Kobold KSR User Manual

Page 1
Operating Instructions
for
Low-Volume Flow Switch
Model: SVN / KSR
Page 2
SVN/KSR
1. Contents ........................................................................................................ 2
2. Note .............................................................................................................. 3
3. Instrument Inspection .................................................................................... 3
4. Regulation Use .............................................................................................. 3
5. Operating Principle ........................................................................................ 4
6. Use in Hazardous Areas ............................................................................... 4
6.1. General ................................................................................................ 4
6.2. Electrical Contact ................................................................................. 5
6.3. Potential Equalisation .......................................................................... 5
7. Mechanical Connection ................................................................................. 5
8. Electrical Connection .................................................................................... 6
8.1. SVN-1200 (Namur) .............................................................................. 6
8.2. SVN-1201 (Proximity Switch) ............................................................... 6
8.3. KSR with Reed Contact ....................................................................... 7
9. Maintenance ................................................................................................. 8
10. Technical Information .................................................................................... 8
11. Order Codes ................................................................................................. 9
12. Dimensions ................................................................................................... 9
13. Declaration of Conformance ....................................................................... 10
Manufactured and sold by:
Kobold Messring GmbH
Nordring 22-24
D-65719 Hofheim, Germany
Tel.: +49 (0)6192-2990
Fax: +49(0)6192-23398
E-mail: info.de@kobold.com
Internet: www.kobold.com
Page 2 SVN/KSR K01/0413
Page 3
SVN/KSR
2. Note
Please read these operating instructions before unpacking and putting the unit into operation. Follow the instructions precisely as described herein. The devices are only to be used, maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the machines fulfil the EWG-machine guidelines.
as per PED 97/23/EC
In acc. with Article 3 Paragraph (3), "Sound Engineering Practice", of the PED 97/23/EC no CE mark. Diagram 6, Pipe, Group 1 dangerous fluids
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition. Should damage to a device be visible, we recommend a thorough inspection of the delivery packaging. In case of damage, please inform your parcel service / forwarding agent immediately, since they are responsible for damages during transit.
Scope of delivery:
The standard delivery includes:
Low-Volume Flow Switch model: SVN / KSR
Operating instructions
4. Regulation Use
Any use of the Flow Switch, model: SVN/KSR, which exceeds the manufacturers specification may invalidate its warranty. Therefore any resulting damage is not the responsibility of the manufacturer. The user assumes all risk for such usage.
SVN/KSR K01/0413 Page 3
Page 4
SVN/KSR
5. Operating Principle
The KOBOLD flow switch types SVN and KSR operate on the known suspended float principle of measurement and are suited for liquids and gases. This switch must be fitted vertically with the media flowing from bottom to top.
Set point
The flow switch is designed for small flows. The set point is set at the factory to the value specified by the customer (a decreasing or increasing flow rate is specified).
6. Use in Hazardous Areas
6.1. General
The Low-Volume Flow Switch, model: KSR, does not have a potential igniting source of its own as a mechanical operating resource; it does not get any
identification according to the guideline 94/9/EC ("ATEX 100a”).
The mounted contact can be used in intrinsically safe circuits as a “simple apparatus” according to EN 60079-14. The following limit values for the switching contact should not be exceeded: U = 30 VUC, I = 100 mA, P = 1,2 W.
The measurement units can be used as follows: a) In the Zone 2 (Gas-Ex, Cat. 3G) in explosion group of IIA, IIB and IIC b) In the Zone 22 (Dust-Ex, Category 3D) with non-conductive dusts with a
minimum igniting energy of > 3 mJ c) In the Zone 1 (Gas-Ex, Cat. 2G) into explosion group of IIA, IIB and IIC d) In the Zone 21 (Dust-Ex, Category 2D) with non-conductive dusts with a
minimum igniting energy of > 3 mJ
Page 4 SVN/KSR K01/0413
Page 5
SVN/KSR
6.2. Electrical Contact
The Low-Volume Flow Switch, model: KSR, can be used in the Ex-area according to category 2G, 2D Cluster II, in Zone 1 and 21, in zone 1 and 21 in connection with a switching amplifier for protection type Ex II (2)GD [EEx ia] IIC (intrinsically safe)
The electrical connection is explained in the section 8 Electrical Connection.
6.3. Potential Equalisation
The Low-Volume Flow Switches, model: KSR, have to be incorporated in the potential equalisation system of the system. This is done by the connection tube made of metal.
7. Mechanical Connection
Before installation:
Remove all packing materials and transport retainers and ensure that no such materials remain in the device.
Make sure that the maximum operating pressure and temperature of the device are not exceeded (see 10 Technical Information).
Install the flow switch in the piping system, ensuring that the piping is rigidly supported at the inlet and outlet of the switch with pipe clamps
Ensure that the piping is aligned with the inlet and outlet fittings and the no piping induced stresses are exerted in the switch. This stress can result in damage to the switch during system operation
Protect the measuring tube from external damage.
Avoid pressure surges in the measuring tube, such as those arising from fast
start up/shut off of flow or pulsating flow.
