Series KP46
Explosion-Proof
Pressure Transducers
Precautions
User's Responsibility for Safety:
•
wide range of process sensors and technologies. While each
of these technologies are designed to operate in a wide
variety of applications, it is the user's responsibility to select a
technology that is appropriate for the application, to install it
properly, to perform tests of the installed system, and to
maintain all components. The failure to do so could result in
property damage or serious injury.
Wiring and Electrical:
•
operated device, only properly trained personnel should install
and maintain this product. Be sure that the power supplied to
the unit is appropriate for the electronics version supplied.
Electrical wiring of the sensor
accordance with all applicable national, state and local codes
AND
in accordance with the most recent version of the
National Electric Code ANSI/NFPA 70 (NEC) Articles 500
thorough 505.
Because this is an electrically
KOBOLD manufactures a
MUST
be performed in
Specifications:
Available Ranges: 0-50 through 0-20000 PSIG
Over Range Protection: 2X full scale
Burst Pressure: 5X full scale
Cycle Life: >100 million cycles
Process Connection: ¼” MNPT (to 10K PSIG),
½” MNPT (15K & 20K PSIG)
Wetted Materials: 316 L Stainless Steel
others available upon request
Corrosion Resistance: Complies with NACE MR0175
Linearity: ±0.25% BFSL
Zero Offset: <±1% of full scale
Span Tolerance: <±2% of full scale
Media Temp Range: -55 to +250°F
Ambient Temp Range: -40-185°F
Compensated Range: 30 to 130°F
Temp. Drift: <±1.5% of full scale for zero
and span over the compensated range
Shock Resistance:100G, 11mSec.
Vibration Resistance: 10G peak, 20-2000Hz
Stability (1 year): ±0.25% of full scale
Electrical Specifications:
Output: 4-20 mA, 2-wire
Input Power Supply: 10-28 VDC
Max. Loop Load: 800 Ohms
Elec. Connection: ½” NPT Conduit with 6 Ft. 18 AWG wire leads
Elec. Protection: NEMA 4X / IP 66
Make a Fail-Safe System:
•
that accommodates the possibility of sensor, relay or
power failure. In critical applications, KOBOLD
recommends the use of redundant backup systems and
alarms in addition to the primary system.
Hazardous Location Approval:
•
standards CSA 30 and U.L. 1203, Explosion-Proof for
Class 1, Div 1 Groups A, B, C, D and Div. 2 Groups A,
B, C, D for use in Hazardous Areas
• - ANSI/ISA 12.27.01-2003 Single
Seal Approved
• - CE EN61326 as per CECV,
Canadian Electrical Code
Variance
Design a fail-safe system
CSA approved to
Wiring Connections:
CAUTION: BE SURE THAT POWER IS DISCONNECTED
BEFORE PROCEEDING!
4-20 mA, 2-wire Output
Red: +V Supply (10-28VDC)
Black: + Signal Output (4-20mA)
Green: Case/Equipment Ground
Installation:
1. Mount the transmitter so that the sensor port will not
become clogged with sediment or debris that could
hamper the sensing ability.
2. Although the transmitter is highly vibration resistant, it is
always good practice to mount the device appropriately to
minimize any potentially damaging shock and vibration.
3. Apply PTFE tape, or other appropriate thread sealant to
the NPT pressure fitting thread before installation. Tighten
the device using the 7/8” Hex next to the pressure
connection. DO NOT USE A PIPE WRENCH ON THE
TRANSMITTER HOUSING!
FM Rev. 05/10/13
KP46_manual_5-13
KOBOLD Instruments, Inc.
Standard Electrical Connections For Model KPD and KP46
Cable
mV
Supply Voltage 5VDC typ., 10VDC max. 5VDC ± 0.01V 10-28VDC 15-28VDC 10-28VDC
Output Load >1 MΩ >10 KΩ >10 KΩ >10 KΩ 0-800Ω
Operating Temperature -40 to 105ºC -40 to 85ºC -40 to 85ºC -40 to 85ºC -40 to 85ºC
Cable / Hookup
Wire Connections
Electrical Connection option
Gauge Wire 24 AWG 24 AWG 18 AWG
Available on KOBOLD Models:
Cable / Hookup
Wire Connections
Output Type Green Black Red
mV & 4-Wire Voltage +S Ground +V -S +S Ground +V -S N/A N/A N/A N/A
3 Wire Voltage N/C Ground +V S N/C Ground +V S Case Ground +V S
4-20 mA N/C Ground +V N/C N/C Ground +V N/C Case Ground +V N/C
0.5-4.5V ratiometric 1-5V, 1-6V, 0-5V 0-10V, 1-10V
Standard Cable Conduit with Cable Explosionproof Conduit with Cable
‘”A, B, C, D” “L, M, N, P” “T, U, W”
KPD
Standard Cable Conduit with Cable Explosionproof Conduit with Cable
White Green Black Red White Green Black Red White
Voltage
KPD
4-20mA
KP46
S= Output Signal
V= Voltage Supply
N/C= Not Connected
Case= Case Ground
2/09/18/13 www.koboldusa.com