Kobold MPV Operating Manual

Pulse Input Rate/Totalizer
Operating Instructions
KOBOLD Instruments, Inc.
1801 Parkway View Drive Pittsburgh, PA 15205 P +1.412.788.2830
www.koboldusa.com
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Disclaimer
The information contained in this document is subject to change without notice. KOBOLD Instruments makes no representations or warranties with respect to the contents hereof; and specifically disclaims any implied warranties of merchantability or fitness for a particular purpose.
!
CAUTION: Read complete
instructions prior to installation
and operation of the meter.
WARNING:
This product is not recommended for life support applications or applications where malfunctioning could result in personal injury or property loss. Anyone using this product for such applications does so at his/her own risk. KOBOLD Instruments Inc. shall not be held liable for damages resulting from such improper use.
WARNING: Risk of
electric shock or
personal injury.
Limited Warranty
KOBOLD Instruments Inc. warrants this product against defects in material or workmanship for the specified period under “Specifications” from the date of shipment from the factory. KOBOLD Instruments’ liability under this limited warranty shall not exceed the purchase value, repair, or replacement of the defective unit.
Registered Trademarks
Modbus® is a registered trademark of Schneider Automation Inc. All other trademarks mentioned in this document are the property of their respective owners.
© 2016 KOBOLD Instruments Inc. All rights reserved.
www.koboldusa.com
2
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Table of Contents
INTRODUCTION ------------------------------------------------------------ 6 ORDERING INFORMATION --------------------------------------------- 7 SPECIFICATIONS ---------------------------------------------------------- 8
General ------------------------------------------------------------------------------- 8 Rate Input --------------------------------------------------------------------------- 9 Rate/Totalizer -------------------------------------------------------------------- 10 Relays ------------------------------------------------------------------------------ 11 Isolated 4-20 mA Transmitter Output ------------------------------------ 12 Modbus® RTU Serial Communications ---------------------------------- 13 MPV-Option-S Digital Input & Output Expansion Module --------- 13
COMPLIANCE INFORMATION ---------------------------------------- 14
Safety ------------------------------------------------------------------------------- 14 Electromagnetic Compatibility --------------------------------------------- 14
SAFETY INFORMATION ------------------------------------------------ 15 INSTALLATION ------------------------------------------------------------ 16
Unpacking ------------------------------------------------------------------------- 16 Panel Mounting Instructions ------------------------------------------------ 16
Mounting Dimensions ------------------------------------------------------- 17
Configuration for 12 or 24 VDC Power Option ------------------------ 18 Transmitter Supply Voltage Selection (P+, P-) ----------------------- 19 Connections ---------------------------------------------------------------------- 19
Connectors Labeling --------------------------------------------------------- 20 Power Connections ---------------------------------------------------------- 20 Signal Connections ---------------------------------------------------------- 21 Modbus RTU Serial Communications ----------------------------------- 23 Relay Connections ----------------------------------------------------------- 23 Switching Inductive Loads -------------------------------------------------- 24 F4 Digital Input Connections ----------------------------------------------- 25 4-20 mA Output Connections ---------------------------------------------- 25 Analog Output Transmitter Power Supply ------------------------------ 25 External Relay & Digital I/O Connections ------------------------------ 26 Interlock Relay Feature ----------------------------------------------------- 27
SETUP AND PROGRAMMING ---------------------------------------- 28
Front Panel Buttons and Status LED Indicators --------------------- 29 Display Functions and Messages ----------------------------------------- 30 Main Menu ------------------------------------------------------------------------ 34 Setting Numeric Values ------------------------------------------------------ 35 Setting Up the Rate/Totalizer Meter (setup) --------------------------- 36
3
