Kobold DVZ series Operating Instructions Manual

Page 1
Operating Instructions
for
Compact Vortex Flow Meter
Model: DVZ
Page 2
page 2 DVZ K04/0810
1. Contents
1. Contents ........................................................................................................ 2
2. Note .............................................................................................................. 3
3. Instrument Inspection .................................................................................... 3
4. Regulation Use .............................................................................................. 3
5. Operating Principle ........................................................................................ 4
6. Mechanical Connection ................................................................................. 4
6.1 Check operating conditions: ................................................................. 4
6.2 Installation ............................................................................................ 4
7. Electrical Connection .................................................................................... 5
7.1 General ................................................................................................ 5
7.2 DVZ-...S300 ......................................................................................... 6
7.3 DVZ-...S30D ........................................................................................ 6
7.4 DVZ-...F300; DVZ-...L3x3 .................................................................... 6
7.5 DVZ-...L443 ......................................................................................... 7
7.6 DVZ-...C30 ........................................................................................... 7
7.7 DVZ-...C34 ........................................................................................... 7
7.8 DVZ-...Ex4R, DVZ-...Gx4R .................................................................. 8
8. Operation ...................................................................................................... 9
8.1 Switch point setting DVZ-...S300, DVZ-…S30D .................................. 9
8.2 Counter electronics DVZ-…Ex4R ........................................................ 9
8.3 Dosing electronics DVZ-…Gx4R ......................................................... 9
9. Adjustments – Compact Electronic DVZ-...C3.. .......................................... 10
9.1 Button function ................................................................................... 10
9.2 Settings .............................................................................................. 10
9.3 Value setting ...................................................................................... 11
9.4 Set-up mode ...................................................................................... 12
9.5 Main menu items ............................................................................... 14
10. Maintenance ............................................................................................... 16
11. Technical Information .................................................................................. 17
12. Order Codes ............................................................................................... 20
13. Dimensions ................................................................................................. 22
13.1 Dimensions - Sensor.......................................................................... 22
13.2 Dimensions - Electronics ................................................................... 28
14. Declaration of Conformance ....................................................................... 31
Manufactured and sold by:
Kobold Messring GmbH
Nordring 22-24
D-65719 Hofheim
Tel.: +49(0)6192-2990
Fax: +49(0)6192-23398
E-Mail: info.de@kobold.com
Internet: www.kobold.com
Page 3
DVZ
DVZ K04/0810 page 3
2. Note
Please read these operating instructions before unpacking and putting the unit into operation. Follow the instructions precisely as described herein. The devices are only to be used, maintained and serviced by persons familiar with these operating instructions and in accordance with local regulations applying to Health & Safety and prevention of accidents.
When used in machines, the measuring unit should be used only when the machines fulfil the EWG-machine guidelines.
as per PED 97/23/EG
In acc. with Article 3 Paragraph (3), "Sound Engineering Practice", of the PED 97/23/EC no CE mark. Diagram 8, Pipelines, Group 1, dangerous fluids
3. Instrument Inspection
Instruments are inspected before shipping and sent out in perfect condition. Should damage to a device be visible, we recommend a thorough inspection of the delivery packaging. In case of damage, please inform your parcel service / forwarding agent immediately, since they are responsible for damages during transit.
Scope of delivery:
The standard delivery includes:
Compact Vortex Flow Meter model: DVZ
Operating Instructions
4. Regulation Use
Any use of the Compact Vortex flow meter, model: DVZ, which exceeds the manufacturer’s specifications, may invalidate its warranty. Therefore, any resulting damage is not the responsibility of the manufacturer. The user assumes all risk for such usage.
Page 4
page 4 DVZ K04/0810
5. Operating Principle
The compact KOBOLD Vortex flow meter, model DVZ, is used for measuring and monitoring smaller and medium-sized flow of low viscosity, water-like fluids in pipes. The device works using the vortex process, making it virtually maintenance-free. This involves the installation of a sharp-edged object (the vortex generator) in the flow duct. A vortex is created behind the object whose frequency is proportional to the flow velocity of the fluid. The flow volume can be determined with a very great degree of accuracy by measuring the vortex frequency. This achieves a very high linearity across the whole measuring range. The device can be fitted with switching, frequency or analogue outputs. There is also an optional compact electronics package that includes a digital display, and both a switching and analogue output.
