Series TED Optical Liquid Level Sensor
Precautions
User's Responsibility for Safety: KOBOLD manufactures a wide range of process sensors and technologies. While each of these technologies are designed to operate in a wide variety of applications, it is the user's responsibility to select a technology that is appropriate for the application, to install it properly , to perform tests of the inst alled system, and to maintain all components. The failure to do so could result in property damage or serious injury.
Proper Installation and Handling: Use only PTFE pipe tape as the thread sealant in all installations. Never overtighten the sensor within its fittings. Always check for leaks prior to system start-up.
Wiring and Electrical: Because this is an electrically operated device, only properly trained personnel should install and maintain this product. Be sure that the power supplied to the unit is appropriate for the electronics version supplied. Electrical wiring of the sensor should be performed in accordance with all applicable national, state and local codes.
Specifications:
Wetted Parts: PFA: PFA / PTFE
Polysulfone: Polysulfone SS: 303 SS, FKM,
Borosilicate Glass
Temperature and Pressure: The TED is designed for use in application temperatures and pressures as listed below. Operation outside these limitations will cause damage to the unit.
Material Compatibility: The TED’s process wetted parts for the various body materials are state d below . Make sure that the TED is chemically compatible with the application liquids. While the sensor’s outer housing is liquid resistant when installed properly, it is not designed to be immersed . It should be mounted in such a way that it does not normally come into contact with fluid.
Flammable, Explosive and Hazardous Applications: The TED is not an explosion-proof design. It should not be used in applications where an explosion-proof design is required.
Make a Fail-Safe System: Design a fail-safe system that accommodates the possibility of sensor or power failure. In critical applications, KOBOLD recommends the use of redundant backup systems and alarms in addition to the primary system.
Wiring Diagram:
Max. Pressure @ 70°F:PFA: 200 PSIG
Polysulfone: 200 PSIG SS: 400 PSIG
Process Fitting: PFA: 3/8” MNPT
Polysulfone: 3/8” MNPT SS: 1/2” MNPT
Temperature Range: -40°F to +230°F
Electrical Protection: NEMA 4
Power Supply: 5 - 35 VDC, 33 mA (excluding load)
Switch Type: NPN open collector, 300 mA max.
Electrical Connection: 18” wire leads, Polyethylene insulation,
1/2” male conduit (PS & SS models)
Installation Torque: PFA: 55 in.-lbs. max.
Polysulfone: 55 in.-lbs. max. SS: 120 in.-lbs. max.
Part Number Information
Material Model Number
PFA
Polysulfone
303 SS
TED-3611
TED-2511F
TED-3212A
FM Rev. 12/03/13
Manual-TED_manual_1-28-02