
5.1.2 Fault Shutdowns, Decision-Maker 3+ Controller 31...................
5.2 Microprocessor Controller Relay Descriptions 32.............................
5.2.1 K1 Relay, Starter Solenoid 32......................................
5.2.2 K2 Relay, Crank Relay on Main Circuit Board 32.....................
5.2.3 K3 Relay, Run Relay on Main Circuit Board 32.......................
5.2.4 K4 Relay, Emergency Stop Relay on Main Circuit Board 32............
5.2.5 K5 Relay, Governor Control Relay 32...............................
5.3 Microprocessor Controller 32..............................................
5.3.1 Troubleshooting 33...............................................
5.3.2 Fuses 34.......................................................
5.4 FASTCHECK Features and Operation 39...................................
5.4.1 Features 39.....................................................
5.4.2 Application 40...................................................
5.4.3 Connect/Operate Procedure 40....................................
5.4.4 Overcrank 41....................................................
5.4.5 Controller Speed Sensor Circuitry 41...............................
5.4.6 Generator Condition Indicator Terminal (TB1 Terminal Strip) 42.........
Section 6 Decision-Makert 1 Controller Troubleshooting 45....................................
6.1 Decision-Makert 1 and Decision-Makert 1 Expanded Relay Controller 45......
6.2 Relay Controller 52.......................................................
Section 7 Component Testing and Adjustment 57..............................................
7.1 Generator Troubleshooting 57.............................................
7.2 Generator Testing 60.....................................................
7.2.1 No Output On Any Phase 60.......................................
7.2.2 Overvoltage 62..................................................
7.2.3 Fluctuating Voltage 62............................................
7.3 LED Circuit Board Test 62.................................................
7.4 SCR Assembly and Photo Transistor Board 64...............................
7.4.1 Concept and Equipment 64........................................
7.4.2 SCR Assembly and Photo Transistor Board Test 64...................
7.5 Automatic Voltage Regulator (AVR) Operation and Adjustment 66..............
7.6 Stator 68................................................................
7.7 Generator Field 69.......................................................
7.8 Exciter Armature 70......................................................
7.9 End Bracket Removal and Replacement 72..................................
7.10 Speed Sensor Test 73....................................................
7.11 Current Transformers 73..................................................
7.11.1 Function and Application 73.......................................
7.11.2 Testing 74.......................................................
7.12 Reactive Droop Compensator 74...........................................
7.12.1 Function and Application 74.......................................
7.12.2 Initial Adjustment 74..............................................
7.12.3 Final Adjustment 75..............................................
7.12.4 Testing 75.......................................................
7.13 Gauge Senders 76.......................................................
7.13.1 Oil Pressure Sender Testing 76....................................
7.13.2 Water Temperature Sender Testing 76..............................
TP-5737 5/01Table of Contents
Table of Contents, continued
7.14 Governor Adjustment 77..................................................
7.14.1 Mechanical Governor 77..........................................
7.14.2 Electronic Governor, Barber-Colman Dyna 2500
7.14.3 Electronic Governor, Barber-Colman Dyna 70025
Section 8 Disassembly/Reassembly 83........................................................
8.1 Disassembly 87..........................................................
8.2 Reassembly 89..........................................................
Section 9 Wiring Diagrams 95................................................................
9.1 Voltage Reconnection 116.................................................
9.1.1 Introduction 116...................................................
9.1.2 Voltage Reconnection Procedure 116................................
9.2 Overvoltage Shutdown Adjustment 119......................................
9.3 Generator Set Frequency Change and Adjustment 121.........................
9.3.1 Frequency Change 121............................................
9.3.2 Frequency Adjustment 121.........................................
Appendix A Abbreviations A-1..................................................................
Appendix B Common Hardware Application Guidelines A-3........................................
Appendix C General Torque Specifications A-4...................................................
Appendix D Common Hardware Identification A-5.................................................
125--150 kW John Deere Engine-Powered 6081 77...................
using Stanadyne D Series Injection Pump
35--99 kW John Deere-Engine Powered 4045 and 6068 80............
Appendix E Common Hardware List A-6.........................................................
Appendix F Operating Hour Service Log A-8.....................................................
TP-5737 5/01 Table of Contents
Safety Precautions and Instructions
IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
This manual has several types of safety precautions and instructions: Danger, Warning, Caution, and Notice.
DANGER
Danger indicates the presence of a hazard that will cause severe
personal injury, death,orsubstantial property damage.
WARNING
Warning indicates the presence of a hazard that can cause severe
personal injury, death, or substantial property damage.
CAUTION
Caution indicates the presence of a hazard that will or can cause minor personal injury or property damage.
NOTICE
Notice communicates installation, operation, or maintenance information that is safety related but not hazard related.
Safety decals affixed to the equipment in prominent places alert the operator or service technician to potential hazards and explain how to act safely. The decals are shown throughout this publication to improve operator recognition. Replace missing or damaged decals.
Accidental Starting
WARNING
Accidental starting. Can cause severe injury or death.
Disconnect the battery cables before working on the generator set. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery.
Disabling the generator set. Accidental starting can cause severe injury or death. Before
working on the generator set or connected equipment, disable the generator set as follows: (1) Move the generator set master switch to the OFF position. (2) Disconnect the power to the battery charger. (3) Remove the battery cables, negative (--) lead first. Reconnect the negative (--) lead last when reconnecting the battery. Follow these precautions to prevent starting of the generator set by an automatic transfer switch, remote start/stop switch, or engine start command from a remote computer.
Battery
WARNING
Sulfuric acid in batteries. Can cause severe injury or death.
Wear protective goggles and clothing. Battery acid may cause blindness and burn skin.
Battery electrolyte is a diluted sulfuric acid. Battery acid can cause severe injury or death. Battery acid
can cause blindness and burn skin. Always wear splashproof safety goggles, rubber gloves, and boots when servicing the battery. Do not open a sealed battery or mutilate the battery case. If battery acid splashes in the eyes or on the skin, immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid in the case of eye contact. Never add acid to a battery after placing the battery in service, as this may result in hazardous spattering of battery acid.
Battery acid cleanup. Battery acid can cause severe injury or death.
Battery acid is electrically conductive and corrosive. Add 500 g (1 lb.) of bicarbonate of soda (baking soda) to a containerwith4L(1gal.)ofwaterand mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid and continue to add the neutralizing solution to the spilled battery acid until all evidence of a chemical reaction (foaming) has ceased. Flush the resulting liquid with water and dry the area.
TP-5737 5/01 ISafety Precautions and Instructions
Battery gases. Explosion can cause severe injury or death. Battery gases
can cause an explosion. Do not smoke or permit flames or sparks to occur near a battery at any time, particularly when it is charging. Do not dispose of a battery in a fire. To prevent burns and sparks that could cause an explosion, avoid touching the battery terminals with tools or other metal objects. Remove all jewelry before servicing the equipment. Discharge static electricity from your body before touching batteries by first touching a grounded metal surface away from the battery. To avoid sparks, do not disturb the battery charger connections while the battery is charging. Always turn the battery charger off before disconnecting the battery connections. Ventilate the compartments containing batteries to prevent accumulation of explosive gases.
