Kobold MPV Specifications

Process Panel Display
Dual-Line Rate and Total
measuring
monitoring
analyzing
MPV
• Pulse or Analog Inputs
• Displays Rate and Total Simultaneously
• Square Root Extraction
• 5, 10, or 24 VDC Flowmeter Power Supply
• K-Factor, Internal Scaling, or External Calibration
• 32-point Linearization with Free Software
• Open Channel Flow with Programmable Exponent
• Gate Function for Rate Display of Slow Pulse Rates
• Isolated 24 VDC @ 200 mA Transmitter Power Supply
• On-board Digital Input
• Modbus® RTU Communication Protocol
KOBOLD companies worldwide:
ARGENTINA, AUSTRALIA, AUSTRIA, BELGIUM, BULGARIA, CANADA, CHILE, CHINA, COLOMBIA, CZECH REPUBLIC, EGYPT, FRANCE, GERMANY, HUNGARY, INDIA, INDONESIA, ITALY, MALAYSIA, MEXICO, NETHERLANDS, PERU, POLAND, REPUBLIC OF KOREA, ROMANIA, SINGAPORE, SPAIN, SWITZERLAND, TAIWAN, THAILAND, TUNISIA, TURKEY, UNITED KINGDOM, USA, VIETNAM
01/10-2015
KOBOLD Instruments, Inc. 1801 Parkway View Drive Pittsburgh, PA 15205
Main Ofce:
1.800.998.1020
1.412.788.4890 info@koboldusa.com www.koboldusa.com
Process Panel Display Model MPV
Description
The MPV is designed for simultaneous display of both the flow rate and total for flowmeters with analog or pulse outputs. The upper display can be programmed to display flow rate, total, or grand total and the lower display can be programmed to display flow rate, total, grand total, engineering units, custom legends, or can be turned off. Both displays are also capable of displaying relay set points, or maximum and minimum values. They are also able to provide power to the flowmeter. The MPV features a rugged design with a unique front panel that is nearly impenetrable in typical applications. Set-up is easy with the user-friendly dual line display.
Specifications
Display: Upper Display: 0.60” (15 mm) high. Lower Display: 0.46” (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs
Intensity: 8 Intensity Levels, User Adjustable Update Rate: 5/second (200 ms) Overrange: Flashes 999999 Underrange: Flashes -99999
Display Assignment: The upper and lower displays may be
assigned to rate, total, grand total, alternate (rate/total, rate/grand total, rate/units, total/ units, and grand total/units), max/min, units (lower display only), set points, or Modbus
®
input. Additional displays are available if parameter total is off, and parameter d-SCAL is on: gross, alternating gross/net, PV1, PV2, and PCT
Front Panel: NEMA 4X, IP 65 Programming
Methods: Four front panel buttons, digital inputs, PC
and MeterView Pro software, Modbus® registers, or cloning using 'Copy' function.
Noise Filter: Programmable from 2 to 199 (0 disables) Filter Bypass: Programmable from 0.1 to 99.9% of span Recalibration: Calibrated by factory, recommended to
recalibrate at least every twelve months Max/Min Display: Max (peak) and Min (valley) readings are
stored until user reset of power to meter is cycled
Password: Three programmable passwords restrict modification of programmed settings and two prevent resetting the totals
Non-Volatile Memory: All programmed settings are stored in non-
volatile memory for a minimum of ten years if power is lost
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC 20 W max, or jumper selectable 12/24 V
DC
±10%, 15 W max.
Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 10%. 12/24
VDC powered models selectable for 24, 10, or 5 VDC supply (internal jumper J4). 85-265 VAC models rated @ 200 mA max, 12/24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply
Normal Rejection Mode: Greater than 60 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line, 500 V
input-to-output or output-to-P+ supply
Operating Temp. Range: -40...149 °F
Storage Temp. Range: -40...185 °F
Relative Humidity: 0 to 90% non-condensing
Connections: Removable screw terminal blocks accept
12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial comm. adapters
Enclosure: 1/8 DIN, high impact plastic, UL-94V-0 Mounting: 1/8 DIN panel cutout required, 3.622"
x 1.772", bracket assemblies included
Tightening Torque: Screw terminal connectors, 5 lb/in
Dimensions: 4.68” x 2.45” x 5.64” Weight: 9.5 oz (269 g) UL File Number: UL & c-UL Listed. E160849; 508
Industrial Control Equipment. Warranty: 3 years parts & labor
*Except where noted all specifications apply to operation at 77 °F.
