SEN-9601
2. Note
Please read these operating instructions before unpacking and putting the unit
into operation. Follow the instructions precisely as described herein.
The devices are only to be used, maintained and serviced by persons familiar
with these operating instructions and in accordance with local regulations
applying to Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the
machines fulfil the EC-machine guidelines.
Devices with max. allowable pressure ≤200 bar:
as per PED 2014/68/EU
In acc. with Article 4 Paragraph (3), "Sound Engineering Practice", of the PED
2014/68/EU no CE mark.
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition.
Should damage to a device be visible, we recommend a thorough inspection of
the delivery packaging. In case of damage, please inform your parcel service /
forwarding agent immediately, since they are responsible for damages during
transit.
Any use of the Pressure Sensor with Ceramic Sensor Element, model: SEN9601, which exceeds the manufacturer’s specification, may invalidate its
warranty. Therefore, any resulting damage is not the responsibility of the
manufacturer. The user assumes all risk for such usage.
Caution!
The manufacturer disclaims all responsibility in case of damages
caused by the improper use of the product and by the non-respect of
the instructions reported in this manual.
- Follow carefully the specific safety rules in case of measuring oxygen
pressure, acetylene, inflammable or toxic gas or liquids.
- Disconnect the instruments only after depressurization of the system.
- The process fluids residuals in the disassembled instruments could
affect people, the environment and the system. It is highly
recommended to take proper precautions.
Before installation be sure that the right instrument has been selected
following the working conditions and in particular the range, the
working temperature and the compatibility between the material used
and the process fluid.
- This manual does not concern the instruments conforming to
standard 94/9/CE (ATEX).
- The product warranty is no longer valid in case of non-authorized
modifications and of wrong use of the product.
- The user is totally responsible for the instrument installation and
maintenance.
- Handle and carefully stock the instrument used for toxic or
inflammable liquids measurement
The pressure transmitter turns the input pressure into an output electrical signal.
The electrical signal changes in proportion to the input pressure level.
page 4 SEN-9601 K04/1117
SEN-9601
5. General
The KOBOLD SEN-96 Standard model is an electronic transmitter with ceramic
sensor for air, industrial, technical gases and water and oil, designed to be
installed in gas distribution plants, on bottles, on refrigerators, on compressors,
on vacuum pumps and hydraulics and water high pressure plants.
6. Installation
Before installing electrical instrument safely and securely into a plant or a system
the user should verify the instrument suitability to the plant characteristics and the
correct installation. After installation the user should verify that the instrument is
not exposed to any source of heat exceeding the established ambient limits.
Secure the instrument thread through a special key/wrench on the process
connection hexagon (20…30 Nm). The correct torque depends on the type of
process connection and the type of seal used (form and material).
As for those process connections with a cylindrical thread (Gas-Metric), a head
gasket compatible with the measurement gas or fluid should be used.
If the connection thread is conical the instrument is tightened through a simple
screwing on the plug. In order to improve the thread tightness it is recommended
to place a PTFE layer on the male thread.
SEN-9601 K04/1117 page 5
SEN-9601
7. Electrical Connection
Output signal: 4…20 mA
No. of wires: 2
Load max.: RL ≤ (UB-8)/0,02 Ω
Supply UB: 8…30 VDC
The transmitter metal case should always be connected to ground (GND) through
the process connection thread in order to protect the sensor from disturbances
due to electromagnetic fields or electrostatic charges.
The sensor can also be connected via the ground connection to the system
ground.
page 6 SEN-9601 K04/1117
SEN-9601
8. Maintenance
The SEN-9601 transmitter is “maintenance free”.
If a fault occurs, contact Kobold.
9. Product Label
SEN-9601 K04/1117 page 7
SEN-9601
10. T echnical Information
Ranges: 0 ...1/0 ... 600 bar, relative,
-1... 0/-1... +24 bar, relative
Accuracy: ≤ ± 0.5% of full scale*
Non-linearity (BFSL): ≤ ± 0.25 % of full scale, according to EN 61298-2
Non-repeatability: ≤ 0.1 % of full scale, according to EN 61298-2
Output signal
deviation of zero: ≤ ± 0.5 % of span, typical;
≤ ± 0.8 % of span, max.