6. Mechanical Connection
6.1 Check operating conditions:
Flow rate
max. operating pressure
max. operating temperature
6.2 Installation
Remove all packing materials and transport retainers and ensure that no such materials remain in the device.
Install with flow in direction of arrow (universal mounting)
Avoid pressure and radial tension
Fasten the pipe at up stream and down
stream at a distance of 50 mm from the connections
Attention! Retransfer the unit on the metal bolting (not on the plastic housing!) Mount switches using the proper tightening torque according the following table!
Page 5
DVZ
DVZ K04/0810 page 5
Nominal size of
threads
Proper tightening torque
3/8” 22 bis 24 Nm 1/2” 28 bis 30 Nm 3/4” 28 bis 30 Nm
1” 36 bis 38 Nm
Note! The switch may be damaged if it is tightened above the tightening torque range. Also, if it is tightened below the tightening torque range, the connecting thread section may loosen.
Ensure inlet section of 10xDN and outlet section of 10xDN
Avoid valves or large reduction on the inlet section (this increases the
inaccuracy of measurements)
Check the seals of the connections
Attention! When used with an open output side, there is a danger of cavitation.
7. Electrical Connection
7.1 General
Attention! Make sure that the voltage values of your system correspond with the voltage values of the measuring unit.
Make sure that the supply wires are de-energised.
Connect the supply voltage and the output signal to the plug PIN’s as stated
below.
We recommend the use of wires with cross sectional area of min. 0,25 mm².
Page 6
page 6 DVZ K04/0810
7.2 DVZ-...S300
7.3 DVZ-...S30D
1
2
3
4
Output N/C
Output
N/O
+Vs
GND
7.4 DVZ-...F300; DVZ-...L3x3
Connection example DVZ-...L3x3
1
2
3
4
+Vs
Signal Out
n.c.
GND
1
2
3
4
+Vs
Signal Out
n.c.
GND
+Vs
GND
1
2
3
4
5
Output N/O
Output
Common
Output
N/C
+Vs
GND
Page 7
DVZ
DVZ K04/0810 page 7
7.5 DVZ-...L443
7.6 DVZ-...C30
7.7 DVZ-...C34
1
2
3
4
5
Switch Out 2
Switch
Out 1
+Vs
GND
GND
+Vs
Signal Out
+Vs
GND
GND
1
2
3
4
5
+Vs
GND
GND
Switch out
1
0(4)-20 mA
Page 8
page 8 DVZ K04/0810
7.8 DVZ-...Ex4R, DVZ-...Gx4R
Cable connection
Wire number
DVZ-...E14R Counter electronics
DVZ-...G14R Dosing electronics
1 +24 VDC +24 VDC 2 GND GND 3 4-20 mA 4-20 mA 4 GND GND 5 n. c. control 2* 6 reset part quantity control 1* 7 relay S1
normally open
relay S1 normally open
8 9 relay S2
normally open
relay S2 normally open
10 *Start-dosing: Control 1 connect with GND Stop-dosing: Control 2 connect with GND Reset-dosing: Control 1 and Control 2 at the same time with GND
Do not connect any external voltage to the control units!
Plug connection
-E34 R
+ Vs
Reset TM
0 (4) - 20 mA
GND
1
30 V / 2 A
AC/DC
34
5
1
3
4
5
6
S 2
8
d.c. *)
Output
d.c.*) Don't connect!
Page 9
DVZ
DVZ K04/0810 page 9
8. Operation
The units are preset and after electrical connection ready for operation.
8.1 Switch point setting DVZ-...S300, DVZ-…S30D
Switch setting Switch point
0 switch function deactivated 1 start of measuring range 2 20% of f.s. 3 30% of f.s. 4 40% of f.s. 5 50% of f.s. 6 60% of f.s. 7 70% of f.s. 8 80% of f.s. 9 90% of f.s.
Flow above switch point: DUO-LED green Flow below switch point: DUO-LED red Measuring range overflow: DUO-LED orange flashing
8.2 Counter electronics DVZ-…Ex4R
Operating please see Operating Instructions ZED-Z
8.3 Dosing electronics DVZ-…Gx4R
Operating please see Operating Instructions ZED-D
Page 10
page 10 DVZ K04/0810
9. Adjustments – Compact Electronic DVZ-...C3..
Connect the compact electronic according to previous connection diagram. After power on, the measuring range (end current) will be shown for 3 seconds.