Battery short circuits. Explosion can cause severe injury or death.
Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together.
Engine Backfire/Flash Fire
Servicing the fuel system. A flash fire can cause severe injury or death.
Do not smoke or permit flames or sparks near the carburetor, fuel line, fuel filter, fuel pump, or other potential sources of spilled fuels or fuel vapors. Catch fuels in an approved container when removing the fuel line or carburetor.
Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator
set with the air cleaner/silencer removed.
Combustible materials. A sudden flash fire can cause severe injury or death. Do not smoke or permit flames
or sparks near the fuel system. Keep the compartment and the generator set clean and free of debris to minimize the risk of fire. Wipe up spilled fuels and engine oil.
Combustible materials. A fire can cause severe injury or death.
Generator set engine fuels and fuel vapors are flammable and explosive. Handle these materials carefully to minimize the risk of fire or explosion. Equip the compartment or nearby area with a fully charged fire extinguisher. Select a fire extinguisher rated ABC or BC for electrical fires or as recommended by the local fire code or an authorized agency. Train all personnel on fire extinguisher operation and fire prevention procedures.
Exhaust System
WARNING
Carbon monoxide symptoms. Carbon monoxide can cause severe nausea, fainting, or death. Carbon
monoxide is a poisonous gas present in exhaust gases. Carbon monoxide poisoning symptoms include but are not limited to the following:
D Light-headedness, dizziness D Physical fatigue, weakness in
joints and muscles
D Sleepiness, mental fatigue,
inability to concentrate or speak clearly, blurred vision
D Stomachache, vomiting, nausea
If experiencing any of these symptoms and carbon monoxide poisoning is possible, seek fresh air immediately and remain active. Do not sit, lie down, or fall asleep. Alert others to the possibility of carbon monoxide poisoning. Seek medical attention if the condition of affected persons does not improve within minutes of breathing fresh air.
Copper tubing exhaust systems. Carbon monoxide can cause severe nausea, fainting, or death. Do not
use copper tubing in diesel exhaust systems. Sulfur in diesel exhaust causes rapid deterioration of copper tubing exhaust systems, resulting in exhaust/water leakage.
Inspecting the exhaust system. Carbon monoxide can cause severe nausea, fainting, or death. For the
safety of the craft’s occupants, install a carbon monoxide detector. Consult the boat builder or dealer for approved detector location and installation. Inspect the detector before each generator set use. In addition to routine exhaust system inspection, test the carbon monoxide detector per the manufacturer’s instructions and keep the detector operational at all times.
WARNING
Fire. Can cause severe injury or death.
Do not smoke or permit flames or sparks near fuels or the fuel system.
Carbon monoxide. Can cause severe nausea, fainting, or death.
The exhaust system must be leakproof and routinely inspected.
TP-5737 5/01II Safety Precautions and Instructions
Operating the generator set. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide
is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Use the following precautions when installing and operating the generator set. Do not install the exhaustoutlet where exhaust can be drawn in through portholes, vents, or air conditioners. If the generator set exhaust discharge outlet is near the waterline, water could enter the exhaust discharge outlet and close or restrict the flow of exhaust. Never operate the generator set without a functioning carbon monoxide detector. Be especially careful if operating the generator set when moored or anchored under calm conditions because gases may accumulate. If operating the generator set dockside, moor the craft so that the exhaust discharges on the lee side (the side sheltered from the wind). Always be aware of others, making sure your exhaust is directed away from other boats and buildings. Avoid overloading the craft.
Fuel System
WARNING
Explosive fuel vapors. Can cause severe injury or death.
The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly
explosive. Use extreme care when handling and storing fuels. Store fuels inawell-ventilatedareaawayfrom spark-producing equipment and out of the reach of children. Never add fuel to the tank while the engine is running because spilled fuel may ignite on contact with hot parts or from sparks. Do not smoke or permit flames or sparks to occur near sources of spilled fuel or fuel vapors. Keep the fuel lines and connections tight and in good condition. Do not replace flexible fuel lines with rigid lines. Use flexible sections to avoid fuel line breakage caused by vibration. Do not operate the generator set in the presence of fuel leaks, fuel accumulation, or sparks. Repair fuel systems before resuming generator set operation.
Draining the fuel system. Explosive fuel vapors can cause severe injury or death. Spilled fuel can cause an
explosion. Use a container to catch fuel when draining the fuel system. Wipe up spilled fuel after draining the system.
Installing the fuel system. Explosive fuel vapors can cause severe injury or death. Fuel leakage can cause an
explosion. Do not modify the tank or the propulsion engine fuel system. Equip the craft with a tank that allows one of the two pickup arrangements described in the installation section. The tank and installation must conform to USCG Regulations.
Pipe sealant. Explosive fuel vapors can cause severe injury or death.
Fuel leakage can cause an explosion. Use pipe sealant on all threaded fittings to prevent fuel leakage. Use pipe sealant that resists gasoline, grease, lubrication oil, common bilge solvents, salt deposits, and water.
Hazardous Noise
CAUTION
Hazardous noise. Can cause hearing loss.
Never operate the generator set without a muffler or with a faulty exhaust system.
Engine noise. Hazardous noise can cause hearing loss. Generator sets
not equipped with sound enclosures can produce noise levels greater than 105 dBA. Prolonged exposure to noise levels greater than 85 dBA can cause permanent hearing loss. Wear hearing protection when near an operating generator set.
Use extreme care when handling, storing, and using fuels.
TP-5737 5/01 IIISafety Precautions and Instructions
Hazardous Voltage/ Electrical Shock
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
Grounding electrical equipment. Hazardous voltage can cause severe injury or death. Electrocution
is possible whenever electricity is present. Open the main circuit breakers of all power sources before servicing the equipment. Configure the installation to electrically ground the generator set, transfer switch, and related equipment and electrical circuits to comply with applicable codes and standards. Never contact electrical leads or appliances when standing in water or on wet ground because these conditions increase the risk of electrocution.
Disconnecting the electrical load. Hazardous voltage can cause severe injury or death. Disconnect
the generator set from the load by opening the line circuit breaker or by disconnecting the generator set output leads from the transfer switch and heavily taping the ends of the leads. High voltage transferred to the load during testing may cause personal injury and equipment damage. Do not use the safeguard circuit breaker in place of the line circuit breaker. The safeguard circuit breaker does not disconnect the generator set from the load.
Moving rotor.
Testing the voltage regulator. Hazardous voltage can cause severe injury or death. High voltage
is present at the voltage regulator heat sink. To prevent electrical shock do not touch the voltage regulator heat sink when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and PowerBoostt V voltage regulator models only)
Electrical backfeed to the utility. Hazardous backfeed voltage can cause severe injury or death.
Connect the generator set to the building/marina electrical system only through an approved device and after the building/marina main switch is opened. Backfeed connections can cause severe injury or death to utility personnel working on power lines and/or personnel near the work area. Some states and localities prohibit unauthorized connection to the utility electrical system. Install a ship-to-shore transfer switch to prevent interconnection of the generator set power and shore power.
