Kobold MAN-SD series Operating Instructions Manual

Page 1
Operating Instructions
for
Digital Manometer
Model: MAN-SD
Page 2
page 2 MAN-SD 03/04
1. Contents
1. Contents........................................................................................................2
2. Note ..............................................................................................................3
3. Instrument Inspection....................................................................................3
4. Regulation Use..............................................................................................4
5. Operating Principle........................................................................................4
6. Mechanical Connection.................................................................................5
7. Electrical Connection ....................................................................................6
8. Function Keys ...............................................................................................7
9. Adjustments ..................................................................................................7
10. Control Functions ..........................................................................................8
11. Maintenance ...............................................................................................12
12. Technical Information..................................................................................12
13. Order Codes ...............................................................................................13
14. Dimensions .................................................................................................14
15. Declaration of Conformance .......................................................................15
Manufactured and sold by:
Kobold Messring GmbH
Nordring 22-24
D-65719 Hofheim
Tel.: +49(0)6192-2990
Fax: +49(0)6192-23398
E-Mail: info.de@kobold.com
Internet: www.kobold.com
Page 3
MAN-SD
MAN-SD 03/04 page 3
2. Note
Please read these operating instructions before unpacking and putting the unit into operation. Follow the instructions precisely as described herein. The devices are only to be used, maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the machines fulfil the EWG-machine guidelines.
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition. Should damage to a device be visible, we recommend a thorough inspection of the delivery packaging. In case of damage, please inform your parcel service / forwarding agent immediately, since they are responsible for damages during transit.
Scope of delivery:
The standard delivery includes:
Transmitter with display
Operating Instructions
9 Volt – block battery (IEC 6 LR 61)
Page 4
page 4 MAN-SD 03/04
4. Regulation Use
Any use of the Digital Manometer, model: MAN-SD, which exceeds the manufacturers specification may invalidate its warranty. Therefore any resulting damage is not the responsibility of the manufacturer. The user assumes all risk for such usage.
The model MAN-SD serves to measure, monitor and transmit pressure­dependent operational processes in machines and systems.
These devices are equipped as follows:
4-digit LCD display
Three Programming keys
Process connection (St. Steel)
Power Supply via 9V block battery
Limit relays (option)
Peak value memory (option)
Analogue output (option)
5. Operating Principle
A ceramic sensor detects system pressure and sends the signal to evaluation electronics. The sensor signal is conditioned and sent to the LCD display as a pressure reading. Parallel to this, an output is provided as analogue signal for the purpose of transmitting measured pressure. A programmable relay-output is also available as an option.
Page 5
MAN-SD
MAN-SD 03/04 page 5
6. Mechanical Connection
Before installation:
Ensure that the max. pressure in your system is within the prescribed range of the digital manometer. The measuring range can be read from the nameplate label of the device.
Make sure that the permitted max. operational temperature of the device is not exceeded.
Confirm that there are no fragments of packing material present inside the pressure sensing port.
Installation:
Ensure that the piping is fully depressurised..
The digital manometer should be mounted just like a mechanical manometer.
With standard thread connection, sealing is achieved by means of a suitable
gasket (flat-seal or seal-ring DIN 16258).
While threading in the device, install by using a wrench on the hexagonal screw (SW 24) and not the gauge housing.
If possible, after the mechanical installation, pressure test the piping to determine whether the connection joint is adequately sealed.
Attention! The MAN-SD digital manometer must be installed into a grounded system. This action is necessary in order to fulfil the EMV­guideline.
Flat seal-ring acc. to DIN 16 258
Page 6
page 6 MAN-SD 03/04
Cable wires colour-coded
plug M12x1 5-core cable
21
4
5
3
View of plug contacts
7. Electrical Connection
Attention! Please ensure that you use a 9 V – alkali-manganese-block battery (IEC 6 LR 61).
Make sure that the power supply lines are not active. (Only with option limit-contacts or analogue output.)
Open the battery enclosure on the back-side of the unit and connect the 9V block battery with the connection plug.
Place the 9V block battery in the enclosure and close it with the lid.
Terminate the connection wires on the plug (cable), as shown in the illustration
below. (Only with option limit-contacts or analogue output.)
Power supply conductor (area of cross-section): min.0.34 mm².
Attention! Incorrect wiring will lead to damage of the unit’s electronics.
Cable
No.
