KOB PYRTEC SERIES, PYRTEC 530, PYRTEC 1250, PYRTEC 720, PYRTEC 950 Assembly And Installation Instructions Manual

Page 1
Assembly and Installation Instructions 530 to 1250
ID: 104661-F english
Page 2
Flotzbachstraße 33 A-6922 Wolfurt All rights reserved, including photomechanical reproduction and storage in electronic media.
Page 3
1 General Information 1
1.1 State of the art 1
1.2 Documented information 1
2 Important Instructions 1
2.1 Safety instructions 1
2.2 Permits by public authorities 1
2.3 Standards and regulations 1
3 The structural Surroundings for the Furnace 2
3.1 Heating room requirements 2
3.2 The chimney connection 2
4 Transport and Installation 2 5 Water System Installation 3
5.1 Safety Equipment 3
5.2 Expansion 3
5.3 The boiler circuit with return circuit valve 3
5.4 The extinguishing water tank 3
6 Electrical Installation 3
6.1 Positioning the control cabinet 3
6.2 Electrical connection 3
7 Fire Protection 4
7.1 Protection against burn-back for the boiler plant 4
7.1.1 Preventing overfilling of the fire box 4
7.1.2 Preventing burn-back 4
7.1.3 The backflash safeguard (RZS) 4
7.1.4 Automatically Triggering Extinguishing System for the Furnace Feed (SLEK) 4
7.2 Burn-back safeguard for the fuel supply system (RSE) 4
7.2.1 Automatically Triggering System for the Material Supply System (SLE-M) 4
7.2.2 The slide valve 4
7.2.3 Rotary valve 5
7.2.4 Double rotary valve with pressure compensation system 5
7.3 Fire protection for the fuel storage space 5
8 Commissioning 5
8.1 Filling the heating system 5
8.2 Fuel for the commissioning 5
8.3 Inspection of the installation 6
8.4 Commissioning and handover 6
9 Spec Sheets
7960-1, 2 PYRTEC Grate Firing System, Installation of Closed System 7960-3, 4 PYRTEC Grate Firing System, Installation of Open System 4550-1 Extinguishing System, Installation F 2682/3 Extinguishing System F 2482/4 Extinguishing System 7010-1, 2, 3, 4 PYRTEC Grate Firing System, Boiler Plant 7110-1, 2 PYRTEC Grate Firing System, Exhaust Gas Deduster 7120-1, 2 PYRTEC Grate Firing System, De-ashing & Cleaning Systems 7200-1 PYRTEC Grate Firing System, Furnace Accessories 7800-1, 2, 3 PYRTEC Grate Firing System, Pyrocontrol Control System 7810-1, 2 PYRTEC Grate Firing System, Double-boiler System PYRTEC/ PYROT 7850-1, 2 Pyrocontrol Control System, Remote Transmission 1120-1, 2 Services and Installation 1010-1, 2 Wood Fuels, Minimum Requirements / Instructions 1000-1, 2 General Terms and Conditions of Delivery Supplement EC Attestation of Conformity
Page 4
1
1 General Information
Köb solid-fuel furnaces may only be set up and commissioned by specialists. This will rule out any incorrect assembly or commissioning. These in­structions have thus been reduced to important technical data, references to regulations, technical rules and other regulations.
The PYRTEC is a heat generator in boiler category 3 for heating systems with hot water with a safety temperature of 110°C following EN 303-5: 1999 (Heating boilers for solid fuels, manually and automatically loaded firing systems).
1.1 State of the art
The operating instructions are in keeping with the PYRTEC at the time of its delivery. In the interest of our customers, we reserve the right to make subsequent alterations resulting from further tech­nical development without being required to give notification of such.
1.2 Documented information
The installation instructions contain the information required according to the EC Machinery Directive, 98/37/EEC, Appendix 1, Number 1.7.4.
Issue: 2006-07_english Prepared by: KaW
2 Important Instructions
2.1 Safety instructions
The water-bearing and electrical installation as well as the chimney connection must be carried out by individuals authorised to do so, complying with all relevant standards and safety regulations.
2.2 Permits by public authorities
The PYRTEC has been inspected and approved following the European Standard EN 303-5:1999. The PYRTEC also complies with all European na­tional divergences based on tightened regulations concerning emissions levels and efficiencies:
Austria:
Art. 15a B-VG "Agreement on the Saving of Energy" "Agreement on Protective Measures concerning Small-scale Furnaces"
Federal Law Gazette 331
st
Act Furnaces Act FAV dated 18.11.1997 Part II
Germany:
German Federal Emissions Control Act "Small-scale Furnace Systems Act, 1
st
BImSchV",
dated 1997-03-14
Switzerland:
Air-pollution Control Act, LRV, dated 16 Dec 1985, incl. the amendment dated 20 Nov 1991
Netherlands:
NeR
Dutch Directive on the Incineration of Clean Rem­nant Wood, June 1995
The installation of the PYRTEC Grate Firing System must be approved by the local building authority and registered there.
