Kobold TDD Operating Manual

Operating Instructions
for
Electronic Temperature Switch
Model: TDD
TDD
1. Contents
2. Note .............................................................................................................. 3
3. Instrument Inspection .................................................................................... 3
4. Regulation Use .............................................................................................. 3
5. Operating Principle ........................................................................................ 4
6. Mechanical Connection ................................................................................. 4
7. Electrical Connection .................................................................................... 5
7.1. Connector pin assignment TDD-153, TDD-353 ................................... 5
7.2. Connector pin assignment TDD-553, TDD-753 ................................... 6
8. Commissioning .............................................................................................. 7
8.1. Button function ..................................................................................... 7
9. Adjustments .................................................................................................. 8
9.1. Value setting ........................................................................................ 8
10. Set- up Mode ................................................................................................ 9
10.1. Adjustments for TDD-1... and TDD-3... ................................................ 9
10.2. Adjustments for TDD-5...; TDD-7... .................................................... 10
11. Main Menu Options ..................................................................................... 12
11.1. Switching point ................................................................................... 12
11.2. Hysteresis .......................................................................................... 12
11.3. Window point (Double Point), (only for TDD-1… and TDD-3…) ........ 12
11.4. Switching behaviour ........................................................................... 13
11.5. Filter (only for TDD-1… and TDD-3…)............................................... 14
11.6. Transient response (only for TDD-5… and TDD-7…) ........................ 14
11.7. Contact model .................................................................................... 15
11.8. Change Code ..................................................................................... 15
12. Maintenance ............................................................................................... 15
13. Technical Information .................................................................................. 16
14. Order Codes ............................................................................................... 17
15. Dimensions ................................................................................................. 18
16.
Declaration of Conformance..................................................................… .. 19
page 2
Manufactured and sold by:
Kobold Messring GmbH
Nordring 22-24
D-65719 Hofheim
Tel.: +49(0)6192-2990
Fax: +49(0)6192-23398
E-Mail: info.de@kobold.com
Internet: www.kobold.com
TDD K06/0416
2. Note
Please read these operating instructions before unpacking and putting the unit into operation. Follow the instructions precisely as described herein. The devices are only to be used, maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the machines fulfil the EC-machine guidelines.
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition. Should damage to a device be visible, we recommend a thorough inspection of the delivery packaging. In case of damage, please inform your parcel service / forwarding agent immediately, since they are responsible for damages during transit.
TDD
Scope of delivery:
The standard delivery includes:
Electronic Temperature Switch model: TDD
Operating Instructions
4. Regulation Use
Any use of the Electronic Temperature Switch, model: TDD, which exceeds the manufacturer’s specification may invalidate its warranty. Therefore any resulting damage is not the responsibility of the manufacturer. The user assumes all risk for such usage.
TDD K06/0416
page 3
TDD
5. Operating Principle
The KOBOLD Model TDD temperature sensor is used for economical measuring and monitoring of temperature. It can be used for any application in which temperatures must be monitored with great accuracy.
The sensor element is a semiconductor that outputs a digital signal to the electronic processor in 0,5 °C steps. The measured values are shown on a 3-digit LED display. The switch setpoint can be adjusted as required within the measuring range.
6. Mechanical Connection
Before installation:
Please check, if the switching temperature and switching function of TDD device is in agreement with your system requirements (specifications).
Ensure that the maximum operating pressure or temperature for the device is not exceeded.
Installation:
This device is installed in a matching sleeve. Use sealing tape (i.e. Teflon tape) or a flat gasket to seal the threaded connections.
The mounting position should be selected so that the sensor tip is always immersed in the liquid being monitored, thus ensuring optimal heat exchange between the liquid and the temperature sensor.
Note that deposits that build up on the sensor tip or dirty liquids can have an insulating effect and cause invalid measurements.