MAN-SD2... MAN-SD3... Cable colour
1 brown 2 Contact output (Relay in) white 3 GND (0V Reference) blue 4 Analogue output 0-2VDC black 5 Contact output (Relay out) grey
Page 7
MAN-SD
MAN-SD 03/04 page 7
8. Function Keys
For the selection of menu options, the following functions keys are available:
È Next Menu Option Ç Previous Menu Option
P Press once to Switch-on P Press twice to Switch-off P & È Exit Menu
Adjustment and Function:
Ç Value-adjustment upwards È Value-adjustment downwards
P Enter value and jump to next Menu Option Ç&È Reject input, Return to Menu Option
9. Adjustments
Possible adjustments of the device:
1. Zero point
2. Password (factory pre-set: 0005)
3. Peak value memory (option)
4. Relay and hysteresis (option)
(factory pre-set: switching point on 50% of measuring range)
Factory pre-sets:
1. Battery symbol on: voltage under 7 V
2. Switch-off delay (default: 0 = inactive)
3. Sampling rate/Dampening (default: 5 measurements per second)
4. Analogue output (linear) within measuring range (option)
Page 8
page 8 MAN-SD 03/04
10. Control Functions
10.1. Standard version MAN-SD10...
and unit with analogue output MAN-SD30...
P
1xP = Unit Switch on
LCD Display
1234
P
1xP = Uni t Swi tch off
ÏÐ
Password input
P A S S
P
0 0 0 0
Password
Ï
&
ÐÏ Ð
set on 0005 (fact ory set ti ng)
Ï
Canc el
P
Access t o further Menu Options
Automatic zero-point setting
Z E R O
P
S E t
On confirmation, automatic
(zero)
Ï
&
Ð
P
zero-point adjustment succeeds
ÏÐ
Canc el
Change password
P S E t
P
4 7 1 1
Last setting (example)
Ï
&
ÐÏ Ð
Password change
Ð
Canc el
P
Return to Display
Page 9
MAN-SD
MAN-SD 03/04 page 9
10.2. Unit with peak value memory MAN-SD1S...
and unit with peak value memory +
analogue output MAN-SD3S...
If the peak value memory is activated, the peak value can be reset by pressing the left arrow key.
Note: with the switch-off of the device the peak value memory is reset.
P
1xP = Unit Switched-on
LCD-display
Resetting
Ï
1234
P
Peak value memory 1xP = Unit switched-off
ÏÐ
Peak value memory
P d u
P
o F F
Last Setting
m A x
Register max. value
ÏÐ
m I n
Register min. value
o F F
Peak value memory Off
Ï
&
ÐÏ Ð
Select
Cancel
P
Confirm selection and goto
next Menu Option
Password input
P A S S
P
0 0 0 0
Password
Ï
&
ÐÏ Ð
Set on 0005 (Factory setting)
Ï
Cancel
P
Access to further Menu Options
Automatic zero-point setting (zero)
Z E R O
P
S E t
On confirmation, automatic
Ï
&
Ð
P
zero-point setting succeeds
ÏÐ
Cancel
Change password
P S E t
P
4 7 1 1
Last setting (example)
Ï
&
ÐÏ Ð
Password change
Ð
Cancel
P
Return to Display
Page 10
page 10 MAN-SD 03/04
10.3. Unit with switching output MAN-SD20...
LCD Display
1234
P
1xP = Unit Switched-off
ÏÐ
Password input
P A S S
P
0 0 0 0
Password
Ï
&
ÐÏ Ð
Set on 0005 (factory setting)
Ï
Cancel
P
Access to further Menu Options
Relay set point on rising pressure
r E f
P
0 6. 5 0
Last switching point setting
Ï
&
ÐÏ Ð
Set sw. point on 07.50 (example)
ÏÐ
Cancel
P
Relay set point on falling pressure
r E b
P
0 6. 4 0
Last return switching point setting
Ï
&
ÐÏ Ð
Set return sw. point on 06.30
ÏÐ
Cancel
P
(example)
Automatic zero-point adjustment (zero)
Z E R O
P
S E t
On confirmation, automatic
Ï
&
Ð
P
zero-point setting succeeds
ÏÐ
Cancel
Change Password
P S E t
P
4 7 1 1
Last setting (example)
Ï
&
ÐÏ Ð
Password change
Ð
Cancel
P
Return to Display
Page 11
MAN-SD
MAN-SD 03/04 page 11
10.4. Unit with switching output + peak value memory
MAN-SD2S...
If the peak value memory is activated, the peak value can be reset by pressing the left arrow key.
Note: with the switch-off of the device the peak value memory is reset.