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Setting the Input Signal (Input) ------------------------------------------ 37 Setting the Totalizer Features (total) ---------------------------------- 37 Setting the Input Units or Custom Tags (units) ---------------------- 38 Setting the Decimal Point (dEc pt) -------------------------------------- 39 Programming the Rate/Totalizer (prog) -------------------------------- 39
K-Factor Calibration (Factor) ----------------------------------------- 40 Multi-Point Calibration & Scaling -------------------------------------- 40 MeterView® Pro Software ----------------------------------------------- 40 Scaling the Meter (SCALE) ---------------------------------------------- 41 Gate Function (Gate) ---------------------------------------------------- 42 Contact De-Bounce Filter (FiLter) ---------------------------------- 43 Time Base, Total Conversion Factor & Total Reset -------------- 44
Calibrating the Meter with External Source (Cal) ----------------- 45 Setting the Display Parameter & Intensity (dsplay) ----------------- 46 Display Setup Menu --------------------------------------------------------- 47
Setting the Relay Operation (relay) ------------------------------------- 48
Relay Assignment (Assign) ----------------------------------------------- 49 Setting the Relay Action ---------------------------------------------------- 50 Programming Set and Reset Points ------------------------------------- 51 Setting Fail-Safe Operation ------------------------------------------------ 51 Programming Time Delay -------------------------------------------------- 51
Relay and Alarm Operation Diagrams ----------------------------------- 52
High Alarm Operation (Set > Reset) ------------------------------------- 52 Low Alarm Operation (Set < Reset) -------------------------------------- 53 High Alarm with Fail-Safe Operation (Set > Reset) ------------------ 54 Low Alarm with Fail-Safe Operation (Set < Reset) ------------------- 55 Alternation Control Operation --------------------------------------------- 56 Rate Relay Sampling Operation ------------------------------------------ 57 Total Relay Sampling Operation ------------------------------------------ 57 Time Delay Operation ------------------------------------------------------- 58
Relay Operation Details ------------------------------------------------------ 59
Overview ------------------------------------------------------------------------ 59 Relays Auto Initialization ---------------------------------------------------- 59 Fail-Safe Operation ---------------------------------------------------------- 59 Front Panel LEDs ------------------------------------------------------------- 60 Latching and Non-Latching Relay Operation -------------------------- 60 Non-Latching Relay (Auto) ------------------------------------------------- 61 Non-Latching Relay (A-nman) --------------------------------------------- 61 Latching Relay (LatcH) ----------------------------------------------------- 61 Latching Relay (Lt-Clr) ---------------------------------------------------- 62 Acknowledging Relays ------------------------------------------------------ 62 Setting Up the Interlock Relay (Force On) Feature ------------------ 63
Scaling the 4-20 mA Analog Output (Aout) ---------------------------- 64
4
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Reset Menu (reset) ------------------------------------------------------------ 65 Control Menu (Contrl) -------------------------------------------------------- 65 Setting Up the Password (pass) ------------------------------------------- 65
Protecting or Locking the Meter ------------------------------------------- 66 Total Reset Password & Non-Resettable Total ----------------------- 66 Making Changes to a Password Protected Meter -------------------- 67 Disabling Password Protection -------------------------------------------- 67
Advanced Features Menu ---------------------------------------------------- 68
Advanced Features Menu & Display Messages ---------------------- 68 Rounding Feature (round) ------------------------------------------------- 71 Modbus RTU Serial Communications (serial) ---------------------- 71 Select Menu (SElEct) ------------------------------------------------------- 72 Signal Input Conditioning (Functn) -------------------------------------- 72 Multi-Point Linearization (Linear) ---------------------------------------- 73 Low-Flow Cutoff (CutofF) -------------------------------------------------- 73 Analog Output Programming (AoutPr) ---------------------------------- 74 Programmable Function Keys User Menu (user) -------------------- 75
METER OPERATION ----------------------------------------------------- 76
Front Panel Buttons Operation -------------------------------------------- 76 Function Keys Operation ---------------------------------------------------- 76 F4 Operation --------------------------------------------------------------------- 77 Maximum/Minimum Readings ---------------------------------------------- 77
