BVO, RVO K01/0316 Page 7
8. Commissioning of the Instruments
The use of this meter in machines acc. to directive 89/392/EWG is prohibited until
the complete machine complies to this directive.
Adjustment of the limit values
Adjust the switch in this position by means of tightening the fixing screws.
Replace the plug cap and the instrument is now ready for operation.
If the limit switch is adjusted correctly, a bi-stable switch characteristic is
achieved, i.e.: the contact remains closed when the float rises above the set
limit value (PIN 1+2, or alternatively PIN 2+3).
Hysteresis
Hysteresis is characterised by the difference between the switching on and
switching off points of the contact. By matching the magnet and reed contact
sensitivity (AW Number) a hysteresis of approx. 6-10 mm way of float movement
is achieved. At the same time it may be assured that the contacts have a bistable switching characteristic.
Loosen the two fixing srews on the contact base.
Slide the switch housing to the bottom stop.
After loosening the holding screw, remove the plug
cap from the contact base.
Connect a suitable continuity meter to PIN 1+2
(changeover switch PIN 2+3).
When the instrument is installed, open the inlet line
and introduce the medium slowly until the top edge of
the float indicates the required minimum flow volume.
The reed contact is now closed (electrical continuity).
Warning: Sudden opening or closing of the flow line
may result in pressure peeks several times higher
than the system pressure. This may cause the
destruction of the measuring glass.
When the instrument is not yet installed, the float may
be lifted with a suitable tool.
Push the switch housing to the top until the reed
contact opens
(no electrical continuity).