9.1 Button function
In the normal mode (measuring mode)
In the set-up mode
9.2 Settings
The following values can be changed at the temperature transmitter:
Scale range Factory setting
Switch point (SPo, SP1, SP2)
0...999 0,00
Hysteresis (HYS)
-199...0 -0,00
Window point (duo point) (duo)
Switch point ...999 --- (inactive) contact-type (Con, Co1, Co2) N/O, N/C or Frequency (Fr)** N/O Start current (S-C)*
000...999 000
End current (E-C)*
000...999 f.s.
Start current selection (SCS)
0-- (0 mA), 4-- (4 mA) 4 mA Change Code (CCo)
000...999 000
* Start- and end value of flow relating to 0/4-20 mA. ** not calibrated, frequency at f.s. approx. 500 -600Hz
: Press 3 sec. Setup mode
: Switch point/Window point
: Next Step
: Change Value
3 sec
Standard mode
Any time
or do not press
a button for 20 sec
Page 11
DVZ
DVZ K04/0810 page 11
9.3 Value setting
From the main menu item (for example: switch point, "SPo"), press the "" button to set the value. The flow chart below illustrates the universal routine for changing individual parameters.
[From the main menu item]
1. Adjust position
2. Adjust position
3. Adjust position
Adjust decimal point
Save selected value or enter new value.
[To the next main menu item]
save
Page 12
page 12 DVZ K04/0810
9.4 Set-up mode
Compact electronic DVZ-...C30..
Contact 2 function
N/O N/C
Save
Code entering
Value setting
Contact 1 function
N/C
Frequency
Save
Hysteresis
Value setting
Switching point 2
Value setting
Switching point 1
Value setting
Code=
3 sec
Code entering
Value setting
Page 13
DVZ
DVZ K04/0810 page 13
Compact electronic DVZ-...C34
Contact function
N/O
N/C
Frequency
Save
Code entering
Window point
Hysteresis
Switching point
3 sec
Code=
End current
Start current
7sec
7sec
Value setting
Value setting
Value setting
Value setting
Value setting
Value setting
Page 14
page 14 DVZ K04/0810
9.5 Main menu items
9.5.1 Switching point
The switching point is entered in the menu item "Spo, SP1, SP2". A setting value between 000 and 999 can be selected. This value can also include a decimal point. The decimal point can be set at two points (e.g. 10.0 or 1.00). If the display value exceeds the set switch point, the electronic is activated and is signalised by a lightning LED. If the hysteresis is equal to zero and the window point is de-activated, the electronic switches back whenever the indicated value falls below the switching point.
9.5.2 Hysteresis
After the setting of the switching point, the hysteresis can be entered as a negative value in the "
HYS" menu. The standard hysteresis value is zero. In
operation condition this can lead to ambiguous switching behaviour, if the reading fluctuates around the switching point or window point. In this case, increasing the hysteresis can put things right. The hysteresis relates to the switching point and the window point (switching point minus hysteresis; window point plus hysteresis).
Example: Switching point 100 l/min; Hysteresis: -2.5 l/min
The electronic switches when 100 l/min is exceeded and switches back when the reading drops below 97.5 l/min.
9.5.3 Window point (duo-point)
As well as the switching point, it is also to define a "duo" (duo-point), the window point. This must be higher than the switching point. By using the window point and the switching point it is possible to monitor the measurement value in a certain range. The switching point limits the measurement range to smaller values and the window point to larger values.
Changing code
Value setting
Storing
7sec
4-20
mA
0-20
mA
Analog output
choosing
Page 15
DVZ
DVZ K04/0810 page 15
If the window point (duo-point) is less than or equal to the switching point, an error report (Er4) will be indicated on the display and its value is deleted and its function is invalid (in the case that the window point and switching point out of adjustment).
The value is set in the same way as the switching point. The window point is needed for process, in which monitoring of a certain temperature range is necessary.