2.3 Standards and regulations
- Hot-water heating systems: Safety Equipment
DIN 4751 ÖNORM B 8130, ÖNORM B 8131
- Indoor chimneys: Requirements, Planning and
Execution, DIN 18160
- Chimney Dimensioning, DIN 4705 ÖNORM
M7515
- Heating water: Preventing Damage by Corro-
sion and Scale Formation in Hot Water Heating Systems, VDI 2035
- Storage of non-pelletised wood fuels:
Pressure Relief of Dust Explosions, VDI 3673 SUVA, Swiss Accident Insurance Association Guideline No: 1875, Wood Shavings Silos SUVA Technical Rules No: 66050 Green Woodchip Silos
- Fire protection
Automatic Wood-burning Systems, TRVB H118, Issue 1997 Wood-burning on Steam Boilers, TRD 414, Version of August 1996
- Supplementary air devices for indoor chimneys,
DIN 4795
The regulations applicable to the respective lo­cation of installation must always be complied with.
On request, we will be glad to provide you with the sources referred to for the standards and regula­tions listed. When on stock, we will be glad to send such to you at cost price.
Page 5
2
3 The structural Surroundings for the Furnace
The national building regulations existing in this connection must always be complied with.
3.1 Heating room requirements
A separate, dry heating room must always be pro­vided for the PYRTEC Grate Firing System. No combustible materials may be stored in the heating room. The heating boiler may only be set up on a fire- and temperature-resistant floor. No tempera­ture-sensitive pipes or lines may be installed in the floor beneath the heating boiler. The load-bearing capacity of the heating room floor must be designed for the weight of the system plus filling with water and fuel. The load-bearing capac­ity of the floor in the area of the boiler bearing sur­face must be 2500kg/m². Detailed technical di­mensioning is possible with data sheet no. 7010. The minimum distance to the walls and ceiling re­quired according to the table of dimensions for proper cleaning and maintenance of the boiler must be complied with. A sufficient supply of fresh air must be provided directly from outdoors into the heating room. Induced ventilation is necessary for heating rooms that are confined or enclosed. The temperature in the heating room must not ex­ceed +40°C while the system is in operation (in the area approx. 1 m away from the boiler). The temperature in the heating room must not fall below +10°C while the system is in operation (in­ner side of exterior walls).
3.2 The chimney connection
The PYRTEC Grate Firing System is equipped with an exhaust fan and thus a fireplace without a draught requirement. The design of the chimney should be carried out as for a fireplace with an oil or gas blast burner without a draught requirement (exhaust tempera­ture at rated load of 160°C-200°C). The PYRTEC Grate Firing System is output­controlled within a range from 25%-100% of the rated boiler output. This produces exhaust tem­peratures within a range from min. 100°C and max. 250°C. An insulated chimney should be provided to prevent the danger of sooting. The distance from the exhaust fan to the chimney should be as short as possib le. 90 °-elbows should be avoided if possible. Exhaust gas lines of more than 1 m in length must be insulated. The connection to the chimney should be made such that it rises at an angle from 30°-45°. The exhaust line, incl. the lead-in into the chimney, should be executed so as to be gas-tight.
4 Transport and Installation
The personnel who carry out the transport have to know the dangers of accidents that might arise on doing so and prevent such through suitable measures.
Only hoist the boiler when it is entirely empty (of water, fuel and ash).
Hoist by both lifting lugs simultaneously, with a max. spread angle of 45°. Otherwise use a load spreader.
Page 6
3
5 Water System Installation
Customers must ensure that there is a supply of water independent of the electricity supply. This (redundant) design ensures that in case of a power failure, the boiler will be reliably cooled by the thermal run-off safety valve.
Refer furthermore to the standards and regula­tions listed in this document.
5.1 Safety Equipment
The safety equipment for the heating installation must be carried out by the heating engineer authorised to do so.
See Spec Sheet 6960 as an example.
5.2 Expansion
With closed expansion, the supply pressure to the expansion tank should be equal to the max. amount of the facility plus 0.2 bar.
5.3 The boiler circuit with return circuit
valve
To reliably prevent boiler corrosion through con­densation of the exhaust gases, the boiler return flow temperature must in no case be below 65°C.
The PYRTEC Grate Firing System is infinitely variably output-controlled. For this, it is necessary for there to be a constant flow through the boiler of the water to be heated. The boiler circuit with the boiler pump and boiler mixer must therefore be in­stalled according to Spec Sheet 6960.
The design of the boiler circuit should be carried out such that the temperature difference between the forward flow and the return flow is equal to or less than 15°C.
The triggering of the boiler pump and boiler control valve is integrated in the control system that comes with the facility.