Whenever possible, after the mechanical installation is complete, the joint at the threaded connector and the supply piping should be checked to ensure that it is tight and does not leak.
page 4
TDD K06/0416
7. Electrical Connection
Attention! Make sure that the supply voltage of your system correspond with the voltage of the measuring unit specified on the nameplate.
Make sure that the electrical supply lines are de-energised.
Make the connection using the M 12x1 connector socket, as shown in the
accompanying diagram.
Appropriate connectors with different cable lengths are optionally available.
Attention! Incorrect wiring will lead to damage of the unit’s electronics.
TDD
7.1. Connector pin assignment TDD-153, TDD-353
Option: plug with cable ZUB-KAB-12K002
Plug
TDD K06/0416
page 5
TDD
g
7.2. Connector pin assignment TDD-553, TDD-753
TDD-...553 TDD-...753
PNP-Output 1 NPN-Output 1
+24 VDC +24 VDC
0 V / GND 0 V / GND
PNP-Output 2 NPN-Output 2
0 V / GND 0 V / GND
Plug
PNP connection scheme
Plu
NPN Connection Scheme
Plug
page 6
TDD K06/0416
8. Commissioning
Attention! Please take note that during operation at high temperatures, the surface and the elements within the unit may become very hot!
Connect the temperature switch according to the figure shown on the previous page, and supply the device with the specified voltage.
8.1. Button function
In the normal mode (measurement mode)
TDD
: Press 3 sec set-up mode
: Switch point/display window point
: Switch point/display hysteresis
In adjustment mode
: Next level
: Change values
TDD-1
TDD-5 and TDD-7
Anytime:
3 sec
or 20 sec
Don’t press any key
Normal Mode
TDD K06/0416
page 7
TDD
9. Adjustments
The following values can be changed at the temperature transmitter:
Switching point (SPo, set-point) Hysteresis (HYS) Window point (double) Filter (Filt) Contact-Type (Con) Contact (N/O) or (N/C) N/O Contact Code (CCo, change code)
9.1. Value setting
From main menu option (e.g. Switching point, "SPo"), press "" key in order to go to Parameter Adjustment. The following structure shows the sequence of steps required to change a single parameter.
Display range Factory pre-set
-199...999 50.0
-199...0 000 Switching point ...999 --- (inactive) 1/2/4/8/16/32/64 1
000...999 000
[From main menu option]
1. Set position
2. Set position
3. Set position
Adjust decimal point
page 8
Save selected value or key-in new value
Save
[to next main menu option]
TDD K06/0416
10. Set- up Mode
10.1. Adjustments for TDD-1... and TDD-3...
TDD
Code input
Switch point
Hysteresis
Duo-point
3 sec
Code=
Setting parameter
Setting parameter
Setting parameter
Setting parameter
: Next level
: Change value
Anytime:
3 sec
or 20 sec
Don’t press any key
Normal Mode
On-delay
Off-delay
Contact type
Code change
N/O contact N/C contact
Setting parameter
Setting parameter
Save
Setting parameter
TDD K06/0416
page 9
TDD
10.2. Adjustments for TDD-5...; TDD-7...
3 sec
Code input
Setting parameter
Code=
Switch pt. 1
Switch pt. 2
Hysteresis 1
Hysteresis 2
On-delay 1
On-delay 2
Setting parameter
Setting parameter
Setting parameter
page 10
Setting parameter
TDD K06/0416
Off-delay 1
Off-delay 2
TDD
Setting parameter
Contact type 1
Contact type 2
Change code
N.O. contact N.C. contact
Save
N.O. contact N.C. contact
Save
Setting parameter
TDD K06/0416
page 11
TDD
11. Main Menu Options
11.1. Switching point
In menu option "SP0", “SP1” and “SP2” the switching point is entered. A setting value between -199 and 999 can be selected. This value can also include a decimal point. The decimal point can be set at two points (e.g. 10.0 or 100). If the measuring value is the set switch point, the temperature switch is activated and is signalised by a lightning LED. If the hysteresis is zero and the window point is inactive, the temperature switch will be reacted if the temperature is below the switch point.