2
www.koboldusa.com
No responsibility taken for errors;
subject to change without prior notice.
Process Panel Display Model MPV
Analog Input
Inputs: Field selectable: 0-20, 4-20 mA, ±10 V
DC
(0-5, 1-5, 0-10 V), Modbus PV (Slave) Accuracy: ± 0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy range: 10-100% of calibrated span
Temperature Drift: 0.005% of calibrated span/°C max from 0
to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient
Signal Input Conditioning: Linear, square root, programmable
exponent, or round horizontal tank volume calculation
Multi-Point Linearization: 2 to 32 points
Programmable Exponent: 1.0001 to 2.9999
Low-Flow Cutoff: 0-999999 (0 disables)
Decimal Point: Up to five decimal places or none (x.xxxxx, xx.xxxx, xxx.xxx, xxxx.xx xxxxx.x, xxxxxx)
Calibration Range:
Input Range Min Span Input 1 & 2
4-20 mA 0.15 mA
± 10 V 0.10 V
*Error message appears if input signals are too close
Input Impedance: Voltage ranges: > 1 MΩ, Current ranges: 50-100 Ω (depending on resettable fuse impedance
Input Overload: Current input protected by resettable fuse,
30 VDC Max, reset after fault is removed
Pulse Inputs
Inputs: Field selectable: pulse or square wave 0-5 V, 0-12 V, or 0-24 V @ 30 kHz; TTL; open collector 4.7 kΩ pull-up to 5 V @ 30 kHz; NPN or PNP transistor, switch contact
4.7 kΩ pull-up to 5 V @ 40 Hz; coil (sine wave) 40 mVp-p min @ 10 kHz; Modbus® PV (Slave)
Low Voltage Mag. Pick-up: Isolated, sensitivity of 40 mVp-p to 8 Vp-p
Min. Input Frequency: 0.001 Hz (Min. frequency depends on high gate setting)
Max. Input Frequency: 30,000 Hz (10,000 for low voltage mag. pick-up)
Pulse Inputs Continued
Input Impedance: Pulse input is >300 kΩ @ 1 KHz, open
collector/switch input is 4.7 kΩ pull-up to 5 V
Accuracy: ± 0.03% of calibrated span ±1 count Display
Update Rate: Total: 10/sec, Rate: 10/sec to 1/1000 sec Temperature
Drift: Not affected by changes in temperature Multi-Point
Linearization: 2 to 32 points Low-Flow
Cutoff: 0-999999 (0 diasbles) Decimal Point: Up to five decimal places or none Calibration: May be calibrated using K-factor, scale
using internal calibration, or calibrate by applying an external calibration signal
K-Factor: Field programmable K-factor converts input pulses to rate in engineering units, may be programmed from 0.00001 to 999,999 pulses/unit
Calibration Range: Input 1 signal set anywhere, input 2 set above
Filter: Programmable contact de-bounce filter, 40 to 999 Hz max. input frequency
Time Base: Second, minute, hour, day Low Gate: 0.1 to 99.9 seconds High Gate: 2.0 to 999.9 seconds
Rate/Totalizer
Rate Display Indication: 0 to 999999, “R” LED illuminates
Total Display & Total Overflow: 0 to 999,999, “T” LED illuminates and “GT”
for grand total, up to 999,999,999 with total-overflow feature
Total Decimal Point: Up to five decimal places or none,
total decimal point is independent of rate decimal point
Totalizer: Calculates total based on rate and field programmable multiplier to display total in engineering units, time base must be selected according to the time units in which the rate is displayed, selectable up/down count
Totalizer Rollover: When display exceeds 999,999,999 relay status reflects the display value
Total Overflow Override: Program total reset for automatic with 0.1 second delay and set point 1 for 999,999
No responsibility taken for errors; subject to change without prior notice.
www.koboldusa.com
3
Process Panel Display Model MPV
Rate/Totalizer Cont.