TROUBLESHOOTING ---------------------------------------------------- 78
Diagnostics Menu (diag) ----------------------------------------------------- 78
Determining Software Version -------------------------------------------- 78
Reset Meter to Factory Defaults ------------------------------------------- 79
Factory Defaults & User Settings ----------------------------------------- 80
Troubleshooting Tips --------------------------------------------------------- 83
5
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Table of Figures
Figure 1: 1/8 DIN Panel Cutout and Mounting ................................... 16
Figure 2: Meter Dimensions - Side View ............................................ 17
Figure 3: Meter Dimensions - Top View ............................................. 17
Figure 4: Jumper Configuration for 12/24 VDC Power ..................... 18
Figure 5: Transmitter Supply Voltage Selection ............................... 19
Figure 6: Connector Labeling for Fully Loaded MPV Pulse Input ... 20
Figure 7: Power Connections ............................................................. 20
Figure 8: Flowmeter Powered by Internal Power Supply ................. 21
Figure 9: Flowmeter Powered by External Supply ........................... 21
Figure 10: Self-Powered Magnetic Pickup Coil Flowmeter .............. 21
Figure 11: Relay Connections ............................................................ 23
Figure 12: AC and DC Loads Protection ........................................... 24
Figure 13: Low Voltage DC Loads Protection ................................... 24
Figure 14. F4 Digital Input Connections ............................................ 25
Figure 15: 4-20 mA Output Connections ........................................... 25
Figure 16: Expansion Modules & DIN Rail Mounting Kit .................. 26
Figure 17: External Relays Module Connections ............................. 26
Figure 18: Digital I/O Module Connections ....................................... 27
Figure 19: Interlock Connections ....................................................... 27
Figure 20: Acknowledge Relays w/Function Key or Digital Input ... 62
INTRODUCTION
The KOBOLD Model MPV pulse input rate/totalizer is a multipurpose, easy-to-use rate meter and totalizer ideal for flow rate, total, and control applications. It accepts pulse (40 mVp-p to 8 Vp-p), square wave (0-5 V, 0-12 V, or 0-24 V), open collector, NPN, PNP, TTL or switch contact signals. Three of the front panel buttons can be custom-programmed for specific operation.
The basic model includes an isolated 24 VDC transmitter power supply that can be used to power the input transmitter or other devices. An additional isolated 24 VDC power supply is included with the 4-20 mA output option.
A fully loaded MPV pulse input rate/totalizer has the following: four SPDT relays, 4-20 mA output, and two 24 VDC power supplies. The MPV’s capabilities may be enhanced by adding the following external expansion modules: four SPST relays (creating an eight-relay rate/totalizer), two digital I/O modules with four inputs and four outputs each, and RS-232, RS-485, and USB communication adapters.
The eight relays can be used for alarm indication or process control applications. The 4-20 mA isolated output, Modbus RTU serial communications, and digital I/O options make the KOBOLD Model MPV an excellent addition to any system.
A digital input is standard.
6
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
ORDERING INFORMATION
Standard Models
85-265 VAC Model
MPV-1510 MPV-1310 No options MPV-1512 MPV-1312 2 relays MPV-1513 MPV-1313 4-20 mA output MPV-1514 MPV-1314 4 relays MPV-1515 MPV-1315 2 relays & 4-20 mA output MPV-1517 MPV-1317 4 relays & 4-20 mA output
Options
Model Description
MPV-Option-B RS-485 serial adapter MPV-Option-E Custom Set-up MPV-Option-F USB serial adapter
MPV-Option-R 4 SPST (Form A) relays MPV-Option-S 4 digital inputs & 4 digital outputs (2 may be connected) MPV-Option-X NEMA 4X Enclosure
12/24 VDC Model
Options Installed
7
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
SPECIFICATIONS
Except where noted all specifications apply to operation at +25°C.
General
DISPLAY Upper display: 0.6" (15 mm) high, red LEDs
DISPLAY INTENSITY
DISPLAY UPDATE RATE
OVERRANGE
DISPLAY ASSIGNMENT
PROGRAMMING METHODS
RECALIBRATION All ranges are calibrated at the factory to read frequency in
MAX/MIN DISPLAY
PASSWORD
NON-VOLATILE MEMORY
POWER OPTIONS
FUSE Required external fuse: UL Recognized, 5 A max, slow
ISOLATED TRANSMITTER POWER SUPPLY
ISOLATION 4 kV input/output-to-power line
Lower display: 0.46" (12 mm) high, red LEDs 6 digits: each (-99999 to 999999), with lead zero blanking.