If possible, after completing the mechanical installation, check the threaded connection between the device and the piping for leakage immediately.
For complete information on the proper installation of float-type flow meters, see VDI/VDE Directive 3513.
SVN/KSR K01/0413 Page 5
Page 6
SVN/KSR
8. Electrical Connection
Make sure that the electrical supply lines are de-energized when connecting the device!
Connect the power supply line to the device connection as shown in the illustration below.
8.1. SVN-1200 (Namur)
Supply/
UB = 7.7 – 9 VDC , 2-wire
Attention! The electrical values specified for the proximity switch must not be exceeded.
8.2. SVN-1201 (Proximity Switch)
UB = 10 – 30 VDC , 3-wire Output: NPN, N/O contact
Attention! The electrical values specified for the proximity switch must not be exceeded.
Page 6 SVN/KSR K01/0413
Page 7
SVN/KSR
8.3. KSR with Reed Contact
SPST contact
SPDT contact
Attention! The electrical values specified for the contact must not be exceeded, even for a short time. For higher switching capacities, we recommend installation of our contact protection relay (such as model MSR) or other contact protection measures.
After connection of all necessary external devices to the limit contact, the device is completely set up and can now be placed in operation.
SVN/KSR K01/0413 Page 7
Page 8
SVN/KSR
9. Maintenance
If the medium to be measured is not dirty, SVN/KSR Flow Monitors are essentially maintenance-free. However, any lime or dirt deposits on the housing or the internal parts should be removed regularly.
To clean the flow monitor, proceed as follows:
Make sure that the electrical supply lines are de-energized.
Unscrew the flow monitor from the line.
To disassemble the flow monitor, remove the stud screws.
Clean the flow monitor in a cleaning bath or in an ultrasonic bath.
When reassembling the flow monitor, be sure that the gaskets are seated
properly.
10. Technical Information
Switching ranges (permanently set) Water : 2 – 250 cm3/min (model SVN) 2 – 160 cm³/min (model KSR) Air: 50 – 6000 Ncm³/min at 1013 mbar; 20 °C
Technical Details
Connection: G 1/4 female (1/4 NPT optional) Protection: IP 67 Max. pressure: 16 bar Max. temperature: 70 °C Materials (media contacting): St. steel 1.4305; borosilicate glass Gasket: FPM
Average electrical switch contact life (MTTF):
at max. electrical load: 105 switching operations at half load (<10%max. load): 5*107 switching operations at low load (<10V/<1mA): 108 switching operations
Page 8 SVN/KSR K01/0413
Page 9
SVN/KSR
11. Order Codes
Order Details (Example: SVN-1200 W R08; 100 cm³/min decreasing flow rate)
Order number Limit switch Medium
SVN-1200
SVN-1201
KSR-1200
KSR-1201
*We recommend our transistor relay for the Namur switch: for example model REL-6000 (230 V
Switch Namur*
7.7 - 9 V Switch DC voltage 10 - 35 V 3-wire, NPN, N/O contact Reed contact N/O contact 24 V / 0.1 A / 1 Watt Reed contact changeover cont. 100 V / 0.5 A / 5 Watt / VA
2 - wire
DC,
DC
, 1 changeover contact, 4 A/ 500 VA)
DC
,
W = Water L = Air
12. Dimensions
Connection
(female)
R08 = G 1/4 N08 = 1/4 NPT
(please specify in writing)
For example: 100 cm³/min. decreasing flow rate
Set point
SVN/KSR K01/0413 Page 9
Page 10
SVN/KSR
13. Declaration of Conformance
We, KOBOLD Messring GmbH, Hofheim-Ts, Germany, declare under our sole
responsibility that the product:
Low-Volume Flow Monitor Model: SVN-1201
to which this declaration relates is in conformity with the standards noted below:
DIN EN 50081-1 03/1993
Electromagnetic compatibility (EMC) - Basic specification: Interference emission
DIN EN 50082-2 04/1995
Electromagnetic compatibility (EMC) - Basic specification: Noise immunity
DIN EN 61010-1 01/2001
Safety requirements for electrical measuring, control and laboratory instruments
Also in conformance with the specifications in the following EEC directives:
2004/108/EC EMC Directive
Hofheim, 10. March 2007 H. Peters M. Wenzel General Manager Proxy Holder
Page 10 SVN/KSR K01/0413
Page 11
SVN/KSR
We, KOBOLD Messring GmbH, Hofheim-Ts, Germany, declare under our sole
responsibility that the product:
Low-Volume Flow Monitor Model: KSR-...
to which this declaration relates is in conformity with the standards noted below:
DIN EN 61000-4-4 04/1995
Electromagnetic compatibility (EMC) BURST
DIN EN 61010 01/2001
Safety requirements for electrical measuring, control and laboratory instruments
Also in conformance with the specifications in the following EEC directives:
2006/95/EC Low Voltage Directive
Hofheim, 10. March 2007 H. Peters M. Wenzel General Manager Proxy Holder
SVN/KSR K01/0413 Page 11