Testing live electrical circuits. Hazardous voltage or current can cause severe injury or death. Have
trained and qualified personnel take diagnostic measurements of live circuits. Use adequately rated test equipment with electrically insulated probes and follow the instructions of the test equipment manufacturer when performing voltage tests. Observe the following precautions when performing voltage tests: (1) Remove all jewelry. (2) Stand on a dry, approved electrically insulated mat. (3) Do not touch the enclosure or components inside the enclosure. (4) Be prepared for the system to operate automatically.
(600 volts and under)
Hot Parts
WARNING
Hot coolant and steam. Can cause severe injury or death.
Before removing the pressure cap, stop the generator set and allow it to cool. Then loosen the pressure cap to relieve pressure.
WARNING
Hot engine and exhaust system. Can cause severe injury or death.
Do not work on the generator set until it cools.
Checking the coolant level. Hot coolant can cause severe injury or death. Allow the engine to cool.
Release pressure from the cooling system before removing the pressure cap. To release pressure, cover the pressure cap with a thick cloth and then slowly turn the cap counterclockwise to the first stop. Remove the cap after pressure has been completely released and the engine has cooled. Check the coolant level at the tank if the generator set has a coolant recovery tank.
Servicing the exhaust system. Hot parts can cause severe injury or death. Do not touch hot engine parts.
The engine and exhaust system components become extremely hot during operation.
Short circuits. Hazardous voltage/current can cause severe injury or death. Short circuits can
cause bodily injury and/or equipment damage. Do not contact electrical connections with tools or jewelry while making adjustments or repairs. Remove all jewelry before servicing the equipment.
TP-5737 5/01IV Safety Precautions and Instructions
Moving Parts
WARNING
Hazardous voltage. Can cause severe injury or death.
Operate the generator set only when all guards and electrical enclosures areinplace.
WARNING
Rotating parts. Can cause severe injury or death.
Operate the generator set only when all guards, screens, and covers are in place.
WARNING
Airborne particles. Can cause severe injury or blindness.
Wear protective goggles and clothing when using power tools, hand tools, or compressed air.
Moving rotor.
Tightening the hardware. Flying projectiles can cause severe injury or death. Loose hardware can cause
the hardware or pulley to release from the generator set engine and can cause personal injury. Retorque all crankshaft and rotor hardware after servicing. Do not loosen the crankshaft hardware or rotor thrubolt when making adjustments or servicing the generator set. Rotate the crankshaft manually in a clockwise direction only. Turning the crankshaft bolt or rotor thrubolt counterclockwise can loosen the hardware.
Servicing the generator set when it is operating. Exposed moving parts can cause severe injury or death.
Keep hands, feet, hair, clothing, and test leads away from the belts and pulleys when the generator set is running. Replace guards, screens, and covers before operating the generator set.
Sound shield removal. Exposed moving parts can cause severe injury or death. The generator set
must be operating in order to perform some scheduled maintenance procedures. Be especially careful if the sound shield has been removed, leaving the belts and pulleys exposed.
(Sound-shield-equipped models only)
Notice
NOTICE
This generator set has been rewired from its nameplate voltage to
246242
NOTICE
Voltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized service distributor/dealer.
NOTICE
Hardware damage. The engine and generator set may use both American Standard and metric hardware. Use the correct size tools to prevent rounding of the bolt heads and nuts.
NOTICE
When replacing hardware, do not substitute with inferior grade hardware. Screws and nuts are
available in different hardness ratings. To indicate hardness, American Standard hardware uses a series of markings, and metric hardware uses a numeric system. Check the markings on the bolt heads and nuts for identification.
NOTICE
Fuse replacement. Replace fuses with fuses of the same ampere rating and type (for example: 3AB or 314, ceramic). Do not substitute clear glass-type fuses for ceramic fuses. Refer to the wiring diagram when the ampere rating is unknown or questionable.
TP-5737 5/01 VSafety Precautions and Instructions
NOTICE
Saltwater damage. Saltwater quickly deteriorates metals. Wipe up saltwater on and around the generator set and remove salt deposits from m etal surfaces.
Notes
TP-5737 5/01VI Safety Precautions and Instructions
Introduction
This manual provides troubleshooting and repair instructions for 40COZ/33CFOZ, 40EOZ/33EFOZ, 50COZ/40CFOZ, 50EOZ/40EFOZ, 65COZ/50CFOZ, 65EOZ/55EFOZ, 80EOZ/70EFOZ, 99EOZ/80EFOZ, 125EOZ/100EFOZ, and 150EOZ/125EFOZ model generator sets, controllers, and accessories.
Refer to the engine service manual for generator set engine service information.
x:in:001:001
This manual may be used for models not listed on the front cover.
Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented
Please contact a local authorized distributor/dealer for sales, service, or other information about Kohler Co. Generator Division products.
D Look on the product or in the information included
with the product
D Consult the Yellow Pages under the heading
Generators—Electric
D Visit the Kohler Co. Generator Division web site at
www.kohlergenerators.com
D Inside the U.S.A. and Canada, call 1-800-544-2444 D Outside the U.S.A. and Canada, call the nearest
regional office
Africa, Europe, Middle East
London Regional Office Langley, Slough, England Phone: (44) 1753-580-771 Fax: (44) 1753-580-036
Australia
Australia Regional Office Queensland, Australia Phone: (617) 3893-0061 Fax: (617) 3893-0072
China
China Regional Office Shanghai, People’s Republic of China Phone: (86) 21-6482 1252 Fax: (86) 21-6482 1255
without notice and without any obligation or liability whatsoever.
Read this manual and carefully follow all procedures and safety precautions to ensure proper equipment operation and to avoid bodily injury. Read and follow the Safety Precautions and Instructions section at the beginning of this manual. Keep this manual with the equipment for future reference.
The equipment service requirements are very important to safe and efficient operation. Inspect the parts often and perform required service at the prescribed intervals. Obtain service from an authorized service distributor/dealer to keep equipment in top condition.
x:in:001:002:a
Service Assistance
India, Bangladesh, Sri Lanka
India Regional Office Bangalore, India Phone: (91) 80-2284270
(91) 80-2284279
Fax: (91) 80-2284286
Japan
Japan Regional Office Tokyo, Japan Phone: (813) 3440-4515 Fax: (813) 3440-2727
Latin America
Latin America Regional Office Lakeland, Florida, U.S.A. Phone: (941) 619-7568 Fax: (941) 701-7131
South East Asia
Singapore Regional Office Singapore, Republic of Singapore Phone: (65) 264-6422 Fax: (65) 264-6455
X:in:008:001
TP-5737 5/01 iIntroduction
Notes
TP-5737 5/01ii Service Assistance
Section 1 Specifications
1.1 Introduction
The spec sheets for each generator set provide specific generator and engine information. Refer to the respective spec sheet for data not supplied in this manual. Consult the generator set operation manual, generator installation manual, engine operation manual, and engine service manual for additional specifications.
1.2 Specifications
The generator set consists of a rotating-field generator combined with a smaller rotating-armature generator turned by a common shaft. The main rotating-field generator supplies current to the load circuits while the rotating-armature (exciter) generator supplies rectified AC (DC) to excite the main generator’s field.