Eight user selectable intensity levels
Rate: 10 per second; up to 1 per 100 seconds (and is a function of Low Gate setting)
Total: 10 per second (fixed)
Display flashes
The Upper and Lower displays may be assigned to rate, total, grand total, alternate rate & total, max/min, units (lower display only), set points, Modbus input, & more.
Four front panel buttons, digital inputs, PC and MeterView Pro software, Modbus registers, or cloning using Copy function.
Hz. No recalibration required.
Max/min readings reached by the process are stored until reset by the user or until power to the meter is cycled.
Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals.
Pass 1: Allows use of function keys and digital inputs Pass 2: Allows use of function keys, digital inputs and editing set/reset points Pass 3: Restricts all programming, function keys, and digital inputs. Total: Prevents resetting the total manually Gtotal: Prevents resetting the grand total manually
All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or jumper selectable 12/24 VDC ± 10%, 15 W max
blow; up to 6 meters may share one 5 A fuse
Terminals P+ & P-: 24 VDC ± 10%. 12/24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal jumper J4). 85-265 VAC models rated @ 200 mA max, 12/24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
500 V input-to-output or output-to-P+ supply
999999
8
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
OVERVOLTAGE CATEGORY
ENVIRONMENTAL Operating temperature range: -40 to 65°C
CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG
ENCLOSURE 1/8 DIN, high impact plastic, UL 94V-0, color: black
MOUNTING 1/8 DIN panel cutout required:
TIGHTENING TORQUE
OVERALL DIMENSIONS
WEIGHT 9.5 oz (269 g)
WARRANTY 3 years parts & labor
Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
Storage temperature range: -40 to 85°C Relative humidity: 0 to 90% non-condensing
wire, RJ45 for external relays, digital I/O, and serial communication adapters.
3.622" x 1.772" (92 mm x 45 mm) Two panel mounting bracket assemblies are provided.
Screw terminal connectors: 5 lb-in (0.56 Nm)
4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
Rate Input
INPUTS Field selectable: Pulse or square wave 0-5 V, 0-12 V, or
LOW VOLTAGE MAG PICKUP (Isolated) MINIMUM INPUT FREQUENCY MAXIMUM INPUT FREQUENCY INPUT IMPEDANCE
ACCURACY ±0.03% of calibrated span ±1 count TEMPERATURE DRIFT MULTI-POINT LINEARIZATION LOW-FLOW CUTOFF DECIMAL POINT Up to five decimal places or none:
0-24 V @ 30 kHz; TTL; open collector 4.7 kΩ pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contact 4.7 kΩ pull-up to 5 V @ 40 Hz; Modbus PV (Slave) Sensitivity: 40 mVp-p to 8Vp-p
0.001 Hz Minimum frequency is dependent on high gate setting. 30,000 Hz (10,000 for low voltage mag pickup)
Pulse input: Greater than 300 kΩ @ 1 kHz. Open collector/switch input: 4.7 kΩ pull-up to 5 V.
Rate display is not affected by changes in temperature.
2 to 32 points
0-999999 (0 disables cutoff function)
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
9
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
CALIBRATION May be calibrated using K-factor, internal calibration, or by
K-FACTOR Field programmable K-factor converts input pulses to rate in
CALIBRATION RANGE
FILTER Programmable contact de-bounce filter: 40 to 999 Hz
TIME BASE Second, minute, hour, or day GATE Low gate: 0.1-99.9 seconds
F4 DIGITAL INPUT CONTACTS F4 DIGITAL INPUT LOGIC LEVELS
applying an external calibration signal.
engineering units. May be programmed from 0.00001 to 999,999 pulses/unit. Input 1 signal may be set anywhere in the range of the meter; input 2 signal may be set anywhere above or below input 1 setting. Minimum input span between any two inputs is 10 Hz. An error message will appear if the input 1 and input 2 signals are too close together.
maximum input frequency allowed with low speed filter.