Example: Switching point: 100 L/min; window point: 150 L/min;
hysteresis: -1 L/min The electronic switches when 100 l/min is exceeded. If the switching value remains between 99 L/min (100-1) and 151 L/min (150+1), the contact will also remain in active switching condition (LED on). If it exceeds 151 l/min or is below 99 l/min the electronic switches back.
Switching behaviour
The following diagram clarifies the switching behaviour of the electronic switch. The contact closes (contact type: no) when it drops below the switching point or the window point. It only opens again if the window point plus hysteresis is exceeded or if it drops below the switching point minus hysteresis. An LED indicates the switching condition of the switching point.
Time / t
Display bar (°C)
Hysteresis
LED on
Time / t
Display bar (°C)
Switchpoint
Hysteresis
LED on
Hysteresis
Window point
LED on
Page 16
page 16 DVZ K04/0810
9.5.4 Contact type
The function of the transistor switching output is set in menu item "Con, Co1 or
Co2
". The switching function switches from
no - N/O contact to nc - N/C to Fr – frequency (only Con and Co1) and back.
N/O contact: contact closes when switching point is exceeded N/C contact: contact opens when switching point is exceeded Frequency: frequency output synchronised with the vane frequency
9.5.5 Current output
The current output is selected in menu items "S-C" Start current indicated value < > 0(4) mA "E-C" End current indicated value < > 20 mA "SCS" Start current selection (0-20 mA or 4-20 mA). The indicated value at which 0(4) mA flow is entered in menu item Start current. The indicated value at which 20 mA flow is entered in menu item End current.
9.5.6 Change Code
The change code option "CCo" secures the unit against unauthorised tampering. If the code is different from 000, the user must input the code immediately after entering the adjustment mode.
10. Maintenance
The measurement device requires no maintenance if the measurement medium does not cause deposits or include fibre parts, which wrap around the sensor or the gate. In order to avoid problems, we recommend the installation of a filter, such as the magnetic filter, type MFR. If it is necessary to clean the sensor, the sensor can be rinsed with a suitable liquid. Fiber parts or large particles can be carefully removed with tweezers, etc.
Ensure that the sensor is not damaged.
Work on the electronics can only be performed by the factory, or the warranty is otherwise voided.
Page 17
DVZ
DVZ K04/0810 page 17
11. Technical Information
Measurement process: Vortex principle Mounting position: any, flow in direction of arrow Response time: 1 s Accuracy: ±2.5% of f.s. Repeat accuracy: ±1% of f.s. Inlet / outlet runs: 10xDN Protection: IP 65 Media temperature: 0...80 °C Ambient temperature: -10...+60 °C
Max. Pressure
Connection fixed rotatable Standard version 10 bar 20 bar Reinforced version 20 bar -
Pressure loss
Model Upper range value Pressure loss
DVZ-**04 4,5 L/min 420 mbar DVZ-**07 6,5 L/min 650 mbar DVZ-**10 10,0 L/min 780 mbar DVZ-**16 16,0 L/min 600 mbar DVZ-**22 22,0 L/min 450 mbar DVZ-**32 32,0 L/min 370 mbar DVZ-**40 40,0 L/min 450 mbar DVZ-**50 50,0 L/min 400 mbar DVZ-**63 63,0 L/min 380 mbar DVZ-**80 80,0 L/min 400 mbar DVZ-**99 100,0 L/min 350 mbar
Weight - Sensor
Measuring range Size Connection fixed
Connection
strengthened
Connection
rotatable
bis 32 L/min ¼", 3/8", ½" approx. 450 g approx. 600 g approx. 800 g
bis 32 L/min ¾" approx. 600 g approx. 600 g approx. 900 g
bis 32 L/min 1" approx. 1050 g approx. 950 g approx. 950 g
40...100 L/min ¾" approx. 1050 g approx. 1300 g approx. 1350 g
40...100 L/min 1" approx. 900 g approx. 1150 g approx. 1400 g
Weight - Electronics
Model Weight
DVZ-...F3x0 DVZ-...S30x DVZ-...Lxx3
approx. 80 g
DVZ-...C3xx approx. 300 g DVZ-...Exxx DVZ-...Gxxx
approx. 250 g
Total weight = weight sensor + weight electronics
Page 18
page 18 DVZ K04/0810
Wetted parts
Sensor housing: PPS, fibreglass-reinforced Sensor: PVDF Connections: brass (from 32 L/min nickel plated from 40 L/min blank) or stainless steel 1.4404 Bluff body: PPS, fibreglass-reinforced or oxide ceramic (non-wear version) Seal: NBR, EPDM or FPM
DVZ-...S300, DVZ-…S30D
Display: duo-LED for switching condition and when range limit is exceeded Switching output: relay changeover, max. 1 A/30 V
DC
or active 24 VDC, N/C / N/O Switch point: measuring range beginning from 90% f.s. in 10%-steps
can be configured by the customer using a rotary switch
Power supply: 24 V
DC
± 20%
Power consumption: 12 mA Electrical connection: plug M12x1.5 pole Measuring range overflow: flash of the DUO-LED (red/green) from 105 % of f.s.