Engine
Specification
Engine Prealarm and
Shutdown Switches
Anticipatory high engine temperature switch
Anticipatory low oil pressure switch
High engine temperature shutdown switch
Low oil pressure shutdown switch
High exhaust temperature switch (wet exhaust only)
Controller Gauge
Senders
Oil Pressure Sender
0kPa(0psi) 120 (+9/--8) 240 (+17/--15)
172 kPa (25 psi) 76.5 (+6/--7.5) 153 (+12/--15)
690 kPa (100 psi) 16.8 33.5
Water Temperature Sender
54° C (130° F) 100 ±15 180 ±12
82° C (180° F) 40 ±6 71 ±8
COZ/CFOZ and EOZ/EFOZ
Models
96_ C (205_ F) ±7
138 kPa ±14 kPa
(20 psi ±2)
103_ C (218_ F) ±7
103 kPa ±14 kPa
(15 psi ±2)
88--102_ C
(190--215_ F) ±5
Specification
(in ohms)
COZ/CFOZ
Models
Specification
(in ohms)
EOZ/EFOZ
Models
Generator
Component Specification Value
Controller/battery electrical system 12 or 24 volts DC
Generator field resistance (F+/ F--):
40/50COZ and 33/40CFOZ 2.0--2.9 ohms
65COZ and 50CFOZ 1.8--2.2 ohms
40EOZ and 33EFOZ 2.1--2.5 ohms
50EOZ and 40EFOZ 2.7--3.1 ohms
65/80EOZ and 55/70EFOZ 1.7--2.1 ohms
99EOZ and 80EFOZ 2.0--2.4 ohms
125EOZ and100EFOZ 1.4--1.8 ohms
150EOZ and 125EFOZ 1.6--2.0 ohms
Exciter armature resistance:
40/50COZ and 33/40CFOZ 0.13 ohms
65COZ and 50CFOZ 0.27 ohms
40EOZ and 33EFOZ 0.23 ohms
50EOZ and 40EFOZ 0.14 ohms
65/80EOZ and 55/70EFOZ 0.27 ohms
99EOZ and 80EFOZ 0.27 ohms
125EOZ and100EFOZ 0.27 ohms
150EOZ and 125EFOZ 0.27 ohms
SCR assembly terminal nut torque 1.4 Nm (12 in. lbs.)
Fan to rotor flange torque 29 Nm (260 in. lbs.)
Drive disks to rotor shaft torque 61 Nm (45 ft. lbs.)
Speed sensor air gap 0.36--0.71 mm
(0.014--0.028 in.)
Speed sensor voltage 2 (black) &
16 (white)
3--6 volts DC
2 (black) & 24 (red)
8--10 volts DC
Electronic governor magnetic pickup air gap
Magnetic pickup output voltage during cranking
Flex plate to flywheel bolt torque (3/8-16)
0.36--0.71 mm
(0.014--0.028 in.)
2.5 volts AC min.
52.9 Nm
(39 ft. lbs.)
TP-5737 5/01 1Section 1 Specifications
1.3 Accessories
1.3.1 Remote Annunciator Kit
Kohler Co. offers several accessories to finalize the installation and to add convenience to operation and service. Accessories vary with each generator set model and controller. Kohler Co. offers accessories factory-installed and/or shipped loose. Some accessories are available only with microprocessor controllers. Obtain current information by contacting your local authorized service distributor/dealer. Several accessories available at the time of print of this publication are detailed in the following subsections.
Remote Annunciator
A remote annunciator allows convenient monitoring of the generator set’s condition from a remote location. See Figure 1-1. The flush-mounted annunciator panel extends all of the fault and prealarm lights/audio of the Decision-Maker 3+ controller. The remote annunciator includes an alarm horn, an alarm silence switch, a lamp test, and the same lamp indicators (except air damper and auxiliary prealarm) as the microprocessor controller, plus the following:
Line Power. Lamp illuminates to indicate the power source is shore power.
Generator Power. Lamp illuminates to indicate the power source is the generator set.
14-Relay Dry Contact Box
42A 2 K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K13 K14K12
CONTACTRATINGS: 10A@120VAC RES.LOAD
INPUT
NO C CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO CNO
K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14
.01A@28VDC MIN.
10A@28VDC MAX.
42B
FBA--1
10 AMP
LOT NO.
P
Figure 1-1 Remote Annunciator with 14-Relay Dry Contact Kit
PCBASSY A--320639
N
P
A-344522­TP-5750-1
TP-5737 5/012 Section 1 Specifications
1.3.2 Safeguard Breaker
1.3.4 Run Relay Kit
The safeguard breaker senses output current on each generator phase and shuts off the AC voltage regulator in the event of a sustained overload or short circuit. It is not a line circuit breaker and does NOT disconnect the generator from the load. See Figure 1-2.
X-796
Figure 1-2 Safeguard Breaker
1.3.3 Line Circuit Breaker
The line circuit breaker interrupts generator output in the event of an overload or short circuit. Use the kit to manually disconnect the generator set from the load when servicing the generator set. See Figure 1-3.
The run relay kit energizes only when the generator set is running. Typically, the three sets of contacts control air intake and/or compartment ventilation fans. However, alarms and other signalling devices can also connect to the contacts. See Figure 1-4.
273705
Figure 1-4 Run Relay Kit
TP-5352-1
Figure 1-3 Line Circuit Breaker
TP-5737 5/01 3Section 1 Specifications
1.3.5 FASTCHECK Diagnostic Tester (Microprocessor Controller Only)
The FASTCHECKâdiagnostic tester simulates engine operation to identify faults in the controller and engine circuitry. Use the FASTCHECK startup problems or to test and troubleshoot the controller when the controller is removed from the generator. Perform tests without starting the generator set. Functions performed by the FASTCHECKâare listed below; refer to Figure 1-5 to identify LEDs and switches.
â
when troubleshooting
LEDs on the FASTCHECK
â
indicate the energizing of
the following circuits:
D Fuel solenoid (diesel) D Engine crank D AC voltage regulator D Battery connection (correct polarity) D Engine malfunction alarm and/or alarm shutdown
â
Switches on the FASTCHECK
D Engine cranking D Engine running D Engine overspeed D Low fuel D Low engine coolant temperature D Anticipatory low engine oil pressure D Anticipatory high engine coolant temperature D Low engine oil pressure D High engine coolant temperature
simulate the following:
B-291930
Figure 1-5 FASTCHECKâDiagnostic Tester
TP-5737 5/014 Section 1 Specifications
2.1 Fast-Responset II Concepts
The generator excitation system uses a permanent magnet exciter with a silicon controlled rectifier (SCR) assembly that controls the amount of DC current fed to the generator field. This type of system uses a voltage regulator that signals the SCR assembly through an optocoupler. The voltage regulator monitors generator output voltage and engine speed and signals the SCR assembly to turn on or off accordingly through the optocoupler. The optical coupler consists of a light emitting diode (LED) mounted on the stationary end bracket and a photo transistor mounted on the rotating shaft. The photo transistor picks up the infrared signal from the LED and signals the SCR assembly to turn on or off, depending upon the need, as dictated by the voltage regulator. See Figure 2-1.