Totalizer Presets: Up to 8, user selectable, any set point can
be assigned to total and be programmed anywhere in the meter range
Total Reset Delay: 0.1...999.9 seconds, applied to first relay assigned to total or grand total, if meter is programmed to reset total to zero automatically when preset is reached then a delay will occur before total is reset
Total Reset: Via front panel button, external contact closure on digital inputs, automatically via user selectable preset value and time delay, or through serial communications
Total Reset Password: Total and grand total passwords may be
entered to prevent resetting the total or grand total from the front panel
Non-Resettable Total: The grand total can be programmed as a
non-resettable total by entering the password “050873”
Caution: Once the grand total has been programmed
as non-resettable, it can't be disabled
Relays
Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (≈ 50 watts) @ 125/250 VAC for inductive loads such as contactors, solenoids, etc
Noise Suppression: Recommended for each relay contact switching inductive loads
Relay Assignment: May be assigned to rate, total, grand total
Deadband: 0-100% of span, user programmable High or Low
Alarm: Program any alarm for high or low trip point, unused alarms and relays can be turned off
Relay Operation: Automatic (non-latching), latching (requires
manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), off (disable unused relays and enable interlock feature, manual on/off control mode)
Relay Reset: User selectable via front panel buttons digital inputs, or PC
1) Automatic reset only (non-latching) when input passes reset or total reset to 0
2) Automatic + manual reset at any time (non-latching)
3) Manual reset only, anytime (latching)
4) Manual reset after alarm clears (latching)
Relays Cont.
Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset
Time Delay: 0 to 999.9 seconds, on & off relay time delays, programmable and independent for each relay
Fail Safe Operation: Programmable and independent for each relay
Note: Relay coil energized in non-alarm condition,
in case of power failure, relay goes to alarm state
Auto Initialization: When power is applied to meter, relays reflect state of input to meter
Isolated 4-20 mA Transmitter Output
Output Source: Process variable (PV), max, min, set points
1-8, manual control setting, or Modbus® input
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated: 4.000 to 20.000 = 4-20
mA output Analog Output
Programming: 23.000 mA Max for all parameters: overrange, underrange, max, min, break
Accuracy: ± 0.1% of span ± 0.004 mA Temperature
Drift: 0.4uA/°C max from 0 to 65 °C ambient,
0.8 uA/°C max from -40 to 0 °C ambient
Note: analog output drift is separate from input
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%, may
be used to power the 4-20 mA output or other devices, all models rated @ 40 mA max.
External Loop Power Supply: 35 VDC Max
Output Loop
Resistance: Loop Resistance
Power Supply Minimum Maximum
24 V
35 V
DC
DC
10 Ω 700 Ω
100 Ω 1200 Ω
No responsibility taken for errors;
4
www.koboldusa.com
subject to change without prior notice.
Process Panel Display Model MPV
Serial Communications
Protocol: Modbus® RTU Meter Address
Slave ID: 1-247 Baud Rate: 300-19,200 bps Transmit Time
Delay: Programmable, between 0 and 199 ms or transmitter always on for RS-422
Data: 8 bit (1 start bit, 1 or 2 stop bits) Parity: Even, odd, or none with 1 or 2 stop bits Byte-to-byte
Timeout: 0.01-2.54 seconds Turnaround
Delay: Less than 2 ms (fixed)
Order Details (Example: MPV-4 5 2 4 R X)
Model Function
Operating
Voltage
Input Signal Output Options
..0 = None*
Connections
RELAY4 RELAY3
4 36 5 2 1
C NONO NC NC C
F4
P- COMP+ V+ mA+
3 41 2 5
DW1815
SIGNAL
Pulse Input Connections
RELAY2 RELAY1
4 36 5 2 1
C NONO NC NC C
6
1 2 3 4 5 6 7 8
M-LINK
Analog Input Connections
MA OUT
+
POWER
13 2
RI- I+
-
21
..1.. = Rate and Total
MPV-..
..4.. = Batching
Dimensions
..3.. = 12-36 V
..5.. = 85-265 V
2.45"
(62 mm)
0.59"
(15 mm)
DC
1.76"
(44.5 mm)
6" (152 mm) Clearance
Side View
..1.. = Pulse Input
..2.. = Analog Output
AC
(121 mm)
4.77"
5.05"
(128 mm)
..2 = Two SPDT Relays*
..3 = 4-20 mA*
..4 = Four Relays
..5 = 4-20 mA & Two SPDT Relays
..7 = 4-20 mA & Four SPDT Relays
R
C
+
C
NO
NC
NC
Optional Connectors Installed
3.61"
(91.5 mm)
-
4.68"
(119 mm)
Top View
NO
C
NC
..B = RS-422/485 Serial Adapter
..E = Custom Set-up
..G = Meter Copy Cable
..R = 4x Relay Expansion Module
..S = Digital I/O Expansion Module
..X = NEMA 4X Enclosure
*Output Option Only Available for MPV-1 Models
C
NO
NC
NO
4.17"
(106 mm)
No responsibility taken for errors; subject to change without prior notice.
www.koboldusa.com
5
Loading...