2.Note
Please read these operating instructions before unpacking and putting the unit into operation. Follow the instruction precisely as described herein. The devices are only to be used, maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health & Safety and prevention of accidents.
By usage in machines, the measuring unit should be used only then when the machines fulfil the EC-machine guidelines.
3. Regulation use
LSP-P
These units (type LSP) are employed in order to monitor the air-flow in air environment industry. All these units are equipped with adjustable limit-contacts. Monitoring of fluids is suitable only for those gases and air, which would not attack the materials used in flow monitor. This air-flow monitor should not be used for monitoring of flammable and explosive gases.
Material Combination
Housing Galvanised base-plate
/Cover (ABS) Paddle St. Steel (AISI) Paddle arm Brass (Ms 58) Connection- plate Galvanised iron
Flat Gasket Flexoid
Switch Off/On (adjustable)
Switch-off values (min) 1.5 m / sec.
(max) 8.0 m / sec. (with shortened paddle)
Switch-on values (min) 2.5 m / sec.
(max) 9.2 m / sec. (with shortened paddle)
and
4.Operating Principle
The air flow being controlled presses against the paddle, which is mechanically linked to a dust-tight changeover microswitch. The latter will signal whether or not the minimum or maximum preset air flow exists. The switching point is adjustable over a wide range of values.
LSP-P 01/1116
Page 3
LSP-P
5.Instrument Inspection
Instruments are checked before dispatch and should arrive in perfect condition. In case of damage, please inform your local Kobold office or if you had the parcel transport your parcel service / forwarding agent immediately, since they are responsible for damages during transit. Should the damage to a device be visible, we recommend a thorough inspection of the delivery packing.
Scope of delivery:
Air-Flow Monitor Model: LSP-P
Flat Gasket
Operating Instructions
6.Mechanical connection
Before mounting
Please ensure that the actual flow value remains within the switching range of
the unit.
Make sure that the permitted max. operational pressure and temperature limits
of this unit are not exceeded.
Please ensure a minimum run inner pipe diameter of 5 x D upstream and
downstream of the switch.
Assembly
Drill a hole and a slit in your air-channel as shown in the adjacent
drawing.
Fix the flow-monitor over the air-channel and secure it with 4 metal
screws (D=3.5 mm).
The paddle can also be mounted after the installation, it is
then sufficient to drill a 20 mm diameter hole.
Sealing is carried out by means of supplied flat gasket.Mounting of this unit is position independent. The affixed arrow sign
on housing must point in the direction of the flow. The upper part of the flow-monitor must be vertical with respect to the pipe axis. With vertical mounting, the switching point must be adjusted in order to compensate for the paddle-weight.
For gases containing dust particles, the flow monitor must be positioned in
such a way that no dust particles can deposit inside the connection head (e.g. mounting on the upper side of the air-channel).
Page 4
LSP-P 01/1116
7. Electrical Connection
Please ensure that the voltage as well as the current
values of your power supply does not exceed the permitted values specified for the flow monitor.
Before making connections, be assured that the
power supply lines are not active.
Remove the housing of the flow monitor by loosening4 screwsMake connections to the flow monitor as shown in the adjoining figure.
After making connections between external units and the limit-contact, the unit is ready for operation.
Erde ground
LSP-P
red
blue
whit
e
LSP-P 01/1116
Page 5
LSP-P
8.Commissioning
These units are supplied along with an adjustable micro-switch. The contact is
hange-over type, which, depending on connections, may be used as normally-
c closed or normally-open switch. These units are factory-set at a switch-off value of 1.5 m / sec. A higher "switch-off" value is set by rotating the range-screw in the clockwise direction. In a switching value over 5 m / sec. is desired, then the paddle must be trimmed at the marked position. When trimmed, the factory-set value changes to 2.5 m/sec.
Page 6
LSP-P 01/1116
9.Technical Information
Max. Switching Current: 15 (8) A Max. Switching Voltage: 24 - 250 VAC Protection Cat.: IP 65 (from external channel) Max. Medium Temp.: +85 °C Ambient Temperature: -40 °C ...+85 °C
10.Order Codes
Description Order number
LSP-P
Air-flow indicator
LSP-
1100P
11.Maintenance
In case, the medium to be measured is not polluted, LSP-P flow-monitor is regarded as maintenance-free. Otherwise, presence of large-size dust-particles may lead to the jamming of paddle arm. Depending upon the degree of pollution, a routine check after regular intervals is recommended.
LSP-P 01/1116
Page 7
LSP-P
12.Dimensions
Page 8
LSP-P 01/1116
13.EU Declaration of Conformance
We, KOBOLD Messring GmbH, Hofheim-Ts, Germany, declare under our sole responsibility
Air-Flow Monitor Model: LSP-P
to which this declaration relates is in conformity with the standards noted below: EN 60730-2-15:2010 Automatic electrical controls for household and
similar use - Part 2-15: Particular requirements for automatic electrical air flow, water flow and water level sensing controls
Also the following EC guidelines are fulfilled:
2014/30/EU EMC Directive 2014/35/EU Low Voltage Directive 2011/65/EU RoHS (category 9) industrial monitoring and control
that the product:
instruments, compliant, no CE-marking for the transitional period until 2017
LSP-P