Kobold NRF Instruction Manual

NRF-100_KM Rev. : 1.0 16/04/2002
Kobold two-wire NRF level transmitters are designed to measure either liquid or certain dry bulk media. The 12-36 VDC 4mA base current is the supply to the unit. The NRF monitors level change by converting movement of media UP or DOWN the probe into pulse wave form which is proportional to changes in level. The amplifier converts this pulse wave into 4 to 20 mA output signal. The conversion of level movement to an electrical signal is due to changes in electrical capacitance. The probe and a ground reference electrode, usually the metal tank wall, have a certain capaci­tance in air. As the medium displaces the air, a change occurs because of the difference in the dielectric constants of the medium and air.
Fig 1.
aran_v02 or higher
01/12/2002
It is a common practice to use the metal tank wall as the reference electrode. In such cases, it is required that the probe housing makes a good electrical connection to the tank wall. If there is any doubt about this connection due to the use of PTFE thread tape, gaskets, paint, rust, or any other reason, a separate grounding wire should be installed between the probe and the tank housing. In case the probe housing is non-metalic, or if the connection fitting is non-metalic, a grounding wire must be connected from the tank to the G terminal on the transmitter.
CAUTION: This unit contains CMOS electronics which may be damaged by static electricity. Electronics may be accessed by removing the top cover of the enclosure (head). Do not remove the transmitter face plate (and touch the electronics). There are no servicable parts.
The NRF comes complete with the transmitter mounted in an enclosure, fitting and probe (Fig. 1). Micro-processor based electronics are protected and potted within a metal housing. Calibration is made via four push buttons (Fig. 3) as explained later. Variety of options including Stainless or PVC housings, rigid or flexible probes (bare or jacketed), NPT, sanitary or flange connections are available.
Unpack the instrument carefully. Inspect all components for damage. Report any damage to Kobold within 24 hours. Check the contents of the packing slip and report any discrepencies to Kobold.
The Kobold NRF level sensor should be located for easy access for service, calibration and monitoring. Sensors should not be exposed to ambient temperatures below
- 4 0°C (- 4 0° F) or above +70°C (+ 1 6 0° F). Special precau tion should be made to prevent exposure to corrosive atmosphere, excessive vibration, shock or physical damage. It is preferable that the NRF is not installed in proximity to high voltage wires or other sources of high electrical noise.
Fig 2.
With plastic, concrete, wood, or any other non-conductive walled vessels a reference electrode must be inserted into a tank. Most commonly, this electrode will be in the form of a concentric, ground tube (i.e. stilling well, Fig. 2) or a metal rod installed in parallel with the probe. In all cases, a good electircal connection must be made between the ground reference electrode and the G terminal of the transmitter (or probe housing).
CAUTION: When installing units with PTFE (or plastic) coated rods or cables, be careful not to damage the insulation. NPT threads have very sharp corners and PTFE (or plastic) can be easily cut. In acidic and/or conductive liquids damaged units may malfunction and the metal rods can corrode
Page 1
NRF-100_KM Rev. : 1.0 16/04/2002
All wiring between the power supply and the transmitter should be done with 18 AWG to 22 AWG shielded twisted pair. The connection is made at the terminal strip within the transmitter enclosure.
CAUTION: Units are designed to operate on the 12 to 36 VDC power only. Application of 110 VAC will destroy the instrument.
1. Make sure the power source is turned off.
2. Pull power supply wires through conduit connection.
3. Connect the positive supply wire to the (+) terminal, and the negative supply to the (-) terminal. Note: Leave shield unattached at transmitter. Connect the shield to ground at the power source.
4. Replace the transmitter enclosure (head) cover until time to calibrate.
5. Connect positive supply wire to the positive terminal of the transmitter. See Fig. 3.
6. Connect the loop current meter in series with the negative supply wire as follows:
a. Negative transmitter wire to positive meter
terminal. See Fig. 3.
b. Negative meter terminal to negative power
source termianl. See Fig.3.
7. Turn ON the power. The meter may read anywhere on the scale at either end. This is normal until calibra tion has been completed. Proceed to the calibration Instructions.
aran_v02 or higher
01/12/2002
In order to calibrate the transmitter, you must use the loop current meter. It should read currents in the range of 1.00 to 25.00 mA, with a resolution of .01 mA. Using a meter of less resolution will somewhat reduce the calibration accuracy. To calibrate the instrument :
1. Remove enclosure (head) cover.
2. Connect the loop current meter as per instructions in WIRING section(Fig. 3).
3. The loop current should now be in the range of 1.5 mA to 38 mA, which is normal at this point.
Three calibration procedures are described. Follow the one which fits your application. Note the following defini­tions used in the calibration procedures, referring to Fig 4.
L = the level of material which corresponds to 4.00 mA of
loop current, i.e., the 0%
L1 = a material level higher than L H1 = a material level higher than L1, but less than H. H = the level of material in the vessel which corres-
ponds to 20.00 mA of loop current, i.e., the 100% level.
Note: To avoid the possibility of a “dead zone”, L must be at least two (2) inches above the end of the probe for (4) conductive media and four inches above for non­conductive media.
Page 2
CALIBRATION L- H = when material in tank can be set to L (0%) and H (100%).
CALIBRATION L - H1 = when material in tank can be set to L (0%) and H1 (less than 100 %).
CALIBRATION L1 - H1 = when material in tank can be set to L1 (greater than 0 %) and H1 (less than 100%).
NOTE: Calibration procedure L-H gives the most accurate results and is the recommended procedure in all cases.
Fig. 3
Loading...
+ 3 hidden pages