High gate: 2.0-999.9 seconds
3.3 VDC on contact. Connect normally open contacts across F4 to COM. Logic High: 3 to 5 VDC Logic Low: 0 to 1.25 VDC
Rate/Totalizer
DISPLAY ASSIGNMENT
RATE DISPLAY INDICATION TOTAL DISPLAY & TOTAL OVERFLOW
ALTERNATING DISPLAY TOTAL DECIMAL POINT
TOTALIZER Calculates total based on rate and field programmable
TOTALIZER ROLLOVER
The Upper and Lower displays may be assigned to rate, total, grand total, alternate rate/total, alternate rate/grand total, set points, alternate rate/units, alternate total/units, alternate grand total/units, display Hi, display Lo, display Hi/Lo, display Modbus, display units (lower display) and display Off (lower display).
-99999 to 999999, lead zero blanking. “R” LED illuminates while displaying rate or frequency. 0 to 999,999; automatic lead zero blanking. “T” LED is illuminated while displaying total or grand total. Up to 999,999,999 with total-overflow feature. “ displayed to the left of total overflow and LED is illuminated. Either display may be programmed to alternate between rate and total or rate and grand total every 10 seconds. Up to five decimal places or none:
oF” is
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
Total decimal point is independent of rate decimal point.
multiplier to display total in engineering units. Time base must be selected according to the time units in which the rate is displayed. Totalizer rolls over when display exceeds 999,999,999. Relay status reflects display.
10
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
TOTAL OVERFLOW OVERRIDE TOTALIZER PRESETS
PROGRAMM­ABLE DELAY ON RELEASE
TOTAL RESET Via front panel button, external contact closure on digital
TOTAL RESET PASSWORD NON­RESETTABLE TOTAL
Program total reset for automatic with 0.1 second delay and set point 1 for 999,999
Up to eight, user selectable under setup menu. Any set point can be assigned to total and may be programmed anywhere in the range of the meter for total alarm indication.
0.1 and 999.9 seconds; applied to the first relay assigned to total or grand total. If the meter is programmed to reset total to zero automatically when the preset is reached, then a delay will occur before the total is reset.
inputs, automatically via user selectable preset value and time delay, or through serial communications. Total and grand total passwords may be entered to prevent resetting the total or grand total from the front panel. The grand total can be programmed as a non-resettable total by entering the password “050873”.
Once the Grand Total has been programmed as “non-resettable” the feature cannot be
!
Caution!
disabled.
Relays
RATING 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A)
NOISE SUPPRESSION
RELAY ASSIGNMENT
DEADBAND 0-100% of span, user programmable
HIGH OR LOW ALARM
RELAY OPERATION
external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP ( 50 W) @ 125/250 VAC for inductive loads
Noise suppression is recommended for each relay contact switching inductive loads; see page 24 for details.
Relays may be assigned to rate, total, or grand total.
User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turn off).
Automatic (non-latching) Latching (requires manual acknowledge) Sampling (based on time) Alternation control (2 to 8 relays) Off (disable unused relays and enable Interlock feature) Manual on/off control mode
11
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
RELAY RESET
TIME DELAY 0 to 999.9 seconds, on & off relay time delays
FAIL-SAFE OPERATION
AUTO INITIALIZATION
User selectable via front panel buttons, digital inputs, or PC
1. Automatic reset only (non-latching), when the input passes the reset point or total is reset to zero.
2. Automatic + manual reset at any time (non-latching)
3. Manual reset only, at any time (latching)
4. Manual reset only after alarm condition has cleared (Latching with clear)
Note: Front panel button or digital input may be assigned to
acknowledge relays programmed for manual reset.
Programmable and independent for each relay.
Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition.
In case of power failure, relay will go to alarm state.
When power is applied to the meter, relays will reflect the state of the input to the meter.
Isolated 4-20 mA Transmitter Output
OUTPUT SOURCE
SCALING RANGE 1.000 to 23.000 mA for any display range.
