Please read these operating instructions before unpacking and setting the unit
into operation. Follow the instructions precisely as described herein.
The devices are only to be used, maintained and serviced by persons familiar
with these operating instructions and in accordance with local regulations
applying to Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the
machines fulfil the EC-machine guidelines.
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition.
Should damage to a device be visible, we recommend a thorough inspection of
the delivery packaging. In case of damage, please inform your parcel service /
forwarding agent immediately, since they are responsible for damages during
transit.
Scope of delivery:
The standard delivery includes:
Magnetic Level Switches for Liquids model: M-...
Operating Instruction
All parts falling under the standard scope of delivery are properly assembled
within the unit.
4. Regulation Use
Magnetic Level Switches are employed for monitoring and control of liquid-levels
in boilers and containers. There are innumerable and diverse applications that
require these Magnetic Level Switches to be made according to customers'
specific requirements.
Attention! These units should not be installed in the vicinity of
strong magnetic fields, since this can impair their intended
functionality.
page 3 DT0493
M series
5. Float designs
Float
Model Form Materials
Cylinder
M01
M02
M03
M04
M05
M061)
M07
M08
M10
M11
M13
M16
M20
solid
material
Cylinder
Hollow
Cylinder
hollow
Ball
hollow
Cylinder
hollow
Cylinder
solid
material
Cylinder
hollow
Cylinder
hollow
Ball
hollow
Ball
hollow
Cylinder
hollow
Cylinder
hollow
Ball
hollow
NBR 18 25 10 > 0.6 80 °C 10 bar
PP 26 16 10 > 0.65 80 °C 3 bar
PVC-U 26 26 10 > 0.9 55 °C 3 bar
St. steel
1.4404
PP 42 40 14 > 0.6 80°C 3 bar
PP 40 20 14 > 0.9 90 °C 100 bar
PVC-U 42 40 14 > 0.9 55 °C 3 bar
St. steel
1.4404
St. steel
1.4404
St. steel
1.4404
PVDF 38 60 18 > 0.6 125°C 2 bar
PVC-U 60 60 18 > 0.8 55°C 3 bar
St. steel
1.4404
Outside
[mm]
30 28 9 > 0.8 150 °C 15 bar
44 52 15 > 0.65 150°C 20 bar
52 52 15 > 0.6 150°C 30 bar
52 52 15 > 0.6 150°C 30 bar
95 95 20.8 > 0.5 150°C 15 bar
1) For M06 model. one float is required for each switch point.
For all other floats two contacts can be operated with one float.
Height
[mm]
Hole
Bore
[mm]
Min. Liquid
Density
[kg/dm³]
Max.
Temperature
°C
Nominal
Pressure
[bar] at
20 °C
page 4 DT0493
M series
Supplementary devices:
1. Contact protection relays
We recommend the use of contact protection relays in conjunction with sealed
contacts.
Contact protection relays have the following advantages:
No contact overloads arising from sparking and high currents, which can,
for example, be caused by self-induced e.m.f.`s when switching solenoid
valves.
Float switches are electrically isolated from the high voltage power supply
system.
Protection for persons who come into contact with liquids according to
Float switches with damping tube for agitated or dirty liquids can be supplied upon
request.
3. Temperature monitoring
Float switches with integrated temperature switch, fixed switch point between
60 °C and 150 °C upon request.
Option: Pt 100 available
4. Mounting instructions
Float switches can also be fitted in the bottom for vessels.
Attention: The contact operation is then reversed.
AC
page 5 DT0493
M series
6. Operating Principle
Kobold magnetic float switches are fitted with a hermetically sealed contact which
is situated in the tube.
The float sliding on the tube contains a ring magnet whose magnetic field
switches the sealed contact in a non-contacting fashion. The sealed contacts are
available as N/O, N/C or changeover contacts.
The float sliding up and down on the liquid is the only moving part in the Kobold
magnetic float switches.
7. Mechanical Connection
The slide-tube of the float switch may not be bent or exposed to hard impacts,
since otherwise the reed contacts inside the tube can be damaged.
Adjustment-rings or anchor-clamps may not be readjusted, since otherwise the
switching function (N.O. contact, N.C. contact or changeover switch) is no more
guaranteed.
Ensure the correct use of cable gland and gasket on float switches with plug to
prevent the penetration of humidity.