Section 2 Operation
2
3
1
4
7
5
6
8
The voltage recovery period of this type of generator is several times faster than the conventionally wound field brushless generator because the generator set does not have to contend with the inductance of the exciter field. The generator set also has better recovery characteristics than the static-excited machine because it is not dependent upon the generator set output voltage for excitation power. Possibly the greatest advantage of this type of machine is its inherent ability to support short-circuit current and allow system coordination for tripping downstream branch circuit breakers.
The generator set systems deliver exciter current to the main field within 50 milliseconds (0.050 seconds) of a change in load demand.
2.2 Short Circuit Performance
When a short circuit occurs in the load circuit(s) being served, output voltage drops and amperage momentarily rises to 600--1000% of the generator set’s rated current until removal of the short. The SCR assembly sends full exciter power to the main field. The generator then sustains up to 300% of its rated current. Sustained high current causes correspondingly rated load circuit fuses/breakers to trip. The safeguard breaker kit shuts down the excitation system in the event of a sustained heavy overload or short circuit.
12
11
13
16
1. Main armature
2. Main field
3. Main generator
4. Stator
5. SCR assembly
6. Exciter armature
7. Rotor
8. Exciter generator
9. Exciter field magnets
10. Optical coupler
11. LED board (PCB assembly)
12. Photo transistor board (PCB assembly)
13. AC voltage regulator
14. Starting battery
15. Safeguard breaker (optional)
16. Main output leads
15
Figure 2-1 Alternator Schematic
9
10
14
TP-5353-1
TP-5737 5/01 5Section 2 Operation
2.3 Prestart Checklist
To ensure continued satisfactory operation perform the following checks or inspections before or at each startup, as designated, and at the intervals specified in the service schedule. In addition, some checks require verification after the unit starts.
Air Cleaner. Check for a clean and installed air cleaner element to prevent unfiltered air from entering the engine.
Air Inlets. Check for clean and unobstructed air inlets.
Air Shrouding. Check for securely installed and
positioned air shrouding.
Battery. Check for tight battery connections. Consult the battery manufacturer’s instructions regarding battery care and maintenance.
Fuel Level. Check the fuel level and keep the tank(s) full to ensure adequate fuel supply.
Oil Level. Maintain the oil level at or near, not over, the full mark on the dipstick.
Operating Area. Check for obstructions that could block the flow of cooling air. Keep the air intake area clean. Do not leave rags, tools, or debris on or near the generator set.
Seawater Pump Priming. Prime the seawater pump before initial startup. To prime the pump: (1) close the seacock, (2) remove the hose from the water-filter outlet, (3) fill the hose and seawater pump with clean water, (4) reconnect the hose to the water filter outlet, and (5) open the seacock. Confirm sea water pump operation on startup as indicated by water discharge from the exhaust outlet.
Coolant Level. Check the coolant level according to the cooling system maintenance information.
Drive Belts. Check the belt condition and tension of the water pump and battery charging alternator belt(s).
Exhaust System. Check for exhaust leaks and blockages. Check the silencer and piping condition and check for tight exhaust system connections.
Inspect the exhaust system components (exhaust manifold, mixing elbow, exhaust line, hose c lamps, silencer, and exhaust outlet) for cracks, leaks, and corrosion.
D Check the hoses for softness, cracks, leaks, or dents.
Replace the hoses as needed.
D Check for corroded or broken metal parts and replace
them as needed.
D Check for loose, corroded, or missing clamps.
Tighten or replace the hose clamps as needed.
D Check that the exhaust outlet is unobstructed.
D Visually inspect for exhaust leaks (blowby). Check
for carbon or soot residue on exhaust components. Carbon and soot residue indicates an exhaust leak. Seal leaks as needed.
D Ensure that the carbon monoxide detector is (1) in the
craft, (2) functional, and (3) energized whenever the generator set operates.
2.4 Marine Inspection
Kohler Co. recommends that all boat owners have their vessels—especially the exhaust system attached to the generator set—inspected at the start of each boating season by the local Coast Guard Auxiliary. If there is no Coast Guard Auxiliary in the area, contact an authorized Kohler distributor/dealer for the inspection.
m:op:001:003
2.5 Angular Operation
See Figure 2-2 for angular operation limits for units covered in this manual.
Intermittent—
Continuous
25_ 30_
Maximum value for all directions
3 minutes or less
Figure 2-2 Angular Operation
m:op:001:004
2.6 Exercising the Generator Set
Operate the generator set under load once each week for one hour with an operator present.
The operator should perform all of the prestart checks before starting the exercise procedure. Start the generator set according to the starting procedure in the controller section of this manual. While the generator set is operating, listen for a smooth-running engine and visually inspect the generator set for fluid or exhaust leaks.
x:op:001:005
TP-5737 5/016 Section 2 Operation
2.7 Decision-Makerä 3+ 16-Light Microprocessor Controller Operation
Figure 2-3 identifies the Decision-Makert 3+ 16-light controller’s indicators and controls and their functions.
12 34 5 6
18
1. Fuses (inside controller)
2. Frequency meter
3. AC voltmeter
4. Controller TB1 and TB2 terminal strips (on circuit board)
5. AC ammeter
6. Scale lamps (upper/lower)
7. Selector switch
8. Annunciator panel lamps
9. Alarm silence switch
10. Lamp test
11. Generator set master switch
12. Alarm horn
13. DC voltmeter
14. Emergency stop switch, if equipped
15. Water temperature gauge
16. Voltage adjustment
17. Oil pressure gauge
18. Hourmeter
7
8
9
1011121314151617
ADV-5849 P1
Figure 2-3 Decision-Makert 3+, 16-Light Microprocessor Controller
TP-5737 5/01 7Section 2 Operation
2.7.1 Controls and Indicators
The following table describes the controls and indicators located on the controller.
Name Description
AC ammeter The meter displays the AC output
AC voltmeter The meter displays the AC output
DC voltmeter The meter displays the voltage of
Alarm horn The horn sounds if any fault or
Alarm silence switch The switch disconnects the alarm
Auxiliary fault lamp The lamp flashes or lights when
Frequency meter The meter displays the frequency
Generator set master switch
High engine temperature lamp
Hourmeter The hourmeter records the
amperage. Use the selector switch to choose the phase current.
voltage. Use the selector switch to choose the output lead circuits.
the starting battery(ies).
anticipatory condition exists. Place the generator set master switch in the AUTO position before silencing the horn. See the Controller Resetting Procedure later in this section.
during service (place the generator set master switch in the AUTO position before silencing the alarm horn). Restore the alarm horn switches at all locations (controller, remote annunciator, and audio/visual alarm) to normal positions after correcting the fault shutdown to avoid reactivating the alarm horn. See the Controller Resetting Procedure later in this section.
the controller detects a fault. See the lamp conditions section following.
(Hz) of the generator set output voltage.
The switch functions as the controller reset and generator set operation switch.
The lamp illuminates if the generator set shuts down because of high engine temperature. Shutdown occurs 5 seconds after the engine reaches temperature shutdown range.
generator set total operating hours for reference in maintenance scheduling.
Lamp test switch The switch tests the controller
Low oil pressure lamp
Overcrank lamp The lamp illuminates and cranking
Overspeed lamp The lamp illuminates if the
Water temperature gauge
Oil pressure gauge The gauge displays the engine oil
Scale lamps (upper/lower)
Selector switch The switch selects the generator
Voltage adjustment potentiometer
indicator lamps.