5.4 The extinguishing water tank
A self-triggering extinguishing device must always be installed by the furnace feed system. With re­gard to the assembly, refer to the spec sheets in the annex.
The functioning is carried out by means of an ex­tinguishing valve and is not dependent on electric current. A float-type switch monitors the water level and should be electrically connected (see connection diagram).
6 Electrical Installation
6.1 Positioning the control cabinet
The control cabinet with the control panel should be installed by the installing electrical company at a place easily accessible for control.
The position of the control cabinet should be se­lected such that any negative influences by heat radiation (front side of boiler, rear of boiler with ex­haust gas collector and exhaust fan as well as ex­haust line) or dust will be as low as possible during cleaning.
The ambient temperature for the control cabinet (approx. 10 cm away from the control cabinet) should not exceed 40°C while the system is in op­eration. In case of doubt, preference should be given to placing the control cabinet outside the heating room near the heating room door.
6.2 Electrical connection
- This should be carried out according to the ter­minal connection diagram. The terminal con­nection diagram is located on the inside of the door of the control cabinet that comes with the facility.
- In the area of hot parts (exhaust gas fan, ex­haust gas pipe), the lines should be installed in steel pipes at an appropriate distance so as to be temperature-protected.
- The cable bushings to the motors and equip­ment must be executed so as to be dust-tight and provided with a strain relief.
The regulations of the local electrical utility company must be complied with.
Page 7
4
7 Fire Protection
The fire protection regulations for wood heating systems differ from country to country.
The regulations applicable to the respective lo­cation of installation must always be complied with.
7.1 Protection against burn-back for the boiler plant
These are part of the scope of delivery for the PYRTEC Grate Firing System.
7.1.1 Preventing overfilling of the fire box According to TRVB 118, a level monitor must be
installed to prevent overfilling of the fire box. The PYRTEC Grate Firing System has a light barrier to monitor the embers.
7.1.2 Preventing burn-back With a sensor directly on the insertion pipe, any
danger of burn-back beginning will be detected and quickly counteracted at an early stage through boosted output (an increase in the advancing of the material).
As a result, any requirement for a protective device coming into effect is avoided, and normal opera­tion, defined as the greatest possible degree of safety supplying heat, is adhered to.
7.1.3 The backflash safeguard (RZS) According to TRVB 118, a backflash safeguard is
required for all facilities over 150 kW. TRD 414 prescribes a continuously present isolat-
ing layer if a spark-alarm and extinguishing system is dispensed with. (TRD 414 refers primarily to remnant wood from the processing of wood and derived timber products.)
For chip materials from the forestry and sawmill sectors, the restrictions are eased in part in this connection.
The PYRTEC Grate Firing System is always equipped with an isolating layer and is continu­ously operated with negative pressure.
As a result, according to both TRVB 118 a nd TRD 414, the PYRTEC Grate Firing System is consid­ered as equipped with a backflash safeguard (RZS).
7.1.4 Automatically Triggering Extinguishing System for the Furnace Feed (SLEK)
A water extinguishing system is always necessary on the feed auger.
This system should reliably prevent burn-back in case of a malfunction (such as a power failure). For safety reasons and to prevent damage by flooding, connecting the extinguishing system di­rectly to the water network is not advisable.
This extinguishing system must always be equipped with a 25-l extinguishing water tank with a float-type switch and an adjustable Danfoss ex­tinguisher valve.
According to TRVB 118, the tank for the SLE must be equipped with a level monitoring system.
If there is a shortage of water, the PYRTEC Grate Firing System will switch off automatically. In case of excess temperature, the feed auger will be flooded reliably but in a limited fashion.
The pipework for the extinguishing system must be carried out by the heating engineer according to Spec Sheet 4550.
7.2 Burn-back safeguard for the fuel supply system (RSE)
The rest of the "burn-back protection for material transport" depends on the respective requirements (location, size of the fuel storage site, material, pressure conditions & regulations), these being separate items for the scope of delivery ordered from KÖB & SCHÄFER GmbH according to the descriptions below.
7.2.1 Automatically Triggering System for the
Material Supply System (SLE-M)
Approved in part as a variation to the shut-off valve in pressure-less fuel storage units (does not meet TRVB).
The installation of the extinguishing system must be carried out by the heating engineer according to Spec Sheet 4550.
7.2.2 The slide valve
This is approved in pressure-less fuel storage units in all cases and applies according to TRVB 118 (test certificate BV 2979/89) as a suitable safe­guard against back-burn.
Page 8
5
7.2.3 Rotary valve If remnant wood is moved into fuel storage spaces
with fans, then, in order to reduce pressure ap­plied, at least one rotary valve is necessary to re­duce pressure between the fuel storage unit and the furnace. The rotary valve is suited to reduce pressure and at the same time is considered ac­cording to TRVB 118 (test certificate BV 2979/89) as a suitable safeguard against back-burn.
