Kobold SV Operating Manual

Page 1
KOBOLD SV FLOWMETER/SWITCH
User Instructions
KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205
Phone (412) 788-2830 • Fax (412)-788-4890 • www.koboldusa.com
R2_4-13
Page 2
Page 3
Table Of Contents
1.0 General . . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 1
2.0 Specifications. . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 1
3.0 Installation . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 2
4.0 Electrical Installation . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 3
5.0 Operation . . . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 4
5.1 Reading Flow. . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 4
5.2 Adjusting the Setpoint for Increasing Flow. . . . . . . . . . . . . . . . . . . . 4
5.3 Adjusting the Setpoint for Decreasing Flow. . . . . . . . . . . . . . . . . . . 4
6.0 Arrival of Damaged Equipment . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 5
7.0 Maintenance . . . . . . . . . . .. . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 5
SV
8.0 Need help with your SV Flow Switch?. . .. . . . . . . . . . . . . . . . . . . . . 5
List Of Diagrams
Diagram 4.1 Electrical Connections. . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 3
List of Tables
Table 2.1 Material Composition. . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . 2
FM Rev. 4/16/13
Page 4
Page 5
SV
KOBOLD SV FLOWMETER/SWITCH
User Instructions
CAUTION: For safety reasons, please read the cautionary information located at
the end of the manual, before attempting installation.
1.0 General
The KOBOLD SV flowmeter/switch is intended for applications where only measurement, or measurement and flow monitoring of liquids and gases with vertical, upward flow is required. The instrument has a direct reading scale and may be factory fitted with single or dual magnetic reed contacts that actuate when the desired flow is achieved.
The principle of operation of the SV is that of the well-known float in a conical tube. The KOBOLD SV, however, uses our patented cylindrical control tube with V-groove to replace the conical tube. This method has advantages in that the float is stabilized over its entire measuring range and offers a large flow range in a small instrument. The float has a built-in permanent magnet that actuates a reed switch (when equipped) mounted on the exterior housing of the device. The optional switch is therefore hermetically separated from the medium. The optional switches are user adjustable so that setpoints may be adjusted to any flow value within the range of the instrument.
2.0 Specifications
Measurement Accuracy: +/- 5% of Full Scale Maximum Medium Temperature: 240 Degrees F
-with PP or PVDF Float 160 Degrees F
Maximum Operating Pressure: 145 PSIG
Switch Specifications: Maximum Voltage: 240 VAC
Maximum Current: SPST (N/O): 1.5 A
SPDT: 0.8 A
Maximum Power Dissipation: SPST (N/O): 50 VA/50 W
SPDT: 30 VA/30 W
Environmental Protection: IP 65 (IEC 259)
(Equal to NEMA 4)
cCSAus Approval
FM Rev. 4/16/13
Page 6
SV 2
Table 2.1 Material Composition
Brass Version SS Version
Housing: Anodized Aluminum Anodized Aluminum Flow Tube: Borosilicate Glass Borosilicate Glass
Slotted Nozzle: Ni-Plated Brass 304 SS Float: Ni-Plated Brass or PP 304 SS or PVDF Fittings: Ni-Plated Brass 304 SS
Seals:
3.0 Installation
NBR
FKM
CAUTICAUTICAUTIOOON:N:N: ForForFor sssaaafffeeetttyyy rrreeeaaasssonsonsons,,, plplpleeeaaassseee rrreeeaaad d d ttthehehe cccaaautututiiionaonaonarrryyy iiinfnfnfororormmmaaatttiiion on on lllocococaaattteeed d d aaattt
ttthehehe eeend nd nd ofofof ttthehehe mmmaaanuanuanualll,,, bebebeffforororeee aaatttttteeemmmptptptiiing ng ng iiinsnsnstttaaallllllaaatttiiion.on.on.
ToToTo iiinnnstststaaallllll,,, ppprrrooocececeeeeddd aaas s s fffooollllllooows:ws:ws:
111... ThThTheee SSSVVV ffflllooowwwmmmeeettteeerrr///swiswiswitttchchch mmmuuuststst bbbeee iiinnnstststaaalllllleeeddd iiinnn aaa veveverrrtttiiicacacalll pppooosisisitttiiiooonnn wwwiiittthhh ttthhheee ffflllooowww iiinnnllleeettt aaattt ttthhheee bbbooottttttooommm...