11.2. Hysteresis
After the setting of switching point, the hysteresis can be entered as a negative value in the "HYS", “HY1” and “HY2” menu. The standard hysteresis value is zero. In operation condition this can lead to ambiguous switching behaviour if the reading fluctuates around the switching point or window point. Aid can be given here by increasing the hysteresis. The hysteresis relates to the switching point and the window point (switching point minus hysteresis; window point plus hysteresis). Example: Switching point 100 °C; Hysteresis: -2.5 °C
The temperature switch switches when 100 °C is exceeded and switches back when the reading drops below 97.5 °C.
11.3. Window point (Double Point), (only for TDD-1… and TDD-3…)
As well as the switching point, it is also to define a "duo" (duo-point), the window point. This must be higher than the switching point. Using the window point and the switching point it is possible to monitor the measurement value in a certain range. The switching point limits the measurement range to smaller values and the window point to larger values.
If the window point (duo-point) is less than or equal to the switching point, an error report (Er4) will be indicated on the display and its value is deleted and its function is invalid (in the case that the window point and switching point out of adjustment).
The value is set in the same way as the switching point. The window point is needed for process, monitoring of a certain temperature range.
page 12
TDD K06/0416
TDD
Example: Switching point: 50 °C; window point: 70 °C; hysteresis: -2 °C
The temperature contact switches when 50 °C is exceeded. If the temperature remain between 48 °C (50-2) and 72 °C (70+2), the contact will also remain in active switching condition (LED on). If it exceeds 72 °C or drops below 48 °C the temperature switch switches back.
11.4. Switching behaviour
The following diagram clarifies the switching behaviour of the temperature switch. The contact closes (contact type: no) when it drops below the switching point or the window point. It only opens again if the window point plus hysteresis is exceeded or if it drops below the switching point minus hysteresis. An LED indicates the switching condition of the switching point.
Display bar (°C)
LED ON
Switching pt.
Hysteresis
Display bar (°C)
Hysteresis
Window point
time/ t
LED ON
LED ON
Switching pt.
Hysteresis
TDD K06/0416
time / t
page 13
TDD
11.5. Filter (only for TDD-1… and TDD-3…)
The filter function "Filt" makes the measured value for switching purposes the running average from the measured value samples. The following values can be adjusted (see section 9. Adjustments):
1 / 2 / 4 / 8 / 16 / 32 / 64 samples
The filter value determines the dynamic behaviour of the display value. The larger the Filt value, the more dampened the display response. With the adjustment of the filter value " 1 " the filter is switched off, i.e. the display value is equal to the unfiltered measured value.
The integrated overshoot detector reacts to a step change of approx. 6.25% of the measurement range (full scale). During a detected measured value overshoot of >6.25%, the instantaneous measured value is transferred directly to the display without filtering.
11.6. Transient response (only for TDD-5… and TDD-7…)
Using the menu items “dS1”, “dS2”, “dr1” and “dr2” it is possible to set the delay set and the delay reset.
The delay set causes delayed switching of the output if the switching threshold is exceeded.
The delay reset causes a delayed resetting of the output if it drops below the switching threshold – hysteresis.
The setting range for both parameters is 0.0 ... 99.5 seconds. The step rate is 0.5 seconds.
With these two functions it is also possible to suppress temporary disturbances.
page 14
TDD K06/0416
TDD
11.7. Contact model
In menu option "Con", “Co1” and “Co2” the transistor switching output function is set. The switching function changes from
N/O contact to N/C contact, and back.
N/O contact means: Contact closes on exceeding the switching point. N/C contact means: Contact opens on exceeding the switching point.
11.8. Change Code
The code change "CCo" protects the device against unauthorised changes in adjusted device parameters. If the code is different from 000, the user must input the adjusted code in order to perform any programming changes.
12. Maintenance
This device is maintenance-free when properly installed. However, deposits from dirty liquids can lead to invalid measured values.