CALIBRATION Factory calibrated: 0.0 to 1000.0 = 4-20 mA output
ANALOG OUT PROGRAMMING
ACCURACY ± 0.1% FS ± 0.004 mA
TEMPERATURE DRIFT
ISOLATED TRANSMITTER POWER SUPPLY
EXTERNAL LOOP POWER SUPPLY
OUTPUT LOOP RESISTANCE
Rate/process, total, grand total, max, min, set points 1-8, Modbus input or manual control mode
23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
0.4 µA/°C max from 0 to 65°C ambient,
0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Terminals I+ & R: 24 VDC ± 10%. May be used to power the 4-20 mA output or other devices. Refer to Figure 6 on page 20 and Figure 15 on page 25.
All models rated @ 40 mA max.
35 VDC maximum
Power supply
24 VDC
35 VDC (external)
Minimum
10 Ω
100 Ω
Maximum
700 Ω
1200 Ω
12
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Modbus® RTU Serial Communications
SLAVE ID 1 – 247 (Meter address)
BAUD RATE 300 - 19,200 bps
TRANSMIT TIME DELAY
DATA 8 bit (1 start bit, 1 or 2 stop bits)
PARITY Even, Odd, or None with 1 or 2 stop bits
BYTE-TO-BYTE TIMEOUT
TURN AROUND DELAY
Note: Refer to the Modbus® Register Tables located at www.koboldusa.com for details.
Programmable between 0 and 199 ms
0.01 – 2.54 second
Less than 2 ms (fixed)
MPV-Option-S Digital Input & Output Expansion Module
CHANNELS 4 digital inputs & 4 digital outputs per module
SYSTEM Up to 2 modules for a total of 8 inputs & 8 outputs
DIGITAL INPUT LOGIC HIGH
DIGITAL INPUT LOGIC LOW
DIGITAL OUTPUT LOGIC HIGH
DIGITAL OUTPUT LOGIC LOW
SOURCE CURRENT
SINK CURRENT
+5 V TERMINAL
3 to 5 VDC
0 to 1.25 VDC
3.1 to 3.3 VDC
0 to 0.4 VDC
10 mA maximum output current
1.5 mA minimum input current
To be used as pull-up for digital inputs only. Connect normally open contacts across +5 V & DI 1-4.
13
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
COMPLIANCE INFORMATION
Safety
UL & c-UL LISTED USA & Canada
UL FILE NUMBER E482438
FRONT PANEL UL Type 4X, NEMA 4X, IP65; panel gasket provided
LOW VOLTAGE DIRECTIVE
Electromagnetic Compatibility
EMISSIONS
Radiated Emissions
AC Mains Conducted Emissions
IMMUNITY
RFI - Amplitude Modulated
Electrical Fast Transients
Electrostatic Discharge
RFI - Conducted AC Surge Surge Power-Frequency
Magnetic Field Voltage Dips
Voltage Interruptions
UL 508 Industrial Control Equipment
EN 61010-1:2010 Safety requirements for measurement, control, and laboratory use
EN 55022:2010 Class A ITE emissions requirements
Class A
Class A
EN 61326-1:2013 Measurement, control, and laboratory equipment
EN 61000-6-2:2005 EMC heavy industrial generic immunity standard
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
±2kV AC mains, ±1kV other
±4kV contact, ±8kV air
10V, 0.15-80 MHz, 1kHz 80% AM
±2kV Common, ±1kV Differential
1KV (CM)
30 A/m 70%V for 0.5 period
40%V for 5 & 50 periods 70%V for 25 periods
<5%V for 250 periods
14
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Note:
Testing was conducted on MPV meters installed through the covers of grounded metal enclosures with cable shields grounded at the point of entry representing installations designed to optimize EMC performance.
Declaration of Conformity available at www.koboldusa.com
SAFETY INFORMATION
Warning!
!
CAUTION: Read complete
instructions prior to installation and operation of the meter.
Hazardous voltages exist within enclosure. Installation and service should be performed only by trained service personnel.