The lamp illuminates if the generator set shuts down because of low oil pressure. Shutdown occurs 5 seconds after the engine reaches oil pressure shutdown range.
stops if the engine does not start after 45 seconds of continuous cranking or 75 seconds of cyclic cranking.
The cranking stops and overcrank lamp lights after 15 seconds if the starter or engine does not turn (locked rotor).
The overcrank lamp flashes if the speed sensor signal is absent longer than one second.
NOTE: The generator set controller’s automatic restart function attempts to restart the generator set if the engine speed drops below 13 Hz (390 rpm). Continued decreased engine speed causes an overcrank condition.
generator set shuts down because governed frequency on 50 and 60 Hz models exceeds 70 Hz.
The gauge displays the engine coolant temperature.
pressure.
The lamps indicate which AC voltmeter and/or ammeter scales to read.
set output circuits to measure. When switched to a position with two circuit labels, measure amperage on the lead shown in the upper label and measure voltage between the two leads shown in the lower label. The AC ammeter and voltmeter function only with the switch in the ON position.
The potentiometer fine-tunes (±5%) the generator set output voltage.
TP-5737 5/018 Section 2 Operation
Name Description
Auxiliary prealarm lamp
The lamp illuminates when customer-provided sensing devices activate the pump.
Emergency stop lamp
The lamp illuminates and the generator set shuts down when energizing the optional emergency stop switch. The lamp needs the optional emergency stop switch to function.
Generator switch not in auto lamp
The lamp illuminates when the generator set master switch is in the RUN or OFF/RESET position.
Low fuel lamp The lamp illuminates when the fuel
level in the tank approaches empty. The lamp needs a low fuel sensor in the fuel tank to function.
High water temperature lamp
The lamp illuminates when the water temperature approaches shutdown range. The lamp needs an optional prealarm sender kit to function.
Prealarm high engine temperature lamp
The lamp illuminates when the engine coolant temperature approaches shutdown range. The lamp needs an optional prealarm sender kit to function.
Prealarm low oil pressure lamp
The lamp illuminates when the engine oil pressure approaches shutdown range. The lamp needs an optional prealarm sender kit to function.
System ready lamp The lamp illuminates when the
generator set master switch is in AUTO position and the system senses no faults.
Emergency stop switch
The switch, if activated, instantly shuts down the generator set in emergency situations. Use the emergency stop switch for emergency shutdowns only. Use the generator set master switch for normal shutdowns.
2.7.2 Fuses and Terminal Strips
The following table describes the controller circuit board fuses and controller terminal strips.
Name Description
3-amp remote annunciator fuse
3-amp controller fuse The fuse protects the controller
15-amp engine and accessories fuse
Controller TB1 terminal strip
Controller TB2 terminal strip
The fuse protects the remote annunciator circuit, A/V alarm, and isolated alarm kit, if equipped.
circuit board, speed sensor, and lamp circuit board.
Thefuseprotectsthe engine/starting circuitry and accessories.
The terminal strip provides connection points for customer-supplied sensing devices and generator set accessories such as the emergency stop switch, remote start stop/switch, audio/visual alarms, etc., to the controller. Figure 2-4 shows the location of the TB1 terminal strip on the controller circuit board. Refer to the wiring diagrams for information on connecting accessories to the TB1 terminal strip.
The terminal strip provides connection points for crank mode selection (cyclic or continuous) and remote start/stop switch inputs of operation. Figure 2-4 shows the location of the TB2 terminal strip on the controller circuit board. Refer to the wiring diagrams for connection information.
12
TP-5737 5/01 9Section 2 Operation
3
R41
LED4
P2
1. TB1 terminal strip
2. TB2 terminal strip
3. Fuses
P1
Figure 2-4 TB1 and TB2 Terminal Strips on
Decision-Makert 3+ Controller Circuit Board
A-336415-A
2.7.3 Auxiliary Fault Lamp Conditions
2.7.4 Starting the Generator Set
The following descriptions define the possible auxiliary fault lamp conditions.
Flashing Lamp Conditions
No AC Output. The auxiliary lamp flashes immediately if the controller senses no AC output while the generator set runs (except during the first 10 seconds after startup). The flashing stops and the light goes out when the controller senses AC output. The controller requires no manual reset.
Low Battery Voltage. The auxiliary lamp flashes if the battery power was reconnected or was low and then restored while the generator set master switch was in the RUN or AUTO position. A possible cause is a temporary low battery condition when the battery is weak or undersized for the application. To clear the low battery voltage condition, place the generator set master switch in the OFF/RESET position.
Continuous-On Lamp Conditions
Emergency Stop Switch Energized. Upon activation of the emergency stop switch, if equipped, the auxiliary lamp lights and the generator set shuts down immediately.
Emergency Stop Switch Reset. Resetting the optional emergency stop switch while the generator set master switch is in the AUTO or RUN position causes the auxiliary lamp to light. Place the generator set master switch in the OFF/RESET position to clear the auxiliary lamp ON condition.
Note: Auxiliary Delay Shutdown. The auxiliary lamp
lights and the engine shuts down 5 seconds after the high oil temperature (P1-13) or auxiliary delay shutdown (P1-15) fault, if equipped, occurs. Auxiliary Delay Shutdown is inhibited during the first 30 seconds after crank disconnect.
The following procedures describe starting the generator set.
Local Starting (Nonautomatic). Move the generator set master switch to the RUN position to start the generator set at the controller.
Note: The alarm horn sounds whenever the generator
set master switch is not in the AUTO position.
Automatic (Auto) Starting. Move the generator set master switch to the AUTO position to allow startup by the automatic transfer switch or remote start/stop switch (connected to controller terminals TB1-3 and TB1-4).
Note: The transient start/stop function of the
Decision-Makert3+ controller prevents accidental cranking of the rotating engine. When the generator set master switch is momentarily placed in the OFF/RESET position, then quickly returned to RUN, the generator set slows to 249 rpm and then recranks before returning to rated speed.
Note: The Decision-Makert 3+ controller’s automatic
restart function attempts to restart the generator set if the engine speed drops below 390 rpm (generator output frequency of 13 Hz). Continued decreased engine speed causes an overcrank fault condition.
Crank Mode Selection
The Decision-Makert3+ controller cranks continuously for up to 45 seconds or cyclically for up to 75 seconds (crank 15 seconds, rest 15 seconds, crank 15 seconds, etc.) before overcrank shutdown. Select the crank mode (cyclic or continuous) on the controller circuit board terminal strip. For cyclic cranking, leave circuit board terminal TB2-9 open. For continuous cranking, attach a jumper between circuit board terminal TB2-9A (ground) and terminal TB2-9.
Note: Overvoltage Shutdown. If a generator set is
equipped with this kit, the auxiliary lamp lights and the engine shuts down immediately when an overvoltage condition occurs.
Note: Auxiliary Immediate Shutdown. The auxiliary
lamp lights and the engine shuts down immediately when any customer-supplied sensing devices connected to auxiliary immediate shutdown ports (P1-17 and P1-18) activate them.
x:op:005:004
2.7.5 Stopping the Generator Set
The following procedures describe stopping the generator set.