DVZ-...F300, DVZ-…F390
Impulse output: PNP, Open Collector, max. 200 mA Frequency at f.s. 500 Hz (…F300) 50…1000 Hz (F390) Power supply: 24 VDC ± 20% Power consumption: 5 mA Electrical connection: plug M12x1 Measuring range overflow: F
out
approx. 2 kHz from 105 % of f.s.
DVZ-...L303; DVZ-...L343
Output: 0(4)-20 mA, 3-wire Max. load: 500 Power supply: 24 VDC ± 20% Electrical connection: plug M12x1 Measuring range overflow: I
out
approx. 20,5 mA from 103 % of f.s.
DVZ-...L443 (usage with AUF-3000)
Output: 4-20 mA, 3-wire Max. load: 500 Power supply: 24 VDC ± 20% Electrical connection: plug DIN 43650 Measuring range overflow: I
out
approx. 20,5 mA from 103 % of f.s.
Page 19
DVZ
DVZ K04/0810 page 19
DVZ-...C3 (Compact electronics)*
Display: 3-digit LED Analogue output: (0)4...20 mA adjustable, max. 500 (only DVZ-…C34*) Switching output: 1 or 2 Open Collector PNP or NPN, set at factory, max. 300 mA Contact function: N/C, N/O, frequency, programmable
(frequency output not calibrated, frequency at
f.s. approx. 500 -600Hz) Programming: with 2 keys Power supply: 24 VDC ± 20%, 3-wire Power consumption: approx. 100 mA Electrical connection: plug M12x1 Measuring range overflow: display “OF” from 105% of f.s.
DVZ-...Exxx (Counter electronics)*
Display: LCD, 2x8 digit, illuminated total, part and flow quantities, units selectable Quantity meter: 8-digit Analogue output: (0)4...20 mA adjustable Load: max. 500 Switching output: 2 relays, max. 30 V
AC/DC
/ 2 A / 60 VA Settings: via 4 buttons Functions: reset, MIN/MAX memory, flow monitor, monitoring for part and total quantity, language Power supply: 24 VDC ±20 %, 3-wire Power consumption: approx. 150 mA Electrical connection: cable connection or M12-plug
DVZ-...Gxxx (Dosing electronics)*
Display: LCD, 2x8 digit, illuminated, dosing, total and flow quantity, units selectable Quantity meter: 8-digit Dosage: 5-digit Analogue output: (0)4...20 mA adjustable Load: max. 500 Switching output: 2 relays, max. 30 V
AC/DC
/ 2 A / 60 VA Settings: via 4 buttons Functions: dosing (relay S2), start, stop, reset, fine
dosing, correction amount, flow switch, total quantity, language Power supply: 24 VDC ±20 %, 3-wire Power consumption: approx. 150 mA Electrical connection: cable connection or M12-plug
*more technical details see data sheet ZED in the brochure Z2
Page 20
page 20 DVZ K04/0810
12. Order Codes
Fixed connection
Order details (Example: DVZ-1 1 04 G2 S300)
*Reinforced version only in combination with fixed connection **Please specify flow direction in the order
Storage body/
housing
Connection
material/seal
Measuring range
Connection
fixed
Electronics
DVZ-1.. =
PPS
DVZ-2.. = ceramic
DVZ-3..*= PPS/strengthened design
DVZ-4..*= ceramic/strengthe ned design
..1.. = brass/ NBR
..2.. = st. steel/ NBR
..4.. = brass/ EPDM
..5.. = st. steel/ EPDM
..7.. = brass/ FPM
..8.. = st. steel/ FPM