222... ThThTheee mmmeeedddiiiuuummm mmmuuuststst nnnooottt cococonnntttaaaiiinnn aaannny y y sososollliiiddds s s ooorrr cococonnntttaaammmiiinnnaaannnttts s s ttthhhaaattt cococouuulllddd ppprrreeecicicipppiiitttaaattteee ooouuuttt ooofff sososollluuutttiiiooonnn aaannnddd dddeeepppooosisisittt ooonnn ttthhheee iiinnnstststrrruuummmeeennnttt'''s s s iiinnnnnneeerrr wawawalllllls.s.s. ThThThiiis s s wowowouuulllddd ppprrreeevevevennnttt ppprrrooopppeeerrr ooopppeeerrraaatttiiiooonnn ooofff ttthhheee dddeeevivivicecece... UnUnUnclclcleeeaaannn mmmeeedddiiiaaa shshshooouuulllddd bbbeee fffiiilllttteeerrreeeddd uuupppstststrrreeeaaammm ooofff ttthhheee SSSVVV... KKKOOOBBBOOOLLLD D D oooffffffeeerrrs s s aaa mmmaaagggnnneeetttiiic/c/c/scrscrscreeeeeennneeeddd fffiiilllttteeerrr sususuiiitttaaabbbllleee fffooorrr sususuchchch pppuuurrrpppooosesesesss (type MFR).
3. Do not install meter on large masses of ferritic materials, or in areas where strong electric fields are present, as this will hamper proper operation of the reed contact.
FM Rev. 4/16/13
Page 7
4.0 Electrical Installation
3 SV
Maximum values of current and voltage must not be exceeded on the reed relay.
driving inductive or capacitive loads, we recommend the use of a suitable isolation relay, KOBOLD provides a line of relays for such instances. If an isolation relay is not used, a clamping diode is highly recommended for DC inductive loads to minimize contact arcing, which will destroy the reed switch.
Diagram 4.1 Electrical Connections
If
N/O Contact (SPST) Changeover Contact (SPDT)
FM Rev. 4/16/13
Page 8
SV 4
5.0 Operation
We recommend that if possible, a flow control valve be installed downstream of the instrument and be closed as pressure is introduced to the system. Thereafter, the control valve can be opened gradually to achieve the needed flow. This procedure prevents oscillation of the float as the medium is introduced. More importantly, it prevents possible damage due to pressure surges (as described in the cautionary section) to the SV.
5.1 Reading Flow
Read the flow rate off the top edge of the float.
5.2 Adjusting the Setpoint for Increasing Flow
Adjust the setpoint for increasing flow as follows:
1. Loosen the hold-down screws on the reed contact housing.
2. Slide the contact upwards (toward outlet) along its rail until it reaches its stops. The reed contact will be deactuated at this point.
3. Open the medium feed line and set flow to desired volume.
4. Slide the reed contact downwards (toward inlet) until the contact actuates.
5. Tighten the hold-down screws.
5.3 Adjusting the Setpoint for Decreasing Flow
Adjust the setpoint for decreasing flow as follows:
1. Loosen the hold-down screws on the reed contact housing.
2. Slide the contact downwards (toward inlet) along the rail until it reaches its stops. The reed contact will be actuated at this point.
3. Open the feed line and introduce flow until the reed contact deactuates, then lower the flow value to the desired minimum.
4. Slide the contact upwards (toward outlet) until the reed contact actuates again.
5. Tighten the hold-down screws.
FM Rev. 4/16/13
Page 9
5 SV
6.0 Arrival of Damaged Equipment
Your instrument was inspected prior to shipment and found to be defect-free. If damage is visible on the unit, we advise that you carefully inspect the packing in which it was delivered. If damage is visible, notify your local carrier at once, since the carrier is liable for a replacement under these circumstances. If your claim is refused, please contact KOBOLD Instruments for further instructions.
7.0 Maintenance
The KOBOLD SV contains no active mechanisms, such as springs or diaphragms, to wear out. Operation is achieved using gravity and magnetism. This means that reliable operation and a long life may be expected from the SV. We do strongly recommend that, since dirt is the primary enemy of this instrument, only clean or filtered media be passed through it.
8.0 Need help with your SV Flow Switch?
Call one of our friendly engineers at 412-788-2830.
FM Rev. 4/16/13
Page 10
Page 11
7 SV
Caution
PLEASE READ THE FOLLOWING GENERAL FLOW METER/ MONITOR
WARNINGS BEFORE ATTEMPTING INSTALLATION OF YOUR NEW
DEVICE. FAILURE TO HEED THE INFORMATION HEREIN MAY
RESULT IN EQUIPMENT FAILURE AND POSSIBLE SUBSEQUENT
PERSONAL INJURY.