Normal Stopping
1. Cooldown. Run the generator set at no load for 5 minutes to ensure adequate engine cooldown.
2. Stopping. Move the generator set master switch to the OFF/RESET position. The engine stops.
TP-5737 5/0110 Section 2 Operation
Note: The generator set continues running during
a 5-minute cooldown cycle if a remote switch or automatic transfer switch signals the engine to stop.
Emergency Stopping
Move the generator set master switch to the OFF/RESET position or activate the remote emergency stop, if equipped, for immediate shutdown. The controller AUXILIARY lamp lights and the generator set shuts down on activation of the emergency stop switch. The remote annunciator and/or A/V alarms, if equipped, signal an emergency stop.
2.7.6 Prime Power Mode Operation
The Decision-Makert 3+ controller operates in either the normal mode or the prime power mode. In prime power mode, the controller draws less current, minimizing the battery drain. Consider using the prime power mode for installations that do not have a battery charger.
Moving the generator set master switch to the OFF/RESET position disables all controller functions. Moving the generator set master switch to the AUTO position restores controller functions.
Enabling and Disabling the Prime Power Mode.
Enable the prime power mode by connecting jumpers across the following terminals on terminal strip TB2 on the controller circuit board:
D TB2-1P and TB2-2P
D TB2-3P and TB2-4P
D TB2-3 and TB2-4
See Figure 2-4. Remove the jumpers listed above to disable the prime power mode.
Prime Power Starting. The prime power mode provides local starting only at the controller. When the generator set master switch is in the OFF/RESET position, the controller functions are inoperative. Move the generator set master switch to the AUTO position to start the generator set. Do not start the generator set with the master switch in the RUN position because the alarm horn sounds.
Note: Move the generator set master switch to the
AUTO position to return controller functions to normal.
2.7.7 Fault Shutdowns
The generator set shuts down automatically under the following fault conditions and cannot be restarted until the fault condition is corrected. The system automatically resets when the problem is corrected or the generator set cools (if high engine temperature was the fault).
Name Description
High engine temperature
High exhaust temperature
Low coolant level (water-cooled engines only)
Low oil pressure Shutdown occurs 5 seconds after
Overcrank Shutdown occurs after 45 seconds
Overspeed Shutdown occurs immediately
Overvoltage (optional)
Shutdown occurs 5 seconds after the fault. The high engine temperature shutdown does not function during the first 5 seconds after startup.
NOTE: The high temperature shutdown functions only when the coolant level is in the operating range.
Shutdown occurs 5 seconds after the fault. The high exhaust temperature shutdown does not function during the first 5 seconds after startup.
Shutdown occurs 5 seconds after fault. The low coolant level shutdown does not function during the first 5 seconds after startup.
the fault. The low oil pressure shutdown does not function during the first 5 seconds after startup.
NOTE: The low oil pressure shutdown does not protect against low oil level. Check the engine oil level.
of continuous cranking or 75 seconds of cyclic cranking (crank 15 seconds, rest 15 seconds, crank 15 seconds, etc.).
when governed frequency on 50 and 60 Hz models exceeds 70 Hz.
The generator set shuts down and the auxiliary lamp lights when voltage is 15% or more over the nominal voltage for 2 seconds or longer.
NOTE: Overvoltage can damage sensitive equipment in less than one second. Install separate overvoltage protection on on-line equipment requiring faster shutdown.
x:op:005:007
Prime Power Stopping. Move the generator set master switch to the OFF/RESET position to stop the generator set and power down the controller.
TP-5737 5/01 11Section 2 Operation
2.7.8 Controller Resetting Procedure (Following Fault Shutdown)
2.7.9 Resetting the Emergency Stop Switch
Use the following procedure to restart the generator set after a fault shutdown. Refer to Resetting the Emergency Stop Switch in this section to reset the generator set after an emergency stop.
1. Place the controller alarm horn silence switch in the SILENCE position. Place the A/V annunciator alarm switch, if equipped, in the SILENCE position to stop the alarm horn. The A/V annunciator lamp stays lit. (The A/V alarm uses one lamp to indicate a fault shutdown; the respective fault lamp on the remote annunciator lights to indicate a fault condition.)
2. Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch.
3. Correct the cause of the fault shutdown. See the Safety Precautions at the beginning of this section before proceeding.
4. Place the generator set master switch in the OFF/RESET position and then in the RUN position to start the generator set. The A/V annunciator alarm horn sounds and the lamp, if equipped, darkens.
Use the following procedure to restart the generator set after an emergency stop switch shutdown. Refer to the Controller Resetting Procedure in this section to restart the generator set following a fault shutdown. The generator set does not crank until the operator completes the resetting procedure.
Note: The controller auxiliary lamp lights when the
generator set master switch is in the RUN or AUTO position during the resetting procedure.
Procedure to Restart the Generator Set After an Emergency Stop Shutdown:
1. Determine the cause of the emergency stop and correct the problem(s).
2. Reset the controller emergency stop switch by rotating the switch clockwise until the switch springs back to the original position. See Figure 2-3.
3. Toggle the generator set master switch to OFF/RESET and then to RUN or AUTO to restart the generator set.
5. Test operate the generator set to verify that the cause of the shutdown has been corrected.
6. Reconnect the generator set to the load via the line circuit breaker or automatic transfer switch.
7. Place the generator set master switch in the AUTO position for startup by a remote transfer switch or remote start/stop switch. Place the A/V annunciator alarm switch, if equipped, in the NORMAL position.
8. Place the generator set master switch in the AUTO position before silencing the alarm horn.
TP-5737 5/0112 Section 2 Operation
2.8 Expanded Decision-Makert 1 Controller Operation
For identification of the expanded controller’s indicators and controls and their functions, refer to Figure 2-5.
13
1. Frequency meter
2. AC voltmeter
3. AC ammeter
4. Scale lamps (upper/lower)
5. Selector switch
6. Hourmeter
7. Generator set master switch
1
12
2
11
Figure 2-5 Expanded Decision-Makert 1 Controller
3
10
9
8. Voltage adjustment potentiometer
9. Fault lamp
10. 10-amp controller fuse
11. DC voltmeter
12. Water temperature gauge
13. Oil pressure gauge
4
8
7
5
6
ADV-5849E-B
x:op:002:001
2.8.1 Controls and Indicators
The following table describes the controls and indicators located on the controller.
Name Description
AC voltmeter The meter displays the AC output
AC ammeter The meter displays the AC output
DC voltmeter The meter displays the voltage of the
Fault lamp The lamp illuminates during engine
Frequency meter The meter displays the frequency (Hz)
Generator set master switch
Hourmeter The hourmeter records the generator
voltage. Use the selector switch to choose the output lead circuits.
amperage. Use the selector switch to choose the phase currents.
starting battery(ies).
shutdown if the engine shuts down because of one of the following faults: high engine temperature, low water level, low oil pressure, overcrank, or overspeed. See Section 2.8.4, Fault Shutdowns, for additional shutdown information.
of the generator set output.
The switch functions as the controller reset and generator set operation switch.
set total operating hours for reference in maintenance scheduling.
Oil pressure gauge
Scale lamps (upper/lower)
The gauge displays the engine oil pressure.