While installation is carried out, please ensure that the float can move freely (due
allowance should be given to distances from side-walls!).
Mounting position of the slide-tube may not deviate more than ±30° from vertical
position.
If the float has to be removed, pay attention to correct orientation when replacing
the float.
8. Area of application
Magnetic level switch M series are used exclusively for level control and
monitoring of liquid media.
The liquids should not contain suspended solids or tendency to crystallize.
Ensure that the construction materials of the float switch have chemical
resistance sufficient to prevent mechanical deformations that may affect it.
9. Maintenance
In liquids that can cause deposits, the float has to be cleaned at regular intervals.
In this case the measuring tube and float should be cleaned from such deposits.
Other maintenance jobs are not required.
page 6 DT0493
M series
10. Technical Data
Contact NO/NC: 230 V
Contact SPDT: 100 V
Contact NO/NC: 230 V
Contact SPDT: 230 V
/ 0,5 A / 10 VA ( M01...M04 )
AC/DC
/ 0,5 A / 3 VA ( M01...M04 )
AC/DC
/ 1 A / 60 VA ( M05...M20 )
AC/DC
/ 1 A / 60 VA ( M05...M20 )
AC/DC
Atex Exia version : Ui: 40V
Protection type: IP64 ( M01...M04 ), IP65 ( M05...M20 )
IP65 ( all models with connection head )
Min. liquid density: See float design table
Max. pressure (at 20ºC): 2 bar ( M13 )
3 bar ( M02, M03, M05, M16 )
3 bar ( M01 with PVC tube )
10 bar ( M01 with st. st. or brass tube )
15 bar ( M04, M20 )
20 bar ( M08 )
30 bar ( M10, M11 )
100 bar ( M06 )
Max. temp. with PVC cable: 55ºC ( models with PVC tube )
70ºC ( Models without PVC tube )
Max. temp. with. silicone cable: See max. temperature in float design table
Max. length of guide tube: 1 m ( PVC Ø8 mm )
2 m ( st. st. or brass Ø8 mm )
2 m ( PVC Ø12 mm )
3 m ( PVDF or PVC Ø16 mm )
4 m ( st. st. or brass Ø12 mm )
6 m ( st. st. Ø18 mm )
Hysteresis: 3-5 mm difference in level
page 7 DT0493
M series
Definition of switching points referred to density 1 Kg/dm
L1
L2
L3
L4
L0
3
Attention models without earth conductor must be used only with safety extra low voltage ( i.e. contact protection relays ) or external earthing.
11. Electrical Information
Performance data indicated on the device label are absolute maximum ratings,
which may not be exceeded even for brief periods of time. They refer to ohmic
load (resistive load). When switching inductances (e.g. coils from relays and
contactors), the contacts of the float switches should be protected employing
suitable means from high cut-off voltage surges.
Examples of protection circuitry
For capacitive, inductive and lamps load, we recommend our contact protection
relays or the following suppressor circuits.
Lamp load with series or parallel Protection with a RC suppressor
resistance to the reed switch. for a.c. current and inductive load load.
Protection with a diode Protection with an inductance or
for d.c. current and inductive load. resistance for capacitive load.
page 8 DT0493
M series
The Magnetic Level Switches are connected according to the following connection
diagrams.
Attention! While making electrical connections of these devices,
please observe relevant safety measures, norms, regulations and ECguidelines, in particular, DIN VDE 0100, section 610. Float switches
made of PVC can be used up to max. 55 °C!
Connection diagrams
Terminal
connection
coding in
connection
head
1 WH White
2 BN Brown
3 GN Green
4 YE Yellow
5 GR Grey
6 PK Pink
7 BU Blue
8 RD Red
9 BK Black
* For special cables the codification is by numbers
Models with Plug 3-pole
L1- S or C L1- W
Models with Plug 6-pole
L1- S or C
L2- S or C
L3- S or C
L1- W
Cable colour
coding
(DIN47100) for
standards in
silicone and PVC
L1- S or C
L2- S or C
L1- W
L2- W
page 9 DT0493
M series
Models M01….M04
1 switch point ( L1 )
L1- S or C L1- W
2 switch points ( L1, L2 )
L1- S or C
L2- S or C
3 switch points ( L1, L2, L3 )
L1- S or C
L2- S or C
L3- S or C
L1- W
L2- W
L1- W
L2- S or C
L1- S or C
L2- W
page 10 DT0493