FM Rev. 4/16/13
Page 12
SV 8
Media and Chemical Compatibility:
User's Responsibility for Safety:
process sensors and technologies. While each of these technologies are designed to operate in a wide variety of applications, it is the user's responsibility to select a technology that is appropriate for the application, to install it properly, to perform tests of the installed system, and to maintain all components. The failure to do so could result in property damage or serious injury.
Inspect instrument for damage upon arrival:
otherwise damaged instruments must not be put into use, since the device is weakened to an unknown extent. Refer to Section 6.0, Arrival of Damaged Equipment, for additional information.
device have been determined using water and air. If using other media, especially corrosive media, it is critically important that the user determine chemical compatibility with our instruments. KOBOLD Instruments Inc. cannot accept responsibility for failure and consequences resulting from use of media other than water, air, and nitrogen.
Material Compatibility:
selected is chemically compatible with the application liquids. While the meter is liquid and spray resistant when installed properly, it is not designed to be immersed.
Make sure that the model which you have
KOBOLD manufactures a wide range of
Cracked, fractured, bent or
The maximum tolerances of the
Proper Installation in Flow System:
position within your flow system. This avoids excessive stresses which may damage the instrument. In particular:
a.) Ensure that the plumbing leading to and from the instrument is fully supported and that the instrument does not perform the physical function of a joint.
b.) When calculating stress on the device caused by plumbing, the weight of the medium in the pipes must be considered as well.
c.) Misaligned runs of rigid piping can cause large stresses when connected to the instrument. Do not connect in such a fashion.
d.) When connecting fittings, hold the instrument fittings rigid with a correctly sized wrench. Do not install by twisting the instrument into the pipe fittings.
e.) Do NOT install by holding the device housing to provide counter-torque to the pipe fitting.
f.) Use an appropriate amount of PTFE tape on male threads of fitting. This reduces the twisting stresses produced by tightening the fittings into each other.
g.) Do not use pliers or wrenches on the housing, as this may damage it.
Install the device in a fully supported
h.) Do not overtighten, as this may fracture the fittings.
FM Rev. 4/16/13
Page 13
9 SV
While Operating the Flow System:
of situations to avoid:
a.) The sudden cessation of fluid flow causes what is typically referred to as "water hammer". Most people are familiar with this phenomenon from their home experience - it is the cause behind the loud clank of water pipes which occurs when faucets are turned off too suddenly. The cause behind this "water hammer" is quite easy to visualize. Water is fairly massive. The amount of water in long runs of pipe is quite substantial. When the faucets are turned off suddenly, especially from a full on condition, the water has considerable momentum and does not want to stop flowing. The situation is similar to stopping a car by running into a wall, rather than by applying brakes. Both are sudden rather than gradual. The damage to the wall can be substantial (not to mention the car).
b.) The "water hammer" causes surges in fluid pressure which could cause the measurement instrument's pressure limit to be exceeded, resulting in failure and possible personal injury.
c.) Fluid surges, as well as the water hammer, can be particularly damaging to empty flowmeters since there is no back pressure in the device. The damage is caused, once again, by momentary excess pressure. To avoid these surges, fluid lines should remain full (if possible) and water flow should be introduced to the device slowly.
During operation, there are a number
d.) If the instrument is isolated with inlet and outlet valves, the flowmeter must be completely drained when said valves are both closed. Failure to do so could result in damage to the device caused by thermal expansion of fluid.
e.) Freezing of water in the instrument must be avoided since the resultant expansion will damage the flowmeter and make it unsafe for use.
Wiring and Electrical:
Electrical Connections, provide the voltage and current limitations and the wiring for the various sensor types. The sensor electrical ratings should never be exceeded. Electrical wiring of the sensor should be performed in accordance with all applicable national, state and local codes.
Temperature and Pressure:
temperature and pressure limits for each model. Operation outside these limitations will cause damage to the unit and can potentially cause personal injury. Fluid should never be allowed to freeze inside the sensor.
Make a Fail-safe System:
the possibility of switch or power failure. In critical applications, KOBOLD recommends the use of redundant backup systems and alarms in addition to the primary system.
Section 2.0, Specifications and Section 4.0,
Section 2.0, Specifications, provides the
Design a fail-safe system that accommodates
FM Rev. 4/16/13