Max. overpressure allowed in fuel storage unit: +500 Pa Max. negative pressure allowed in fuel storage unit: +0 Pa
7.2.4 Double rotary valve with pressure com­pensation system
If, due to special circumstances, any mechanically produced negative pressures or extraordinarily high overpressures are expected in the fuel stor­age unit, then two rotary valves must be installed in the material transport route according to the re­spective project plan with a pressure compensa­tion line to the outdoors.
Max. overpressure allowed in fuel storage unit: +3000 Pa Max. negative pressure allowed in fuel storage unit: -3000 Pa
One must have the supplier of the chip suction­ing system confirm the maximum pressures to be expected.
The rotary valve below the silo extraction system can become leaky due to wear of the sealing ele­ments or through large pieces of wood that cannot be conveyed. This leakage can make it possible for low-temperature gases to flow back from the furnace into the silo.
A smoke gas alarm must be installed between the rotary valve and the silo extraction system, which, when triggered, will disconnect the system causing the negative pressure for the silo.
7.3 Fire protection for the fuel storage space
The measures necessary for this are never part of the scope of performance from KÖB & SCHÄFER GmbH.
The conditions set by the local building au­thorities must be met by the operating organi­sation in this connection.
8 Commissioning
Only KÖB & SCHÄFER GmbH or another trained specialist may put a newly installed facility into op­eration for the first time.
Before the facility is commissioned, the system must be filled with water, fuel stored for the com­missioning and the installation inspected.
8.1 Filling the heating system
The first filling is usually carried out with untreated water without any chemical water treatment but definitely filtered and thus free of any suspended solids.
Pay special attention when the filling is carried out to be sure the air is carefully bled out. With difficult water conditions (high degrees of hardness, etc) and/or large volumes of water, comply with VDI Guideline 2035 "Preventing Damage through Cor­rosion and Scale Formation in Hot Water Heating Systems" by using appropriate measures for water treatment.
Note: The filling pressure of the cold water re­serve should be approx. 0.1 bar greater than the supply pressure of the closed expansion tank.
8.2 Fuel for the commissioning
For the commissioning, dry fuel (max. W 20%) should be stored in an amount for approx. 10-24 full operating hours.
This is as follows:
PYRTEC 530 approx. 3000 kg PYRTEC 720 approx. 4000 kg PYRTEC 950 approx. 5300 kg PYRTEC 1250 approx. 6800 kg
Since the boiler plant is cold, and the residual moisture will also be drawn from the refractory concrete during the initial operation, the material to be burned for the initial operation has to be at least air dry. The heating-up process should be carried out during the first three hours at low output.
To check the functioning of the silo extraction sys­tem, not too much material to be burned should be stored so as to be able to quickly clear out the ex­traction system to remedy the cause of any mal­function there might be.
Page 9
6
8.3 Inspection of the installation
Before the commissioning, the future operating or­ganisation along with the installing companies (heating engineer & electrician) are obliged to in­spect the installation for the following points:
1. Exhaust gas port connected to the exhaust gas line on the chimney.
2. Chimney completely installed with clear cross section all the way through.
3. Safety valve installed on the boiler and/or boiler forward flow.
4. Thermal run-off safety valve connected to the cold water network.
5. The sensor for the thermal run-off safety valve is situated in the dipping shell.
6. The sensor for the temperature-limiting safety switch is situated in the dipping shell.
7. The extinguishing water tank on the feed au­ger is filled with water.
8. The sensor for the extinguisher valve is mounted tight on the pipe for the feed auger.
9. The expansion tank is connected.
10. The conveying systems are installed between the boiler and the material storage unit.
11. The facility is filled with water.
12. Material to be burned is stored for the test op­eration.
13. The safety limit switch is installed on the door to the material storage site (if there is a walk­through door).
14. The control system is connected to the power supply network.
15. The motors, switches and sensors are electri­cally connected.
Do not put the facility into operation over­hastily without the presence of a specialist from KÖB & SCHÄFER GmbH or another trained specialist.
In case of damage, you would lose your war­ranty claims.
Inspected on . . . . . . . . . . . . . . . . . . . . . . . . . . . .
By . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Signature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.4 Commissioning and handover
A competent contact person from the operating or­ganisation's side must be present for the commis­sioning and handover.
The heat dissipation from the boiler plant has to be assured by the operating organisation or by the heating engineer.
The heating engineer has to confirm that an in­spection of the installation has been carried out positively by handing over these signed Installation Instructions.
Complying with these Installation Instructions and also following the Operating Instructions, you will be provided with heat from wood in a safe and convenient fashion.
KÖB & SCHÄFER GmbH thanks you for the trust you have shown in us.
These Installation Instructions should be kept near the facility on a permanent basis.