WARNING: Risk of electric shock or personal injury.
15
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
A
INSTALLATION
There is no need to remove the meter from its case to complete the installation, wiring, and setup of the meter for most applications. Instructions are provided for setting up a 12/24 VDC powered meter to operate from 12 VDC and for changing the transmitter power supply to output 5 or 10 VDC instead of 24 VDC, see page 18.
Unpacking
Remove the meter from box. Inspect the packaging and contents for damage. Report damages, if any, to the carrier.
If any part is missing or the meter malfunctions, please contact your supplier or the factory for assistance.
Panel Mounting Instructions
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm). Refer to Figure 1 for more details.
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
Remove the two mounting brackets provided with the meter (back-off the two screws so that there is ¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
Insert meter into the panel cutout.
Install mounting brackets and tighten the screws against the panel. To
achieve a proper seal, tighten the mounting bracket screws evenly until meter is snug to the panel along its short side. DO NOT OVER TIGHTEN, as the rear of the panel may be damaged.
A
3.622" (92 mm)
Square Corners to 0.060"
B
1.772"
(45mm)
(1.5mm) Max Radius
Panel Cutout to DIN 43700
Tolerances:
: +0.032 (+0.8mm)
-0.000 (-0.0mm) B: +0.024 (+0.6mm)
-0.000 (-0.0mm)
Figure 1: 1/8 DIN Panel Cutout and Mounting
16
Gasket
Mounting
Bracket
Panel
Mounting
Screw
Removable Connectors
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Mounting Dimensions
Figure 2: Meter Dimensions - Side View
R
O
-
N
+
N
C
C
N
O
N
C
C
O
N
N
C
C
N
N
O
C
C
Figure 3: Meter Dimensions - Top View
17
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Configuration for 12 or 24 VDC Power Option
Do not exceed voltage rating of the selected
Warning!
Meters equipped with the 12/24 VDC power option are shipped from the factory ready to operate from 24 VDC.
To configure the meter for 12 VDC power:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J9 jumper, located behind the power connector, for 12 V as shown below.
Figure 4: Jumper Configuration for 12/24 VDC Power
configuration.
M-LINK
24 VDC
+
12 VDC
_
POWER
MAIN BOARD
J9
J9 CONFIGURATION
24 V
12 V
Factory Default
18
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Transmitter Supply Voltage Selection (P+, P-)
All meters, including models equipped with the 12/24 VDC power option, are shipped from the factory configured to provide 24 VDC power for the transmitter or sensor.
If the transmitter requires 5 or 10 VDC excitation, the internal jumper J4 must be configured accordingly.
To access the voltage selection jumper:
1. Remove all the connectors.
2. Unscrew the back cover.
3. Slide the back cover about 1 inch.
4. Configure the J4 jumper, located behind the input signal connector, for the desired excitation voltage as shown.
Figure 5: Transmitter Supply Voltage Selection
Connections
All connections are made to removable screw terminal connectors located at the rear of the meter.
Use copper wire with 60°C or 60/75°C insulation for all line voltage connections. Observe all safety regulations. Electrical wiring should be performed in accordance with all applicable national, state,
Caution!
and local codes to prevent damage to the meter and ensure personnel safety.
19
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Connectors Labeling
The connectors’ label, affixed to the meter, shows the location of all connectors available with requested configuration.
Do not connect any equipment other than KOBOLD Instruments’ expansion modules, cables, or meters
Warning!
to the RJ45 M-LINK connector. Otherwise damage will occur to the equipment and the meter.
Figure 6: Connector Labeling for Fully Loaded MPV Pulse Input
Power Connections
Power connections are made to a two-terminal connector labeled POWER in Figure 6. The meter will operate regardless of DC polarity connection. The + and - symbols are only a suggested wiring convention.
POWER
-
+
AC or DC
POWER
Required External Fuse:
5 A max, 250 V Slow Blow
Figure 7: Power Connections
20
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Signal Connections
Signal connections are made to a six-terminal connector labeled SIGNAL in Figure 6. The COM (common) terminal is the return for the input signals.
