Kobold LPS-P, LPS-1100P Operating Instructions Manual

Operating Instructions
for
Air-Flow Monitor
Model: LPS-P
LPS-P
1. Contents
1.Contents ........................................................................................................ 2
2.Note .............................................................................................................. 3
3.Regulation use .............................................................................................. 3
4.Operating Principle ........................................................................................ 3
5.Instrument Inspection .................................................................................... 4
6.Mechanical connection .................................................................................. 4
7.Electrical Connection .................................................................................... 5
8.Commissioning .............................................................................................. 6
9.Technical Information .................................................................................... 7
10.Order Codes ................................................................................................. 7
11.Maintenance ................................................................................................. 7
12.Dimensions ................................................................................................... 8
13.EU Declaration of Conformance .................................................................... 9
Manufactured and sold by:
Kobold Messring GmbH
Nordring 22-24
D-65719 Hofheim
Tel.: +49(0)6192-2990
Fax: +49(0)6192-23398
E-Mail: info.de@kobold.com
Internet: www.kobold.com
LPS-P
2. Note
Please read these operating instructions before unpacking and putting the unit into operation. Follow the instruction precisely as described herein. The devices are only to be used, maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health & Safety and prevention of accidents.
By usage in machines, the measuring unit should be used only then when the machines fulfil the EC-machine guidelines.
3. Regulation use
These units (type LPS) are employed in order to monitor the air-flow in air and environment industry. All these units are equipped with adjustable limit-contacts. Monitoring of fluids is suitable only for those gases and air, which would not attack the materials used in flow monitor. This air-flow monitor should not be used for monitoring of flammable and explosive gases.
Material Combination
Housing Galvanised base-plate
/Cover (ABS) Paddle St. Steel (AISI) Paddle arm Brass (Ms 58) Connection- plate Galvanised iron
Flat Gasket Flexoid
Switch Off/On (adjustable)
Switch-off values (min) 1.5 m / sec. (max) 8.0 m / sec. (with shortened paddle) Switch-on values (min) 2.5 m / sec. (max) 9.2 m / sec. (with shortened paddle)
4. Operating Principle
The air flow being controlled presses against the paddle, which is mechanically linked to a dust-tight changeover microswitch. The latter will signal whether or not the minimum or maximum preset air flow exists. The switching point is adjustable over a wide range of values.