Kobelco KNW Series, KNWA00 Instruction Manual

MODEL#: SERIAL#:
INSTRUCTION MANUAL
KOBELCO is the international trademark found on all products of KOBE STEEL, LTD.
MODEL:
KNWA00
RECORD OF CHANGE H
KIMA00H1 (0204)
SAFETY PRECAUTIONS
Safety notices, marked with this symbol, are used in this publication to emphasize that a hazardous condition exists that could cause personal injury and/or damage to the equipment.
1. Read and understand the contents of this manual before installing, operating or maintaining the compressor.
2. Electricity and compressed air are dangerous. When performing maintenance or service work, make absolutely sure the electrical supply is disconnected and locked out. The discharge air lines service valve (customer furnished) must be closed and the compressor relieved of all internal pressure. DO NOT rely on the discharge air line check valve.
3. Compressed air from this unit must not be used for breathing or food processing without adequate filtering and monitoring to meet OSHA 29 CFR 1910 or FDA 21 CFR 178.3570.
4. Do not allow flammable, toxic or corrosive gases to enter the air inlet system or electrical devices.
5. Never attempt to work on compressor or remove guards, panels, covers, shields, etc. while the compressor is in operation.
6. Periodically confirm that all safety and shutdown devices are operating properly.
7. Do not override any safety or shutdown device.
8. Make certain all associated pipe and equipment beyond this compressor is compatible with maximum pressures and temperatures to be encountered during normal and adverse operation. Do not use plastic pipe in the compressed air system.
9. Keep doors closed during normal operation. The noise level inside cabinet exceeds 90 decibels (dbA) and the operating temperature of some components is sufficient to burn the skin.
10. Never assume it is safe to work on the compressor because it is not operating. Many installations have automatic start/stop controls, and the compressor may start at any time.
TABLE OF CONTENTS
1. GENERAL DESCRIPTION................. 1 5.2 Programmable Logic
1.1 Compressor................................ 1 Controller.................................... 27
1.2 Compressed Air Flow................. 3 5.2.1 CPU................................. 27
1.3 Cooling Air Flow......................... 5 5.2.2 PLC Status LED’s............ 29
1.4 Oil Flow....................................... 5 5.2.3 PLC Inputs....................... 29
1.5 Capacity Control System............ 7 5.2.4 PLC Outputs.................... 29
1.5.1 Unloaded, Off...................7 5.2.5 PLC Analog Inputs........... 31
1.5.2 Loaded, Running............. 7 5.2.6 Expansion Module
1.5.3 Unloaded, Running.......... 7 Replacement....................31
1.6 Monitoring and Limiting 5.3 Motor Starter............................... 31
Devices....................................... 7
1.7 Alerts........................................... 9 6. MAINTENANCE.................................. 33
1.8 Shutdowns.................................. 9 6.1 Daily............................................ 33
6.2 Weekly........................................ 33
2. INSTALLATION...................................13 6.3 Monthly........................................33
2.1 Inspection....................................13 6.4 Yearly.......................................... 33
2.2 Handling...................................... 13 6.5 Two Year.....................................35
2.3 Foundation.................................. 13 6.6 Lubrication.................................. 35
2.4 Location...................................... 13 6.7 Filter Maintenance...................... 37
2.5 Cooling Air.................................. 13 6.7.1 Dust Filters.......................37
2.6 Air Discharge Piping................... 15 6.7.2 Inlet Air Filter....................37
2.7 Air Receiver................................ 15 6.7.3 Lube Oil Filter...................37
2.8 Wiring.......................................... 17 6.7.5 Sump Breather.................37
3. START UP............................................ 19 SERVICE PARTS LIST.......................38
3.1 Pre-Start Up Check....................... 19
3.2 Initial Start Up................................19
7. STANDBY and STORED UNITS........ 39
4. OPERATING INSTRUCTIONS............ 21 7.1 Stand-by Compressors............... 39
4.1 Starting the Compressor............... 21 7.2 Short Term Storage.................... 39
4.2 Stopping the Compressor............. 21 7.3 Long Term Storage.................... 39
4.2.1 Manual Stop.......................21
4.2.2 Automatic Stop.................. 23
4.3 Normal Operating Conditions........23 8. PROBLEM SOLVING......................... 40
Problem-Cause & Remedy
5. ELECTRICAL CONTROLS................. 25 Compressor................................ 40
5.1 Compressor Operator Panel PLC ............................................ 42
5.1.1 GT Terminal
Page Selection.................25 APPENDIX
5.1.2 Display Maintenance....... 27 A. Daily Operating Record ..................43
5.1.3 GT Terminal Options....... 27 B. Unit Dimensions .............................45
FIGURE 1 - KOBELCO KNW SERIES
MODEL A00 AIR COMPRESSOR
1. GENERAL DESCRIPTION
1.1 Compressor
The Kobelco KNW Series air compressor is a heavy duty, two-stage, rotary screw design that provides completely oil-free compressed air.