..04.. = 0.5 - 4.5 L/min ..07.. = 0.8 - 7.0 L/min ..10.. = 1.3 - 10.0 L/min
..G2.. = G 1/4 ..G3.. = G 3/8 ..G4.. = G 1/2 ..N2.. = 1/4 NPT ..N3.. = 3/8 NPT ..N4.. = 1/2 NPT
switching output ..S300 = relay, M12-plug ..S30D =active 24 VDC, M12-plug
frequency output ..F300 =M12-plug, 500 Hz ..F390 =M12-plug,
50…1000 Hz
analogue output ..L303 =M12-plug, 0-20 mA ..L343 =M12-plug, 4-20 mA ..L443 =DIN-plug, 4-20 mA
compact electronics** ..C30R =2xOpen Coll. PNP ..C30M =2xOpen Coll. NPN ..C34P =4-20 mA,
1xOpen Coll. PNP
..C34N =4-20 mA,
1xOpen Coll. NPN
counter electronics ..E14R =LCD, 0(4)-20 mA,
2xrelay, 1 m cable
..E34R =LCD, 0(4)-20 mA,
2xrelay, M12-plug
dosing electronics ..G14R =LCD, 0(4)-20 mA,
2xrelay, 1 m cable
..G34R =LCD, 0(4)-20 mA,
2xrelay, M12-plug
..16.. = 2.0 - 16.0 L/min
..G3.. = G 3/8 ..G4.. = G 1/2 ..G5.. = G 3/4 ..N3.. = 3/8 NPT ..N4..= 1/2 NPT ..N5.. = 3/4 NPT
..22.. = 3.2 - 22.0 L/min ..32.. = 4.0 - 32.0 L/min
..G4.. = G 1/2 ..G5.. = G 3/4 ..G6.. = G 1 ..N4.. = 1/2 NPT ..N5.. = 3/4 NPT ..N6.. = 1 NPT
..40.. = 4,0 - 40,0 L/min
..50.. = 5,0 - 50,0 L/min
..63.. = 6,3 - 63,0 L/min
..80.. = 8,0 - 80,0 L/min
..99.. = 10,0 - 100 L/min
..G5.. = G 3/4 ..G6.. = G 1 ..N5.. = 3/4 NPT ..N6.. = 1 NPT
Page 21
DVZ
DVZ K04/0810 page 21
Axial rotatable connection
*Please specify flow direction in the order
Storage body/
housing
Connection
material/
Seal
Measuring range
Connection
rotatable
Electronics
DVZ-1.. =
PPS
DVZ-2.. = ceramic
..1.. = brass/ NBR
..2.. = st. steel/ NBR
..4.. = brass/ EPDM
..5.. = st. steel/ EPDM
..7.. = brass/ FPM
..8.. = st. steel/ FPM
..04.. = 0.5 - 4.5 L/min ..07.. = 0.8 - 7.0 L/min ..10.. = 1.3 - 10.0 L/min
..B2.. = G 1/4 ..B3.. = G 3/8 ..B4.. = G 1/2 ..P2.. = 1/4 NPT ..P3.. = 3/8 NPT ..P4.. = 1/2 NPT
switching output ..S300 =relay, M12-plug ..S30D =active 24 VDC, M12-plug
frequency output ..F300 =M12-plug. 500 Hz ..F390 =M12-plug,
50…1000 Hz
analogue output ..L303 =M12-plug, 0-20 mA ..L343 =M12-plug, 4-20 mA ..L443 =DIN-plug, 4-20 mA
compact electronics* ..C30R =2xOpen Coll. PNP ..C30M=2xOpen Coll. NPN ..C34P =4-20 mA,
1xOpen Coll. PNP
..C34N =4-20 mA,
1xOpen Coll. NPN
counter electronics ..E14R =LCD, 0(4)-20 mA,
2xrelay, 1 m cable
..E34R =LCD, 0(4)-20 mA,
2xrelay, M12-plug
dosing electronics ..G14R =LCD, 0(4)-20 mA,
2xrelay, 1 m cable
..G34R =LCD, 0(4)-20 mA,
2xrelay, M12-plug
..16.. = 2.0 - 16.0 L/min
..B3.. = G 3/8 ..B4.. = G 1/2 ..B5.. = G 3/4 ..P3.. = 3/8 NPT ..P4..= 1/2 NPT ..P5.. = 3/4 NPT
..22.. = 3.2 - 22.0 L/min ..32.. = 4.0 - 32.0 L/min
..B4.. = G 1/2 ..B5.. = G 3/4 ..B6.. = G 1 ..P4.. = 1/2 NPT ..P5.. = 3/4 NPT ..P6.. = 1 NPT
..40.. = 4,0 - 40,0 L/min
..50.. = 5,0 - 50,0 L/min
..63.. = 6,3 - 63,0 L/min
..80.. = 8,0 - 80,0 L/min
..99.. = 10,0 - 100 L/min
..B5.. = G 3/4 ..B6.. = G 1 ..P5.. = 3/4 NPT ..P6.. = 1 NPT
Page 22
page 22 DVZ K04/0810
13. Dimensions
13.1 Dimensions - Sensor
DVZ-sensor with fixed connection, measuring range up to 32 L/min
Meas.
