Series TNS/TNF Thermometers
Installation/Operation
KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh, PA 15205
Phone (412) 788-2830 • Fax (412) 788-4890
Precautions
• Please read the entire manual prior installing this
product. These instructions include information on
the TNS/TNF series capillary and rigid stem thermometers. Refer to the part number label on the
instrument housing to verify the exact model number.
• User’s responsibility: The TNS/TNF series thermometer are designed for use in a wide variety of
applications. It is however, the user’s responsibility to
ensure the suitability of the device with respect to a
specific application. Additionally, it is the user’s
responsibility to ensure the unit is properly installed
and tested prior to operation.
• Proper Installation and Sealing: Always use a
proper thread sealant with all installations. Be sure
not to overtighten fittings. Test for leaks prior to operating the instrument.
Instructions
• Wiring and Electrical: For units with switches,
check the current and voltage requirements for
the load to be controlled. Ensure that they do not
exceed the maximum specified switch ratings.
• Temperature and Pressure: Under no circum-
stances should the maximum ratings of operating
temperature and pressure be exceeded. Doing so
can result in equipment damage and personnel
injury.
• Material Compatibility: Ensure that the media
contacted parts are made of a material which is
chemically compatible with the process media.
Ensure that the housing material is compatible
with the ambient environment. Failure to do so
can result in equipment damage caused by chemical attack.
Electrical Connections:
For units with optional adjustable switches, all electrical connections are made via a weather proof 90° angle connector plug on
the side of the indicator housing. Connections are made via numbered screw terminals inside the connector. It is recommended
that a multi-conductor jacketed cable be used. The outside diameter of the jacket should be large enough to ensure that the
weather-tight cable gland on the plug can be tightened down
snugly.
Table 1 (back of page) lists all of the switch type codes and the
functional descriptions for each switch type. The switch type
code is stamped on the dial of the thermometer and is on the wiring diagram which appears on the thermometer housing. Consult
the wiring diagram on the thermometer housing for pin assignments for each switch.
5
6
4
3
1
2
TNS/TNF Terminal Housing
Setpoint Adjusting Tool
Switch Adjustment:
For units which have optional switches, adjust the switch setpoint as follows:
• Remove the switch adjusting tool by pulling it from the center of the 90° angle electrical connector.
• Insert the tool into the adjusting stub at the center of the dial crystal. The setpoint indicators are the ones with the red tips.
Push the adjusting tool in against spring tension and rotate until the adjusting lever contacts the setpoint indicator at its
base.
• Use the tool to rotate the setpoint indicator to the desired setpoint.
• Re-install the adjusting tool into the rear of the electrical connector.
FM Rev 02/27/04
Manual-TNS/TNF

Table 1: Switching Options and Wring Terminal Numbers
Contact Type Code Functional Description
Sliding & Magnetic
Contacts
Single Contact
S10 M10 Single contact closes when temperature is above setpoint Sliding Contact Ratings
S20 M20 Single contact opens when temperature is above setpoint
S30 M30 Changeover (SPDT) contact switches over when temperature is
above setpoint
Max. Voltage: 250 VAC/VDC
Max. Power: 10 Watts
Max. Current: 0.6 Amps
Elec. Protection: NEMA 4X/ IP65
Two Contacts
S11 M11 Both contacts closed when temperature is above setpoint
S12 M12 First contact closed when temperature is above setpoint
Second contact open when temperature is above setpoint
S21 M21 First contact open when temperature is above setpoint
Second contact closed when temperature is above setpoint
S22 M22 First contact open when temperature is above setpoint
Second contact open when temperature is above setpoint
Inductive Contacts
Single Contacts
I10 Single switch activated when temperature is above setpoint Inductive Switch Rating
I20 Single switch de-activated when temperature is above setpoint
Two Contacts
I11 Both contacts activated when temperature is above setpoint
I12 First contact activated when temperature is above setpoint
Second contact de-activated when temperature is above setpoint
I21 First contact de-activated when temperature is above setpoint
Second contact activated when temperature is above setpoint
Magnetic Contact Ratings
Max. Voltage: 250 VAC/VDC
Max. Power: 30 Watts
Max. Current: 0.6 Amps
Elec. Protection: NEMA 4X/ IP65
Output: NAMUR Per DIN 19234
Elec. Protection: NEMA 4X/ IP65
I22 Both contacts de-activated when temperature is above setpoint
Mechanical Specifications
Materials of construction:
Measuring probe
2.5”, 3” and 10” dials: 304 stainless steel
4” and 6” dials: 316 stainless steel
Housing
3” and 10” dials: Painted steel or stainless
steel
4” and 6” dials: Aluminum or stainless steel
Capillary (TNF series only): 316 stainless steel
Capillary armor (option): 304 stainless steel
FM Rev 02/27/04
Maximum Pressure: 350 PSIG
Maximum Temperature: 1.3X measuring range