TDD K06/0416
page 15
TDD
13. Technical Information
Housing cover: St. steel 1.4305 Housing: St. steel 1.4404 (compact version)
Connection compact version: G 1/2 or G 3/4 male thread
Connection separate version:
Sensor: 100 mm, 6 mm; st. st. 1.4404 Cable: 2,5 m PTFE with M 12x1 plug Housing: M 25x1,5 with counter nut
Principle of measurement: Semiconductor Display: TDD-1,-3,-5,-7: 3-digit LED, digit-height: 7mm; Resolution: TDD-1,-3,-5,-7: 0.5 °C to 100 °C
Max. temperature: of measured medium: -20...+120 °C (compact version)
Max. ambient temp.: -20...+50 °C Max. pressure: 80 bar Power supply: 24VDC ± 20% Current intake: TDD-1,-3,-5,-7: approx. 50 mA
Electrical connection: Plug M12x1 or
Switching output: Semiconductor
Contact function: N/O / N/C, window, adjustable Switch. point adjustment: programmable Switching display: programmable Switching state display: 1 (2) LED Hysteresis: programmable
ON/ OFF- switching delay: 0.5....99.5 (separately adjustable)
Measuring cycle: 0.5 s Accuracy (sensor): ± 0.5 °C (between –10...+85 °C)
Protection cat: IP 65
St. steel 1.4305 (separate version)
St. steel 1.4404 Option: 1/2 NPT or 3/4 NPT
1 °C up to 100 °C
-50...+125 °C (separate version)
(without switching output); (without switching output)
PVC-cable (cable t
PNP or NPN (factory set), max. 300 mA, short-circuit proof
(only TDD-5, TDD-7)
± 2 °C (between +85...125 °C) ± 2 °C (between -50...-10 °C)
: 90 °C)
max
page 16
TDD K06/0416
14. Order Codes
(Example: TDD-153 R4H2 00) Please specify cable length with order!
Model
TDD
Electrical
Connection
Plug
M12x1
*Separate version only with 100 mm sensor; maximum length at NPT-threads is 184 mm instead 200 mm
Switching
output
1x PNP
TDD-153 TDD-353 TDD-553 TDD-753
Switching
output
1x NPN
Switching
output
2x NPN
Switching
output
2x NPN
R4H2 =G 1/2; -20...+120°C R5H2 =G 3/4; -20...+120°C N4H2 =1/2 NPT; -
20...+120°C N5H2 =3/4 NPT; -
20...+120°C D6H3 =separate version; smooth sensor; -50...+125°C
Version
Accessories: Electrical connection
Description Model
M12x1 box with terminal
M12x1 box with 2 m cable
M12x1 box with quickon-plug
ZUB-KAB-12D500
ZUB-KAB-12K002
ZUB-KAB-12Q000
Sensor length*
00 =short 10 =100 mm 20 =200 mm
TDD K06/0416
page 17
TDD
15. Dimensions
Compact version short
Compact version long Separate version
page 18
TDD K06/0416
TDD
16.
Declaration of Conformance
We, KOBOLD Messring GmbH, Hofheim-Ts, Germany, declare under our sole responsibility that the product:
Electronic Temperature Switch Model: TDD-1…, TDD-3…, TDD-5… and TDD-7…
to which this declaration relates is in conformity with the standards noted below:
EN 61326-1:2013
Electrical equipment for EMC requirements
EN 61010-1:2011
Safety requirements for electrical equipment for measurement, control and laboratory use -
Part 1: General requirements
measurement, control and laboratory use -
- Part 1: General requirements
Also the following EEC guidelines are fulfilled:
2014/30/EU Electromagnetic Compability
2011/65/EU RoHS (category 9) industrial monitoring and control instruments,
compliant, no CE-marking for the transitional period until 2017
Hofheim, 27. Apr. 2016
H. Peters M. Wenzel
General Manager Proxy Holder
TDD K06/0416
page 19
Loading...