The following figures show examples of signal connections. Setup and programming is performed through the front panel buttons.
Figure 8: Flowmeter Powered by Internal Power Supply
Figure 9: Flowmeter Powered by External Supply
Figure 10: Self-Powered Magnetic Pickup Coil Flowmeter
21
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Figure 11: NPN open Collector Input
Figure 12: PNP Sensor Powered by Internal Supply
Figure 13: Switch Input Connections
22
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Modbus RTU Serial Communications
Serial communications connection is made to an RJ45 connector labeled M-LINK on Figure 6. For interfacing to the meter, use MPV-Option-B for RS-485 or MPV-Option-F for USB. The same port is used for interfacing with all expansion modules (e.g. external relays, digital I/O).
Relay Connections
Relay connections are made to two six-terminal connectors labeled RELAY1 – RELAY4 in Figure 6. Each relay’s C terminal is common only to the normally open (NO) and normally closed (NC) contacts of the corresponding relay. The relays’ C terminals should not be confused with the COM (common) terminal of the INPUT SIGNAL connector.
RELAY4 RELAY3
4365 21
CNONO NC NC C
Figure 11: Relay Connections
RELAY2 RELAY1
4365 21
CNONO NC NC C
23
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
Switching Inductive Loads
The use of suppressors (snubbers) is strongly recommended when switching inductive loads to prevent disrupting the microprocessor’s operation. The suppressors also prolong the life of the relay contacts. Suppression can be obtained with resistor-capacitor (RC) networks assembled by the user or purchased as complete assemblies. Refer to the following circuits for RC network assembly and installation:
C
C
R
R
Figure 12: AC and DC Loads Protection
Choose R and C as follows: R: 0.5 to 1 Ω for each volt across the contacts C: 0.5 to 1 µF for each amp through closed contacts
Notes:
1. Use capacitors rated for 250 VAC.
2. RC networks may affect load release time of solenoid loads. Check to confirm proper operation.
3.
Install the RC network at the meter's relay screw terminals. An RC network may also be installed across the load. Experiment for best results.
Use a diode with a reverse breakdown voltage two to three times the circuit voltage and forward current at least as large as the load current.
Figure 13: Low Voltage DC Loads Protection
24
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
F4 Digital Input Connections
A digital input, F4, is standard on the meter. This digital input connected with a normally open closure across F4 and COM, or with an active low signal applied to F4.
Figure 14. F4 Digital Input Connections
4-20 mA Output Connections
Connections for the 4-20 mA transmitter output are made to the connector terminals labeled MA OUT. The 4-20 mA output may be powered internally or from an external power supply.
24 V
MA OUT
-
+
12-35 VDC
Power Supply
RI- I+
132
RELAY1
321
MA OUT
+
4-20 mA Input
Remote Display,
Chart Recorder, Etc.
24 V
RI- I+
132
-
RELAY1
321
-
+
4-20 mA
Input Meter
Figure 15: 4-20 mA Output Connections
Analog Output Transmitter Power Supply
The internal 24 VDC power supply powering the analog output may be used to power other devices, if the analog output is not used. The I+ terminal is the +24 V and the R terminal is the return.
25
KOBOLD Model MPV Pulse Input Rate/Totalizer Operating Instructions
External Relay & Digital I/O Connections
The relay and digital I/O expansion modules MPV-Option-R & MPV­Option-S are connected to the meter using the CAT5 cable provided with each module. The two RJ45 connectors on the expansion modules are identical and interchangeable; they are used to connect additional modules to the system.
Note: The jumper located between the RJ45 connectors of the MPV-
Option-S must be removed on the second digital I/O module in order for the system to recognize it as module #2.
Do not connect or disconnect the expansion modules with the power on!
Warning!
More detailed instructions are provided with each optional expansion module.
Figure 16: Expansion Modules & DIN Rail Mounting Kit
RLY5 RLY6 RLY7 RLY8
12
NO C NO C NO C NO C
345678
Figure 17: External Relays Module Connections
26
Loading...
+ 58 hidden pages