Page 10
Spec Sheet
PYRTEC Grate Firing System Installation, closed system
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7960-1
2006-02-01_E
The dimensioning of the collector lines must be carried out by the installing heating engineer!
)
Page 11
Spec Sheet
PYRTEC Grate Firing System Installation, closed system
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7960-2
2006-02-01_E
a) Note:
- To reliably prevent boiler corrosion caused by condensation of exhaust gases, the boiler return flow temperature must
not under any circumstances be below 65°C. A boiler circuit pump with a modulating valve should be provided according to the diagram for this purpose. The boiler circuit should be designed such that the temperature difference between the forward flow and the return flow is equal to or less than 15°C.
- The expansion tank has to be connected to the boiler above the boiler forward flow and without any shut-offs.
b) Safety-relevant equipment included in the scope of performance provided by the installing heating engineer
M 20 Boiler pump Y 20 Boiler mixer SV Safety valve, pressure set to max. 3.0 bar, homologated component as per DIN 3440 Nominal width of the valve, of the connection line and of the exhaust pipe as per DIN 4751 Part 2 TS131 Thermal run-off safety valve R ¾”, homologated component; special-purpose design for opening
temperature 100°C, (safety heat exchanger built into boiler), from Pyrtec-720 2 safety heat exchangers in
parallel are required as well as 2 thermal run-off safety valves KW Cold water inlet, min. 2.5 bar, max. 3.5 bar WMS Water level control device, homologated component; required in Germany starting from systems over 350
kW,Installation recommendation: WMS with magnetic transmission of the float movement to a switch unit EL Air separator (recommendation: absorbition-type degasser) ExH Expansion tank closed, with design certification; for heating system
(Recommendation: connect on cool return flow, connected to the boiler via the forward flow without any
blockage units)
ExS Expansion tank closed; with design certification; for safety heat exchanger, max. 4.0 litres, 10 bar DAZ Pressure indication device (pressure gauge) TAZ Temperature indication device (thermometer)
c) Design recommendation
Mode l
KPT-
Boiler circuit (VL, RL, BP)
Thermal run-off safety valve TS-131 (quantity)
Water through-put required at
2.5 bar
Accumulat or volume
3)
Supply line ZL
Drain pipe AL
2)
Safety valve model SV 68M
1)
Safety line SL
2)
530 NW 100 1 2224 l/h 4300 l R ¾“ R 1“ R 1 ½“ NW 65 720 NW 100 2 3020 l/h 5800 l R ¾“ R 1“ R 1 ½“ NW 80 950 NW 125 2 3986 l/h 7600 l R ¾“ R 1“ 2 x R 1 ½“ 2 x NW 65
1250 NW 125 2 5246 l/h 10000 l R ¾“ R 1“ 2 x R 1 ½“ 2 x NW 80
1)
Threaded connection for supply line
2)
Length of the exhaust pipe up to 4.0 m (for longer lines, see DIN 4751 Part 2)
3)
On request, we will be glad to provide a project-based offer on the accumulator(s).
d) Equipment recommendation from KÖB's delivery programme
- Note: The equipment below will only be supplied via the installing heating engineer.
Model KPT-
Designation: Description: Item no: See Spec
Sheet:
Accumulator in the form of a hydraulic switcher
WD-…
4700
TS 131 Thermal run-off safety valve, 100°C
K-TS-131
4500
530 M 20 Grundfos pump UPS 65-60 F, 400 V 1)
ZPS-656-4
4600
720 M 20 Grundfos pump UPS 80-60 F, 400 V 1)
ZPS-806-4
4600
950 M 20 Grundfos pump UPS 80-120 F, 400 V 1)
ZPS-8012-4
4600
1250 M 20 Grundfos pump TP 100-60 F, 400 V 1)
ZPS-1060-4
4600
530 Y 20 Motor-three way tap, VBF 21.100/SQL33
ZH-3-100
4600
720 Y 20 Motor-three way tap, VBF 21.100/SQL33
ZH-3-100
4600
950 Y 20 Motor-three way tap, VBF 21.125/SQL33
ZH-3-125
4600
1250 Y 20 Motor-three way tap, VBF 21.125/SQL33
ZH-3-125
4600
1)
For ∆t 15K, as per illustration
Any additional resistors (heat meters, slide valve) require redesigning of the boiler pump!
Page 12
Spec Sheet
PYRTEC Grate Firing System Installation, open system
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7960-3
2006-02-01_E
The dimensioning of the collector lines must be carried out by the installing heating engineer!