Thermal drift: 0…80 °C, 1 % of span;
2.5 % of span, max.
Long term drift: ≤ 0.1 % of span, according to EN 61298-2
Process fluid temperature,
ambient and stocking
temperature: -25 ...+85 °C
Output signals: 4... 20 mA, 0...5 VDC, 0...10 VDC,
1... 5 VDC, 0.5... 4.5 ratiometric VDC
Response time: <4 ms
Emission and immunity: According to EN 61326, (group 1 - class B; industrial
applications)
Process connection: In AISI 316L (1.4404), hole ø 2.5 mm
Sensor: Ceramic in Al2O3
Case: AISI 316L (1.4404)
Gasket (Sensor): FKM
Electric connection: EN 175301-803 Form A
Protection degree: IP 65 according to IEC 529 / EN 60529**
Weight: 0.12 kg
* Including non-linearity, hysteresis, non-repeatability and output signal
deviation of zero at the reference conditions described in standard
EN 61298-1
** with properly assembled electric connection .
page 8 SEN-9601 K04/1117
SEN-9601
Measuring ranges
[bar, relative]
-1...0 5
-1...0.6 5
-1...1.5 5
-1...3 8
-1...5 12
-1...9 20
-1...15 32
-1...24 50
0...1/0...1.6/0...2.5 5
0...4 8
0...6 12
0...10 20
0...16 32
0...25 50
0...40 80
0...60 120
0...100 200
0...160 320
0...250 500
0...400 600
0...600 800
Overpressure limit
[bar, relative]
SEN-9601 K04/1117 page 9
SEN-9601
11. Order Codes
Order Details (Example: SEN-9601 0 B075 A 0)
Model Output Measuring range Mechanical
Connection
SEN-9601...
* Minimum or quantity = 20 pieces per item (identical model code)
All output signals are provided of protection against short circuit and polarity inversion.
Insulation tension 500 VDC
...0...= 4-20 mA,
2-wire
(standard)
...1...*= 0...5 V
(8...30 V
…2…*= 0…10 VDC
(14…30 VDC)
…3…*= 0.5…4.5 VDC
ratiometric
(5 VDC ± 10 %)
…4…*= 1…5 VDC
(8…30 VDC)
DC
4...20 mA
0
< 25 < 10 < 10 < 10 < 10
DC
)
C 315 = -1...0 bar
C 505* = -1...0.6 bar
C 515 = -1...1.5 bar
C 525 = -1...3 bar
C 535 = -1...5 bar
C 545 = -1...9 bar
C 555 = -1...15 bar
C 565* = -1...24 bar
B 025 = 0...1 bar
B 035 = 0...1.6 bar
B 045 = 0...2.5 bar
B 055 = 0...4 bar
B 065 = 0...6 bar
B 075 = 0...10 bar
B 085 = 0...16 bar
B 095 = 0...25 bar
B 105 = 0...40 bar
B 115 = 0...60 bar
B 125 = 0...100 bar
B 135 = 0...160 bar
B 145 = 0...250 bar
B 155 = 0...400 bar
A 165*= 0...600 bar
0...5 VDC
1
0...10 VDC
2
A = G½, male
(standard)
B* = G¼,male
E* = G¼ DIN
3852-E,
male
F* = ½“NPT,
male
G* = ¼“NPT,
male
0.5...4.5 VDC
ratiometric – 3
Options
0 = without
Y* = special
option
(specify in
clear text)
1...5 VDC
4
page 10 SEN-9601 K04/1117
SEN-9601
12. Dimensions
SEN-9601 K04/1117 page 11
SEN-9601
13. EU Declaration of Conformance
We, KOBOLD Messring GmbH, Hofheim-Ts, Germany, declare under our sole
responsibility that the product:
Pressure Sensor with Ceramic Sensor Elements Model: SEN-9601
to which this declaration relates is in conformity with the standards noted below:
EN 61326-1:2013 Electrical equipment for measurement, control and
laboratory use - EMC requirements - Part 1: General requirements