Oil-Free compressed air is guaranteed by a unique seal arrangement that separates the bearings and gear chambers from the compression section of each stage. The dual vent seal design insures that no oil or its vapor can contaminate air that is being compressed.
The two-stage design provides higher output pressures at a lower operating temperature than would be available from a single-stage design. Both compressor stages are mounted on a heavy duty cast iron gear case for permanent alignment. The stages are driven through precision machined gears, selected for optimum operating speed to maximize efficiency and reduce rotor thrust.
Timing gears are used to separate the rotors and to assist in reducing thrust on the rotors and the rotor bearings, thus extending bearing life.
The Kobelco KNW Series Oil-Free Air Compressor is a complete operating system. A flange-mounted permanently aligned drive motor, intercooler, aftercooler, capacity control valve assembly, lube oil system, compressor controls, and related accessories, are all mounted inside a sound attenuating steel cabinet. All compressor mounting points are vibration isolated. Flexible connections between the compressor assembly and the cabinet insure that no vibration, and its related noise, are transmitted to the cabinet. The result is a very stable and quiet running assembly.
The KNW Series compressor features a separately driven oil pump for drive gear, timing gear, and bearing lubrication. The lube oil pump starts first, then, after a brief delay, the compressor drive motor starts. Starting of the drive motor is delayed to allow pressurized lubrication of the bearings and gears during acceleration of the compressor. The pump is also timed to stop after the compressor. Oil pressure is maintained while the compressor coasts to a stop. Maximum component life is assured by thorough lubrication of moving components.
Another feature of the KNW Series is the direct operating capacity control valve and bleed-off system. This unique valve design provides for extended service intervals and eliminates the need for a bleed-off cooler.
The KNW Series Compressor Operator Panel is a state-of-the-art control system combining robust industrial controls with leading edge operator interface and programmable logic controller technology. Exclusive to KNW Series compressors is the GT Terminal, a versatile graphic touchscreen display with clear graphics and user-friendly operation, showing all necessary compressor information in an easy to understand format.
1
COOLING
AIR OUTLET
AFTERCOOLER
AIR INLET
COOLING AIR INLET
FIGURE 2 - COMPRESSED AIR FLOW DIAGRAM
COMPRESSOR
AIR INLET
COMPRESSED
AIR DISCHARGE
SUMP
OIL DRAIN
FIGURE 3 - BACK OF COMPRESSOR
2
CONDENSATE
DRAIN
1.2 Compressed Air Flow
(Figure 2)
Air to be compressed undergoes two stages of filtration before being compressed. The air enters the cabinet through an opening that is equipped with a dust filter. The air then passes through the air inlet silencer, a duct that is lined with a sound absorbing material. Then the air is drawn through a high efficiency air filter. Filtered air flows through a flex connector, into the capacity control valve, and then into the inlet of the compressor first stage.
The compressor first stage compresses the filtered air to approximately 37 PSIG. The compressed air is discharged into the air­cooled intercooler where it is cooled to approximately 115°F (46°C). The cooled, compressed air then passes through the moisture separator to remove any condensed moisture from the air stream before entering the compressor second stage.
The compressor second stage compresses interstage air to the system operating pressure as controlled by the pressure setting. The hot compressed air then passes through the system check valve and air-cooled aftercooler where it is cooled to within approximately 15°F (8°C) of the ambient air temperature. An ASME safety valve is downstream of the check valve. The compressed air exits the unit into a moisture separator, where condensed moisture is removed before the air enters the plant air system.
The compressed air circuit is monitored with the following discrete devices:
a. Inlet air filter service switch b. Discharge high air pressure switch c. Discharge air safety relief valve
The Programmable Logic Controller, PLC, (ref. Section 5.2) monitors the compressed air circuit for the following:
a. First stage discharge air temperature b. Interstage air pressure c. Second stage suction air temperature d. Second stage discharge air temperature e. Compressor discharge air pressure f. Compressor discharge air temperature
The air temperatures are displayed on the GT Terminal. The PLC continuously monitors for excessive heat, providing a warning if temperatures approach the recommended maximum and a shutdown if they reach the limit. The interstage pressure is monitored to provide load/unload indication and to confirm capacity control valve operation. The pressure at the compressor discharge is monitored to provide load and unload pressure control and a high pressure alarm.