)
Page 13
Spec Sheet
PYRTEC Grate Firing System Installation, open system
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7960-4
2006-02-01_E
a) Note:
- To reliably prevent boiler corrosion caused by condensation of exhaust gases, the boiler return flow temperature
must not under any circumstances be below 65°C. A boiler circuit pump with a modulating valve should be provided according to the diagram for this purpose. The boiler circuit should be designed such that the temperature difference between the forward flow and the return flow is equal to or less than 15°C.
b) Safety-relevant equipment included in the scope of performance provided by the installing heating engineer
M 20 Boiler pump Y 20 Boiler mixer TS131 Thermal run-off safety valve R ¾”, homologated component; special-purpose design for opening
temperature 100°C, (safety heat exchanger built into boiler), from Pyrtec-720 2 safety heat exchangers in parallel are required as well as 2 thermal run-off safety valves. These are not required for open systems,
but we advise installing these. KW Cold water inlet, min. 2.5 bar, max. 3.5 bar WMS Water level control device, homologated component; required in Germany starting from systems over 350
kW,Installation recommendation: WMS with magnetic transmission of the float movement to a switch unit EL Air separator (recommendation: absorbition-type degasser) ExO Expansion tank open, at the highest point in the system, heat insulated; for heating system
ExS Expansion tank closed; with design certification; for safety heat exchanger, max. 4.0 litres, 10 bar DAZ Pressure indication device (pressure gauge) TAZ Temperature indication device (thermometer)
c) Boiler circuit with open expansion, accumulator circuit if necessary, design recommendation
Mode l
KPT-
Boiler circuit (VL, RL, BP)
Thermal run-off safety valve TS-131 (quantity)
Water through-put required at
2.5 bar
Accumulato r volume
2)
Supply line ZL
Drain pipe AL
1)
Safety forward flow (SVL)
Safety return flow (SRL)
1)
530 NW 100 1 2224 l/h 4300 l R ¾“ R 1“ NW 50 NW 40 720 NW 100 2 3020 l/h 5800 l R ¾“ R 1“ NW 50 NW 40 950 NW 125 2 3986 l/h 7600 l R ¾“ R 1“ NW 65 NW 50
1250 NW 125 2 5246 l/h 10000 l R ¾“ R 1“ NW 65 NW 50
1)
Length of the exhaust pipe up to 4.0 m (for longer lines, see DIN 4751 Part 2)
2)
On request, we will be glad to provide a project-based offer on the accumulator(s).
d) Equipment recommendation from KÖB's delivery programme
- Note: The equipment below will only be supplied via the installing heating engineer.
Model KPT-
Designation: Description: Item no: See Spec
Sheet:
Accumulator in the form of a hydraulic switcher
WD-…
4700
TS 131 Thermal run-off safety valve, 100°C
K-TS-131
4500
530 M 20 Grundfos pump UPS 65-60 F, 400 V 1)
ZPS-656-4
4600
720 M 20 Grundfos pump UPS 80-60 F, 400 V 1)
ZPS-806-4
4600
950 M 20 Grundfos pump UPS 80-120 F, 400 V 1)
ZPS-8012-4
4600
1250 M 20 Grundfos pump TP 100-60 F, 400 V 1)
ZPS-1060-4
4600
530 Y 20 Motor-three way tap, VBF 21.100/SQL33
ZH-3-100
4600
720 Y 20 Motor-three way tap, VBF 21.100/SQL33
ZH-3-100
4600
950 Y 20 Motor-three way tap, VBF 21.125/SQL33
ZH-3-125
4600
1250 Y 20 Motor-three way tap, VBF 21.125/SQL33
ZH-3-125
4600
1)
For ∆t 15K as per illustration
Any additional resistors (heat meters, slide valve) require redesigning of the boiler pump!
Page 14
Spec Sheet
Fire-extinguishing Systems
K-SLE & K-SLV Installation
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
We reserve the right to make technical changes.
4550-1
2005-01-31_E
a) Fire-extinguishing System for Burner Slide-in Module, Art. No. K-SLE
Note: Pyromat-DYN has an extra charge with Art. No. K-SLE (see Spec Sheet 4500)
With Pyrot and Pyrtec this is included in the burner article.
Fig. 1: K-SLE on feed auger
b) Fire-extinguishing System for Material Feed Facility, Art. No. K-SLV
For Köb scope of delivery, refer to Spec Sheet 4500
Fig. 2: K-SLV on conveyor auger Fig. 3: K-SLV on extractor system situated on top with
downpipe
Be sure to note:
The lines must be executed in metal (1/2") with fixed pipework (K-SLE and K-SLV).
It must not be possible to shut off the cold water inlet without the aid of tools.
Be especially sure to comply with Point 5 of the Installation Instructions (Fire Prevention).
Note: K-SLV is an alternative or supplementary safety device. As standard, either a slide valve (Art. No. MBA-.; included in Article ADF_.,. / ADE_3,0) is required for pressureless material storage sites or a rotary valve (Art. No. MBZ-.) for material storage sites with over- or under-pressure (loading with fan, such as wood-processing businesses).