LDC Displ ay
P
1xP = Unit Switched-on
Resetting
Ï
1234
P
Peak value memory 1xP = Unit Switched-off
ÏÐ
Peak value memory
P d u
P
o F F
Last setting
m A x
Register max. value
ÏÐ
m I n
Register mi n. value
o F F
Peak value memory Off
Ï
&
ÐÏ Ð
Select
Cancel
P
Confirm sel ection and go to
next Menu Option
Password input
P A S S
P
0 0 0 0
Password
Ï
&
ÐÏ Ð
Set on 0005 (factory setting)
Ï
Cancel
P
Access to further Menu Options
Relay set point on rising pressure
r E f
P
0 6. 5 0
Last switching point setting
Ï
&
ÐÏ Ð
Set sw. point on 07.50 (example)
ÏÐ
Cancel
P
Relay set point on falling pressure
r E b
P
0 6. 4 0
Last return switching point setting
Ï
&
ÐÏ Ð
Set return sw. point on 06.30 (example)
ÏÐ
Cancel
P
Automatic zero-point adjustment (zero)
Z E R O
P
S E t
On confirmation, automatic
Ï
&
Ð
P
zero-point setting succeeds
ÏÐ
Change password
P S E t
P
4 7 1 1
Last setting (example)
Ï
&
ÐÏ Ð
Password change
Ð
Cancel
P
Return to Display
Page 12
page 12 MAN-SD 03/04
11. Maintenance
In case, the medium to be measured is not polluted, the unit is maintenance-free.
12. Technical Information
Nominal size: 74 mm Accuracy class 0,5 % Display: 4-digit LCD; digit height 12,7 mm Measuring range: -1...0, 0...1, 0...1.6, 0...2.5, 0...4, 0...6, 0...10,
0...16, 0...25, 0...40, 0...60, 0...100, 0...160,
0...250, 0...400 bar
Overload range: 3 x P
N
(up to 40 bar)
2 x P
N
(60 to 160 bar) 1,5 x PN (from 250 bar) Power supply: 9 VDC (block battery, IEC 6 LR 01) Service-life at conversion rate 5/s: 5000 h (block battery 600mAh), 10000 h (Lithium block battery 1200 mAh) Conversion rate: 5 per sec. (standard) (1 to 10 per sec. factory-adjustable)
Automatic switch-off times: 2 ...... 90 min, only factory-adjustable
(auto off) (not recommended with analogue or switching
output), 0 = inactive Zero point correction: ≤ ± 25 % Parts in contact with medium: st. steel 1.4571, ceramic, NBR (Buna-N) Connection: G ¼ A (other connection on request) Medium temperature: -30...+85 °C Ambient temperature: 0...+60 °C Storage temperature: -30...+80 °C Permissible relative humidity: <90%, not condensing Protection cat.: IP 65 Limit-value relay (Option): N/O, bistable adjustable setpoint and hysteresis Max. switching power: 30 V
AC/DC
, 2 A (for relay output)
Analogue output (Option): 0 - 2 V
DC
Load: ≥ 100 kΩ Electrical connection M 12 x 1 plug DIN (female connector as accessorie available) Total cable length: max. 3 metres
Peak value memory (option): MIN or MAX value, resetting via keypad
Page 13
MAN-SD
MAN-SD 03/04 page 13
13. Order Codes
MAN-SD 1 0 C315 0
Output
without..................................................
1
Relay/N/O contact................................
2
Analogue output....................................
3
Peak value memory
without........................................................
0
with..............................................................
S
Measuring range code
-1 to 0 bar .......................................................
A315
0 to 1 bar .........................................................
B025
0 to 2.5 bar ......................................................
B045
0 to 4 bar .........................................................
B055
0 to 6 bar .........................................................
B065
0 to 10 bar .......................................................
B075
0 to 16 bar .......................................................
B085
0 to 25 bar .......................................................
B095
0 to 40 bar .......................................................
B105
0 to 60 bar .......................................................
A115
0 to 100 bar .....................................................
A125
0 to 160 bar .....................................................
A135
0 to 250 bar .....................................................
A145
0 to 400 bar .....................................................
A155
Electrical connection
Without...........................................................................
0
0.5 m cable ...................................................................
K
Plug M12 x 1 ............................................................
S
Page 14
page 14 MAN-SD 03/04
14. Dimensions
5114Ø74
G1/4A
M
1
2
x
1
2
4
Rotatable Display
3
5
5
°
Optional: PG7 (LCD)
SW 24
8
9
38
2
3
0
Page 15
MAN-SD
MAN-SD 03/04 page 15
15. Declaration of Conformance
We, Kobold-Messring GmbH, Hofheim-Ts., Federal Republic of Germany,
declare, that the product
Digital Manometer Model: MAN-SD...
complies with the standards given below:
EN 50081-1.2 1994.03
Electromagnetic compatibility - Generic emission standard
EN 61326-1 1998.01
EN 61010-1 1994.03
Safety requirements for electrical measurement, control, and laboratory use
Also, following EWG guidelines are fulfilled:
89/336/EWG
97/23/EG PED
Category I, Table 1, pipe, gas, group 1 dangerous fluids
Signature:
H. Peters M. Wenzel Date: 12.07.02