3
AFTERCOOLER EXHAUST
AFTERCOOLER
AIR DUCT
AIR INLET
(REAR)
AIR DUCT
AIR
OUTLET
COOLING
FAN
OIL
COOLER
FIGURE 4 - COOLING AIR FLOW
INTERCOOLER
FIGURE 5 - LUBRICATION OIL FLOW DIAGRAM
4
1.3 Cooling Air Flow
(Figure 4)
A separate electric motor driven fan draws ambient air into the cabinet through screens in the back panel. The screens are equipped with dust filters. The air takes one of two flow paths. The first passes directly through to the aftercooler and exhausts through the top of the enclosure. In the second path, air enters near the motor, cools the compressor motor and passes into the compressor section of the cabinet. The air then goes through both the intercooler and oil cooler which are mounted side by side. The fan draws all the air through the exhaust chamber and out the top of the enclosure.
When the compressor unloads, hot air is discharged through the bleed-off silencer, pulled through the fan and exhausted. A temperature switch shuts down the compressor if the air temperature inside the cabinet exceeds 150°F (65°C).
1.4 Lubrication Oil Flow
(Figure 5)
Oil for bearing and gear lubrication is stored in a sump, in the lower section of the main gear case/compressor housing. A sight glass, located on the side of the oil sump, is used to monitor the oil level. Lube oil is drawn from the sump by a separate motor driven oil pump. An oil pump discharge relief valve is provided to maintain a constant pressure for component lubrication by relieving excessive pressure back to the suction of the pump.
Oil leaving the pump is cooled to approximately 28°F (15°C) above ambient air temperature in the oil cooler and is then filtered before entering an oil gallery on the rear of the compressor first stage. A portion of the lube oil passes through a tube to an oil gallery on the rear of the compressor second stage. Lube oil flows from the oil galleries to the front of each stage to lubricate and cool the front bearings and drive gears. Lube oil passes through internal passages from the galleries to lubricate the rear bearings and the timing gears. All lube oil drains back into the sump.
The lube oil circuit is monitored with the following discrete devices:
a. Sump oil level indicator. b. Lube oil filter differential switch.
The Programmable Logic Controller, PLC, (ref. Section 5.2) monitors the lubrication circuit for the following:
a. Lube oil pressure b. Lube oil temperature
The oil temperature is displayed on the GT Terminal. The PLC monitors the lube oil temperature. A warning is provided as the temperature approaches the recommended maximum operating temperature, and a shutdown if it reaches the limit. The lube oil pressure is monitored for alarm shutdown if the oil pressure is too low while the compressor is operating.
5
FIGURE 6 - UNLOADED, COMPRESSOR OFF
FIGURE 7 - LOADED, COMPRESSOR RUNNING
FIGURE 8 - UNLOADED, COMPRESSOR RUNNING
6
1.5 Capacity Control System
The capacity control system consists of an inlet capacity control valve with an integral bleed-off valve, a 3-way solenoid valve, and a shuttle valve. Opening (loaded) and closing (unloaded) of the inlet valve is controlled by the solenoid valve which is controlled by the PLC (ref. Section 5.2). The PLC monitors compressor operating conditions and system air pressure to determine when loaded or unloaded operation is required.
1.5.1 Unloaded, Off
(Figure 6)
1.5.2 Loaded, Running
(Figure 7)
When the compressor is off, the spring in the capacity control valve holds the inlet valve (1) closed and the bleed-off valve (2) open. The solenoid valve (4) is deenergized. When the compressor is started pressures at the 1st stage inlet (B) and interstage (F) are both negative, keeping the capacity control valve in the unloaded position.
The compressor remains unloaded until the main drive motor reaches full speed, and lube oil pressure reaches 10 psig. After the compressor reaches full speed and oil pressure is established, the solenoid valve (4) is energized, the capacity control valve operating chamber (C) is disconnected from 1st stage inlet vacuum and is vented to atmosphere (A) through the shuttle valve (3). Vacuum on the spring side of the operating chamber piston helps pull the inlet valve (1) open and closes the bleed-off valve (2). The inlet valve (1) is a butterfly valve which rotates and is operated by a slider on the capacity control valve shaft.
Air is now drawn into the compressor stages through the inlet air filter, compressed, and discharged through the check valve to the air piping system. As air is compressed interstage pressure (F) increases, transferring the shuttle valve (3) and pressurizing the operating chamber (C), keeping the capacity control valve open.