Line from container to the ½" valve (short as possible)
Valve adjustment, Danfoss AVTA 15 50-90°C 3, equivalent to approx. 80° C
KW: cold water inlet DN 15 ½" Min. 2.0, max. 3.0 bar
extinguisher water container 25 l
N25 level monitoring system
firing
material feed facility
CW
metering containermetering container
firing
with isolating layer with isolating layer
CW
firing
Page 15
Page 16
Page 17
Spec Sheet
PYRTEC Grate Firing System Boiler Plant
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes
7010-1
2006-06-01_E
The PYRTEC grate firing system has been designed for automatically burning all dry to wet wood fuels (waste wood, pellets, wood chips, up to max. W50) and combines in the best way possible the benefits of underfeed firing with the benefits of grate firing. The PYRTEC grate firing system is characterized by highest efficiencies and perfect combustion in all load stages. The PYRTEC has been tested and approved in accordance with the latest quality criteria in compliance with EN 303-5 heating boilers for solid fuels, CE certification as per European Machinery Directive and continuous quality assurance by TÜV.
Max. flow temperature: 100°C Max. operating pressure: 6.0 bar Safety heat exchanger: Built in the boiler & ready for use
Function:
- The solid, powerful and heat-resistant feed auger moves the fuel over the burner trough into the descending and into the grate zone, which drops down and travels. Situated on the conveyor pipe are the holding devices both for the burn-back sensor and for the thermal extinguishing valve. Above the auger there is the metering container with a light barrier for setting the level for the fuel isolating layer required according to TRD 414.
- The fuel is either ignited manually or automatically with an electric hot-air fan (separate price item). The tried-and­tested burner trough, the descending external grate and the moving burn-out grate made from highly-refractory cast steel (material no.: 1.4823; approx. 12 mm) allow excellent performance control and highest safety against burn-back in conjunction with automatic de-ashing system (separate price item) to be achieved for the combustion chamber. The solid, horizontally positioned and large-volume firing block has been optimised in terms of incineration, consists of a high-quality fireclay brick lining and is multiply insulated for the lowest possible surface temperatures.
In the lower part, the primary airflow is supplied to the incineration grates via a supply air fan in an output-controlled
fashion and pre-heated.
- In the upper part of the firing block, the secondary airflow is blown into the gas space of the firing system by an output-controlled fan via an encircling ring with high turbulence via individually adjustable nozzles.
This mixes the fuel gases with fresh secondary air for complete burning. The firebox door is solidly constructed, air-cooled and very well insulated. Opening the firebox door with its solid
double-knuckle hinges is an ideal solution for maintenance purposes.
The heat energy from the fuel gases is transferred to the boiler water in the horizontal shell-and-tube heat
exchangers.
The boiler is well insulated, possesses attractive cladding and is highly accessible through the boiler door on the front.
The insulated boiler door also allows a pneumatic cleaner to be installed (separate price item).
- The exhaust gas fan has been specially designed for burning wood and is very quiet. The spring-suspended motor possesses a solid, heat-resistant design with heat dissipation hub. The fan housing on the intake port rotates infinitely variably, and the blow-out nozzle is round. It is usually mounted on the exhaust gas deduster (separate price item).
Includes:
- Feed auger with isolating layer, including extinguishing valve with dirt collector, container with bracket for extinguishing water
- Fire block with burner trough, descending external grate and moving burn-out grate
- Boiler with horizontal shell-and-tube heat exchangers
- Exhaust gas fan
- Accessories: counter flange, including screws and seals, cleaning device
ACCESSORIES for PYRTEC grate firing (Item KPT- …) at extra charge:
Designation Item Text Dimensions Use
Exhaust gas de-duster 240 l KPT-E…-2
7110 7110 Required (exception: pellets)
Exhaust gas de-duster 800 l KPT-E…-8
7110 7110 Variation of 240-litre Preparation system for de-ashing KPT-AV 7120 - Optional for KPT-A2-S De-ashing into bin, 240 l KPT- A2-S
7120 7010 Optional for KPT-AV
De-ashing into skip 800 l KPT- A8-S
7120 7010 Variation of 240-litre Pneumatic cleaning system KPT-W…-S
7120 7010 Optional Automatic system KPT-ZG-S