range
..04/..07/..10
..04/..07/
..10/..16
..04/..07/..10/
..16/..22/..32
..16/..22/..32 ..22/..32
D 1 1/4" 3/8" 1/2" 3/4" 1"
AF 35 35 35 34 -­L 1 100 100 106 120 128 L 2 -- -- -- 50 50 L 3 35 35 35 34 -­L 4 -- -- -- -- 46
for
AF
Page 23
DVZ
DVZ K04/0810 page 23
DVZ-sensor with fixed connection, measuring range from 40 L/min
A
F
o
Page 24
page 24 DVZ K04/0810
DVZ-sensor with strengthened connection, measuring range up to 32 L/min
Meas.
range
..04/..07/..10
..04/..07/
..10/..16
..04/..07/..10/
..16/..22/..32
..16/..22/..32 ..22/..32
D 1 1/4" 3/8" 1/2" 3/4" 1"
AF 34 34 34 34 -­L 1 100 100 106 120 128 L 4 34 34 34 34 46
for
AF
Page 25
DVZ
DVZ K04/0810 page 25
DVZ-sensor with strengthened connection, measuring range from 40 L/min
o
AF
Page 26
page 26 DVZ K04/0810
DVZ-Sensor with rotatable connection, measuring range up to 32 L/min
Meas. range
..04/..07/
..10
..04/..07/
..10/..16
..04/..07/ ..10/..16/
..22/..32
..16/..22/
..32
..22/..32
D 1 1/4" 3/8" 1/2" 3/4" 1" D 2 24 28 35 40 45
AF 19 24 30 36 41
o
Page 27
DVZ
DVZ K04/0810 page 27
DVZ-Sensor with rotatable connection, measuring range from 40 L/min
Meas.
range
..40/..50/ ..60/..80/
..99
..40/..50/ ..60/..80/
..99 D 1 3/4" 1" D 2 40 45
AF 36 41
AF
o
Page 28
page 28 DVZ K04/0810
13.2 Dimensions - Electronics
DVZ-...S30x, DVZ-...F3x0, DVZ-...L3x3
DVZ-...L443
Page 29
DVZ
DVZ K04/0810 page 29
DVZ-...C3xx
Page 30
page 30 DVZ K04/0810
DVZ-...Exxx, DVZ-...Gxxx
Page 31
DVZ
DVZ K04/0810 page 31
14. Declaration of Conformance
We, KOBOLD Messring GmbH, Hofheim-Ts, Germany, declare under our sole responsibility that the product:
Compact Vortex Flow Meter Model: DVZ
to which this declaration relates is in conformity with the standards noted below:
EN 61326/A1 2004-05
Electrical equipment for control and instrumentation technology and laboratory use – EMC-requirements (industrial area)
DIN EN 61010-1 1994-03
Safety requirements for electrical measuring-, control- and laboratory instruments.
EN 60529, DIN VDE 0470-1 1992-11
Protection type housing (IP-Code)
Also the following EEC guidelines are fulfilled:
2004/108/EC EMC Directive
Hofheim, 16. Jan. 2007 H. Peters M. Wenzel General Manager Proxy Holder
Loading...