1.5.3 Unloaded, Running
(Figure 8)
1.6 Monitoring and Limiting Devices
(Figures 9-11)
System pressure is monitored by a pressure sensor on the discharge air piping. When the discharge pressure reaches the upper limit of the desired operating range, the solenoid valve is de-energized, de­pressurizing the operating chamber (C). The spring closes the inlet valve (1) and opens the bleed-off valve (2).
When unloaded a very slight amount of air is drawn through the inlet valve (1) to cool the compressor during unloaded operation. 2nd stage discharge air (G) is vented (D) to atmosphere (E) out of the bleed-off silencer. The check valve prevents system air pressure from pressurizing the compressor.
The compressor assembly is equipped with the following monitoring devices:
a. Interstage air pressure transmitter. Monitors air pressure at the
intercooler outlet. The pressure is shown on the GT Terminal (figure 10). Indicates condition of the intercooler and the compressor stages.
b. Outlet air pressure transmitter. Monitors air pressure at the
aftercooler outlet connection to plant air system. Pressure is shown on the GT Terminal (figure 10). Indicates condition of the aftercooler and the compressor stages.
7
COMPRESSOR OPERATOR PANEL
FIGURE 9 - COMPRESSOR FRONT VIEW
PILOT LIGHTS
PUSHBUTTONS
GT TERMINAL
FIGURE 10 - COMPRESSOR OPERATOR PANEL
8
(cont.)
1.6 Monitoring and Limiting Devices
c. Lube oil pressure transmitter. Monitors lube oil pressure at the
last bearing oil nozzle. Pressure is shown on the GT Terminal (figure 10). Indicates condition of the lube oil system, filter, and the setting of the relief valve.
d. First stage discharge air temperature sensor. Temperature is
shown on GT Terminal (figure 10). Indicates condition of the compressor first stage.
e. Second stage inlet air temperature sensor. Temperature is
shown on the GT Terminal (figure 10). Indicates condition of the intercooler.
f. Second stage discharge air temperature sensor. Temperature is
shown on the GT Terminal (figure 10). Indicates condition of the compressor second stage.
g. Lube oil temperature sensor. Temperature is shown on the GT
Terminal (figure 10). Indicates condition of the oil cooler.
h. Aftercooler discharge air temperature sensor. This is the
temperature of the air delivered to the air out service connection, and is shown on the GT Terminal (figure 10). Indicates condition
of the aftercooler. i. Total running time is shown on the GT Terminal (figure 10). j. Total loaded time is shown on the GT Terminal (figure 10). An
accumulated count of loaded hours assists in tracking air usage
and available excess capacity. k. Normal condition indication lights, on the Compressor Operator
Panel:
1. Standby
2. Run
3. Loaded A lamp test is available using the GT Terminal, which tests all indicating lights on the control panel, and the alarm beeper, if power is on. This test does not affect normal compressor operation.
1.7 Alerts
A blue ALERT light, and an appropriate message on the GT Terminal, indicates that service is required or that a temperature prealarm exists (temperature is approaching the shutdown point). In addition, an audible alarm sounds when an alert occurs. The alarm may be silenced without resetting the indication.
The GT Terminal indicates the following conditions as an ALERT:
a. Service inlet air filter. Indicates that the inlet air filter or the dust
filters are dirty, filter pressure drop exceeds 25 “H2O
b. Service oil filter. Indicates that the lube oil filter is dirty, filter
pressure drop exceeds 15 PSID.
c. Compressor service required. Indicates that 2 years have
elapsed since start-up, or the capacity control valve has cycled 1,000,000 times. Service must be scheduled.
d. Temperature prealarm (applies to all temperatures monitored).
Indicates that a temperature is approaching the shutdown point. Refer to the appropriate paragraph of section 1.8 for details of each monitored temperature. See page 22 for setpoint table.
9
PILOT LIGHTS
GT-TERMINAL
GRAPHIC TERMINAL W/ TOUCHSCREEN
PUSHBUTTONS
FIGURE 11 - COMPRESSOR OPERATOR PANEL
PRESS ARROWS TO CHANGE DISPLAY SCREENS
PRESS “ACK” TO
ALARM MESSAGE
SILENCE BEEPER
ALARM LIGHT
ALARM BEEPER
FIGURE 12 - ALARM DISPLAY
10
PRESS “STAT” FOR ALARM DETAILS
1.8 Shutdowns
Shutdown conditions are indicated by a red ALARM light on the control panel, and an appropriate message on the graphic display. In addition, an audible alarm sounds when an alarm occurs. The alarm beeper may be silenced by pressing ACK/Bell Cancel on the alarm page. The Bell Cancel does not reset the alarm. A "DRY" relay contact is provided as a combined signal for remote indication if any alarm occurs. A table of setpoints is located on page 22.
