Kobold KAL-L Operating Manual

KOBOLD KAL-L (KAL-8000 Series)
Thermal Air Flow Switch
User Instructions
KOBOLD Instruments Inc. 1801 Parkway View Drive Pittsburgh PA 15205
Phone (412) 788-2830 • Fax (412)-788-4890
Manual-KAL-L_5-12
Table Of Contents
1.0 General .......................................................................................................1
2.0 Specifications..............................................................................................1
3.0 Mechanical Installation................................................................................3
3.1 Installation General ..........................................................................3
3.2 Installation of Units with NPT Thread Connection............................5
3.3 Installation of Units with HVAC Flange Connection..........................5
4.0 Electrical Connections ................................................................................5
5.0 Operation ....................................................................................................6
5.1 Flow Setpoint Adjustment ................................................................ 6
5.2 Adjustment of the Start-up Time Delay ............................................8
6.0 Maintenance ............................................................................................... 9
7.0 Need Help with Your KAL-L Flow Switch? ..................................................9
List of Diagrams
Diagram 2.1: Dimensions............................................................................2
Diagram 3.1: General Installation ............................................................... 4
Diagram 3.2: Required Straight Pipe Runs.................................................4
Diagram 4.1: Electrical Connections...........................................................5
Diagram 5.1: Interior Controls Layout for the KAL-L...................................6
List of Tables
Table 2.1: Model Number Codes ........................................................... 3
FM Rev. 5/17/12
CAUTION: For safety reasons, please read the cautionary information located at
the end of the manual, before attempting installation.
1.0 General
The KAL-L (KAL-8000 Series) Thermal Air Flow Switch uses the proven calorimetric principle to monitor the flow of air or non-hazardous gases. A sensing resistive thermal device (RTD) is heated to a few degrees above the temperature of the flow medium. As the medium flows across the sensing RTD it cools the RTD. The rate of cooling is proportional to flowrate. A second RTD measures medium temperature and the KAL-L electronics uses this measurement to compensate for changes in medium temperatures thus preventing false readings due to medium temperature transients. If the measured flow value drops below the setpoint value, an output relay is activated providing an alarm or control input.
2.0 Specifications
Switching Range: 3.3 to 66 feet/second @ 68°F/14.5 PSIA
Restricted span for other pressure and temperature conditions
Accuracy: ±10% of flow rate
Repeatability: ±1% of flow rate
Display
Flowrate: 8 LED trend indicator Switchpoint: Flashing LED in trend indicator Switch Status: Dual colored LED
RED = Flow below switchpoint
GREEN = Flow above switchpoint Max. Temperature Gradient: 30°K(°C)/Min. @ 25 feet/sec and 190°F Response Time: Adjustable 1 to 60 seconds Warm-up Time: 30 seconds Max. Pressure: 120 PSIG Temperature Range
Process: -10 to +250°F Ambient: +15 to +140°F
Wetted Parts: Ni-Plated brass
Housing: Polyamide
Electrical Data
Power Requirements: 24 VDC/VAC +10%/-15% Switch Characteristics: 1-SPDT relay Max. 250 VAC/4 A/1000
VA
Electrical Connection
Standard: Cable gland Optional: 1/2” NPT Conduit or M-12 plug
Protection: NEMA 4/IP 65
FM Rev. 5/17/12
KAL-L 2
Diagram 2.1 Dimensions
7.0
4.0
φ15.5mm
Hex 41mm
4.3
HVAC Duct Mount
Flange
PG 13.5
Cable Gland
1/2” NPT
Compression Fitting
FM Rev. 5/17/12
All dimensions in inches
Unless otherwise noted