The lamps indicate which AC voltmeter and/or ammeter scales to read.
Selector switch The switch selects the generator set
output circuits to measure. When switched to a position with two circuit labels, measure amperage on the lead shown in the upper label and measure voltage between the two leads shown in the lower label. The AC ammeter and voltmeter function only with the switch in the ON position.
Voltage adjustment
The potentiometer fine-tunes (±5%) the generator set output voltage.
potentiometer
Water temperature
The gauge displays the engine coolant temperature.
gauge
10-amp controller fuse
The fuse protects the controller circuitry from short circuits and overloads.
TP-5737 5/01 13Section 2 Operation
2.8.2 Starting the Generator Set
The following procedure describes the actions required to start the generator set.
Local Starting. Move the generator set to the RUN position to immediately start the generator set.
Auto (Automatic) Starting. Move the generator set master switch to the AUTO position to allow startup by the automatic transfer switch or the remote start/stop switch (connected to controller terminals TB1-3 and TB1-4).
Note: The controller provides up to 30 seconds of
continuous cranking before overcrank shutdown occurs.
x:op:002:003
2.8.3 Stopping the Generator Set
2.8.5 Controller Resetting Procedure (Following Fault Shutdown)
Use the following procedure to restart the generator set after a fault shutdown.
1. Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch. See the Safety Precautions at the beginning of this section before proceeding.
2. Correct the cause of the fault shutdown. See the Safety Precautions at the beginning of this section before proceeding.
3. Start the generator set by moving the generator set master switch to RESET/OFF and then to RUN.
4. Verify that the cause of the shutdown has been corrected by test operating the generator set.
The following procedure describe how to stop the generator set.
Normal Stopping
1. Cooldown. Run the generator set at no load for 5 minutes to ensure adequate engine cooldown.
2. Stopping. Move the generator set master switch to the OFF/RESET position. The engine stops.
x:op:002:004
2.8.4 Fault Shutdowns
The generator set shuts down automatically under the following fault conditions and cannot be restarted until the fault condition is corrected. The system automatically resets when the problem is corrected or the generator set cools (if high engine temperature was the fault).
The fault lamp does not stay lit after the generator set shuts down on a fault condition.
5. Reconnect the generator set to the load using the line circuit breaker or automatic transfer switch.
6. Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.
Fault Description
High engine temperature
High exhaust temperature
Low coolant level Shutdown occurs 5 seconds after the
Low oil pressure Shutdown occurs 5 seconds after the
Overcrank Shutdown occurs after 30 seconds of
Overspeed Shutdown occurs immediately when
Shutdown occurs 5 seconds after the fault. The high engine temperature shutdown does not function during the first 5 seconds after startup.
Note: The high temperature shutdown functions only when the coolant level is in the operating range.
Shutdown occurs 5 seconds after the fault. The high exhaust temperature shutdown does not function during the first 5 seconds after startup.
fault. The low coolant level shutdown does not function during the first 5 seconds after startup.
fault. The low oil pressure shutdown does not function during the first 5 seconds after startup.
Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.
continuous cranking. Shutdown occurs after 30 seconds if the engine or starter does not turn (locked rotor).
the governed frequency on the 50 and 60 Hz models exceeds 70 Hz.
x:op:002:006
TP-5737 5/0114 Section 2 Operation
2.9 Standard Decision-Makert 1 Controller Operation
For identification of the standard basic controller’s indicators and controls and their functions, refer to Figure 2-6.
1
2.9.2 Starting the Generator Set
The following procedures describe the actions required to start the generator set.
Local Starting. Move the generator set master switch to the RUN position to immediately start the generator set.
Automatic (Auto) Starting. Move the generator set master switch to the AUTO position to allow startup by the automatic transfer switch or the remote start/stop switch (connected to controller terminals TB1-3 and TB1-4).
Note: The controller provides up to 30 seconds of
continuous cranking before the overcrank shutdown occurs.
x:op:004:003
345
1. Hourmeter
2. Voltage adjustment
3. 10-amp controller fuse
4. Fault lamp
5. Generator set master switch
2
A-227600
Figure 2-6 Decision-Makert 1 Controller
x:op:004:001
2.9.1 Controls and Indicators
The following table describes the controls and indicators located on the controller.
Name Description
Fault lamp Lamp illuminates during engine
Generator set master switch
Hourmeter Hourmeter records the generator
Voltage adjust potentiometer
10-amp controller fuse
shutdown if the engine shuts down because of one of the following faults: high engine temperature, low water level, low oil pressure, overcrank, or overspeed. See Section 2.9.4, Fault Shutdowns, for additional shutdown information.
Switch functions as the controller reset and generator operation switch.
set total operating hours for reference in maintenance scheduling.
Potentiometer fine-tunes (±5%) generator output voltage.
Fuse protects the controller circuitry from short circuits and overloads.
x:op:004:002
2.9.3 Stopping the Generator Set
The following procedure describe how to stop the generator set.
Normal Stopping
1. Cooldown. Run the generator set at no load for 5 minutes to ensure adequate engine cooldown.
2. Stopping. Move the generator set master switch to the OFF/RESET position. The engine stops.
x:op:004:004
TP-5737 5/01 15Section 2 Operation
2.9.4 Fault Shutdowns
The generator set shuts down automatically under the following fault conditions and cannot be restarted until the fault condition is corrected. The system automatically resets when the problem is corrected or the generator set cools (if high engine temperature was the fault).
Fault Description
High engine temperature
High exhaust temperature
Low coolant level Shutdown occurs 5 seconds after
Low oil pressure Shutdown occurs 5 seconds after
Overcrank Shutdown occurs after 30 seconds
Overspeed Shutdown occurs immediately
Shutdown occurs 5 seconds after the fault. The high engine temperature shutdown does not function during the first 5 seconds after startup.
NOTE: The high temperature shutdown functions only when the coolant level is in the operating range.
Shutdown occurs 5 seconds after the fault. The high exhaust temperature shutdown does not function during the first 5 seconds after startup.
the fault. Low coolant level shutdown does not function during the first 5 seconds after startup.
the fault. Low oil pressure shutdown does not function during the first 5 seconds after startup.
NOTE: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.
of continuous cranking. Shutdown occurs after 30 seconds if the engine or starter does not turn (locked rotor).
when the governed frequency on 50 and 60 Hz models exceeds 70 Hz.
x:op:004:005
2.9.5 Controller Resetting Procedure (Following Fault Shutdown)
Use the following procedure to restart the generator set after a fault shutdown.
1. Disconnect the generator set from the load using the line circuit breaker or automatic transfer switch. See the Safety Precautions at the beginning of this section before proceeding.
2. Correct the cause of the fault shutdown. See the Safety Precautions at the beginning of this section before proceeding.
3. Start the generator set by moving the generator set master switch to RESET/OFF and then to RUN.
4. Verify that the cause of the shutdown has been corrected by test operating the generator set.
5. Reconnect the generator set to the load using the line circuit breaker or automatic transfer switch.
6. Move the generator set master switch to the AUTO position for startup by remote transfer switch or remote start/stop switch.
x:op:004:006
TP-5737 5/0116 Section 2 Operation
Loading...
+ 118 hidden pages