The GT Terminal indicates the following shutdown conditions:
a. High 1st Discharge Air Temperature (Shutdown)
Warning: HOT 1st Discharge (Prealarm) Indicates a problem with the first compressor stage.
b. Warning: HOT 2nd Suction (Prealarm)
High 2nd Suction Air Temperature (Shutdown) Indicates a problem with the intercooler or cooling air flow.
c. Warning: HOT 2nd Discharge (Prealarm)
High 2nd Discharge Air Temperature (Shutdown) Indicates a problem with the second compressor stage or a problem with the intercooler.
d. Warning: HOT Air Discharge (Prealarm)
High Discharge Air Temperature (Shutdown) Indicates a problem with the aftercooler or cooling air flow.
e. Warning: HOT Lube OIL (Prealarm)
High Lube Oil Temperature (Shutdown) Indicates a problem with the lube oil cooling system.
f. Low Lube Oil Pressure
Indicates low lube oil level in sump, lube oil pump failure, fouled cooler or piping, clogged oil filter, or improper setting of the relief valve.
g. Lube Oil Pump Motor Overload
Indicates continued over-current operation of the oil pump motor, problem with lube oil pump or motor, or high oil pressure.
h. Cooling Fan Motor Overload
Indicates continued over-current operation of the cabinet cooling fan motor, problem with fan or motor. Also check for obstructed air flow into or out of the cabinet.
i. Compressor Drive Motor Overload
Indicates continued over-current operation of the drive motor for the compressor, excessive discharge pressure or a problem with either compressor stage.
j. High Cabinet Temperature
Indicates an obstruction of the cooling air flow.
k. High Discharge Air Pressure
Indicates a problem with the capacity control system.
l. Main Starter Failure
Indicates a problem with the main starter or controls.
11
COMPRESSOR SECTION
ACCESS PANEL
TO OPEN PANELS FOR INSPECTION,
PULL OUT TOP EDGE
THEN LIFT PANEL UP
STARTER SECTION
ACCESS PANEL
MOUNTING BRACKETS
FIGURE 14
SPACER BLOCKS
FIGURE 13
SPREADERS
SPACER BLOCKS
FIGURE 15
12
2. INSTALLATION
2.1 Inspection
(Figure 13)
2.2 Handling
(Figures
14 & 15)
2.3 Foundation
2.4 Location
The unit should be inspected for damage immediately upon receipt from the carrier and any claims should be made to the delivery carrier immediately.
The compressor unit is equipped with forklift slots for ease in handling. Spacer blocks should be placed between the compressor and forklift mast to insure the cabinet will not be damaged during handling.
When handling the unit with an overhead crane, the lifting straps or chains should pass through the forklift slots. Spacers and spreader bars should be utilized to avoid damage to the enclosure.
The compressor and motor assembly are vibration isolated from the housing and base plate, additional isolation is not required. The assembly should be mounted on a level, horizontal floor. Holes are provided on each end of the compressor for installing bolt down brackets.
The unit should be installed indoors in a clean, well ventilated area, free from excessive dust or dripping liquids. Do not install in an area where chlorine gas, hydrogen sulfide gas, sulfur dioxide gas, highly concentrated ozone, or any other toxic, corrosive or flammable gasses are present.
2.5 Cooling Air
(Figure 17)
WARNING:
The compressor shall not be located where potentially explosive atmospheres may occur. The compressor and controls are not rated for installation in hazardous (classified) locations.
Any contaminates in the atmosphere will be compressed along with the air, therefore, it is important to provide a source of clean intake air. An external source of clean inlet air to the compressor may need to be provided.
The machine must be protected against freezing and excessive ambient temperatures.
For ease of panel removal and maintenance provide ample clearance around the compressor. A minimum of four feet is required in front of the compressor. At least three feet is recommended for each end and for the back.
The compressor should be located where sufficient ventilation is available to cool the compressor. The cooling air inlet and discharge must not be blocked. The warm air exiting the cooling air outlet must be prevented from being drawn into the cooling air inlet. Ventilation may need to be provided if the room in which the compressor is installed exceeds 104°F (40°C) during compressor operation.
Air ducts may be connected to air inlets or outlets if desired. However ducts must be sized to permit no more than 1” H2O restriction at full flow.
13
Loading...
+ 37 hidden pages