Operating Instructions
for
Nitrogen Filled Thermometers
Model: TNS/ TNF

TNS/TNF
page 2 TNS/TNF K01/0707
1. Contents
1. Contents ........................................................................................................ 2
2. Note .............................................................................................................. 3
3. Instrument Inspection .................................................................................... 3
4. Regulation Use .............................................................................................. 3
5. Operating Principle ........................................................................................ 4
6. Electrical Connection (Option)....................................................................... 4
6.1. Contacts ............................................................................................... 5
6.2. Switching Function Contacts ................................................................ 7
7. Installation ..................................................................................................... 8
8. Maintenance and Storage ............................................................................. 8
9. Technical Information .................................................................................... 9
10. Order Codes ............................................................................................... 10
Manufactured and sold by:
Kobold Messring GmbH
Nordring 22-24
D-65719 Hofheim
Tel.: +49(0)6192-2990
Fax: +49(0)6192-23398
E-Mail: info.de@kobold.com
Internet: www.kobold.com

TNS/TNF
TNS/TNF K01/0707 page 3
2. Note
Please read these operating instructions before unpacking and putting the unit
into operation. Follow the instructions precisely as described herein.
The devices are only to be used, maintained and serviced by persons familiar
with these operating instructions and in accordance with local regulations
applying to Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the
machines fulfil the EWG-machine guidelines.
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition.
Should damage to a device be visible, we recommend a thorough inspection of
the delivery packaging. In case of damage, please inform your parcel service /
forwarding agent immediately, since they are responsible for damages during
transit.
Scope of delivery:
The standard delivery includes:
• Nitrogen Filled Thermometer, model: TNS/TNF
• Operating Instructions
4. Regulation Use
Any use of the Nitrogen Filled Thermometer, model: TNS/TNF, which exceeds
the manufacturer’s specifications, may invalidate its warranty. Therefore any
resulting damage is not the responsibility of the manufacturer. The user assumes
all risk for such usage.

TNS/TNF
page 4 TNS/TNF K01/0707
5. Operating Principle
The measuring system of the gas pressure thermometer comprises probe,
capillary tube and Bourdon tube in a casing. These parts form a unit. The
complete measuring system is filled with pressurised nitrogen. A change in
temperature causes a change in inner pressure in the immersion shaft. The
resulting deflection of the Bourdon tube is transferred to the pointer through a
pointer element.
For the model TNF, the display and probe are connected by a capillary tube
separated by a distance up to 100 m.
A version filled with glycerine is available as an option for service at measuring
points exposed to strong vibrations. The fill dampens the measuring system when
exposed to mechanical vibrations and thus enables steady indication; it also
provides good lubrication for moving parts.
We recommend our robust aluminium casing for rough field service conditions.
These thermometers can also be used with aggressive measuring substances
when fitted with a suitable thermowell.
6. Electrical Connection (optional)
The electrical wiring diagram for the incorporated 2-wire transmitter with
4...20 mA output is given below. For all electrical parameters please see section
9. Technical Information: Transmitter.
4
5
3
2
6
1
24 VDC
R
+
-
GND
Screened twisted pair
Pin 1 = Power Supply
Pin 2 = GND (4... 20 mA)
Pin 3 = cable screen
4...20 mA