7200 7010 not suited for > W40 Set of displacement rods KPT-V… 7200 - Base load boiler Flue gas recirculation system KPT-R…-S
7200 - For fuels < W20 Pyrocontrol control system PYR- … 7800 - Required
Page 18
Spec Sheet
PYRTEC Grate Firing System Boiler Plant
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes
7010-2
2006-06-01_E
Technical specs:
PYRTEC Grate Firing System Trade name 530 720 950 1250 Item No: KPT-530 KPT-720 KPT-950 KPT-1250 Performance data
Rated heat output QN [kW] 530 720 950 1250 Continuous output 1) Q
D
[kW] 530 720 950 1250
Minimum heat output 2) Q
min
[kW] 132 180 238 312
Heat output, W45 chips Q
W45
[kW] 515 700 920 1210
Efficiency in operation to be performed
3)
[%] > 90
Maximum water content
4)
[%] W 50
Size of the chips
5)
G 30 / G 50 as per ÖNORM M7133
Exhaust gas figures
Mass flow rate QN; W5; O2 8%; [g/s] 297 404 532 700 Volume flow QN; W5; O2 8%; 150°C [m³/s] 0.36 0.48 0.63 0.83 Mass flow rate Q
W45
; W45; O2 10%; [g/s] 412 560 736 968
Volume flow Q
W45
; W 45; O2 10%; 150°C [m³/s] 0.50 0.67 0.88 1.15
Average exhaust gas temperature at Q
N
6)
[°C] 160
Average exhaust gas temperature at Q
min
6)
[°C] 120
Chimney draught required [Pa] +-0
Electrical connections
Electrical connections (Σ boiler plant) [kW] 7.02 8.12 9.35 11.15 Ignition device [kW] 1.6 Exhaust gas fan [kW] 1.1 2.2 2.2 4.0 Feed auger [kW] 1.5 1.5 2.2 2.2 Primary airflow fan 1 [kW] 0.3 0.3 0.48 0.48 Primary airflow fan 2 [kW] 0.9 Secondary airflow fan [kW] 1.5 1.5 1.85 1.85 Grate drive unit [kW] 0.12 Electric power consumption at QN [kW] 3.57 4.56 5.17 6.79 Electric power consumption at Q
min
[kW] 2.9 3.71 4.15 5.47 Heating-relevant specs Volume on heating gas side [l] 2280 2830 4050 5210 Volume of ash container for grate ash [l] 240 / 800 Volume of ash container for exhaust gas de-duster [l] 240 / 800 Water-bearing resistance (Diff. 15 K) [mbar] 23 43 26 45 Boiler water volume [l] 1444 1861 1943 2482 Heating surface [m²] 42.50 55.50 74.80 91.00 Test pressure [bar] 7,8 Maximum operating pressure [bar] 6 Maximum boiler temperature [°C] 100 Minimum return temperature [°C] 65
Weights
Weight of fire block [kg] 3833 4665 5892 7252 Weight of heat exchanger [kg] 1986 2562 4128 5431 Weight of exhaust gas de-duster [kg] 463 463 695 695 Weight of feed auger [kg] 126 126 148 148 Total weight without water
7)
[kg] 6802 8210 11401 14064
Total weight with water 7) [kg] 8246 10071 13344 16546
1)
Continuous output: Output levelling out as base load boiler in continuous operation with pneumatic cleaning
system (for track time, see Operating Instructions)
2)
Q ≥ Q
min:
Operation with modulated control
Q ≤ Q
min
: Low load with ON Q
min
/ ember maintenance operation
3)
Efficiency: Specification with displacement rods and flue gas recirculation system
for dry fuels (W5 to W20) without flue gas recirculation system-reduced values
4)
Wet fuels: >W45 further restrictions in terms of output, efficiency and control behaviour
5)
Specification: See Spec Sheet 1010, Minimum Requirements for Wooden Fuels
6)
Exhaust gas temperature: A reduction is possible by installing the displacement rods (QN - 20°C; Q
min
– 10°C)
Other influences: fuel water content, ash content, pneumatic cleaning system yes/no, track time (number of
operating hours without cleaning) Specifications for the start of the track time (toward the end of the track time there is an increase in the exhaust gas temperature by approx. +15°C)
7)
Total weight: incl. displacement rods
Page 19
Spec Sheet
PYRTEC Grate Firing System Boiler Plant
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes
7010-3
2006-06-01_E
Dimensional drawing:
Boiler bearing surface
Floor with heat-resistant design additional
Front
(boiler door)
The floor construction has to be free of any pipes or installation lines! Danger through the effects of heat!
1) 800 mm access, firing block 960 mm if there is a door stop & pneum. cleaning system Position of approx. 110° required for manual cleaning of heat exchanger
530 / 720
connection at the centre
950 / 1250
choice of connection
left or right
FIRING BLOCK
BOILER
FEED AUGER
EXHAUST GAS FAN ø A
see spec sheet 7110
Page 20
Spec Sheet
PYRTEC Grate Firing System Boiler Plant
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes
7010-4
2006-06-01_E
Connections/dimensions:
PYRTEC [Item no.] KPT-530 KPT-720 KPT-950 KPT-1250 Water connections PN 6 (see Spec Sheet 7960)
I Boiler forward flow DN 100 DN 100 DN 125 DN 125 II Boiler return flow DN 100 DN 100 DN 125 DN 125 III Connection for extinguishing water R ¾“ AG R ¾“ AG R ¾“ AG R ¾“ AG IV Drain valve for boiler R 1 ½“IG R 1 ½“ IG R 1 ½“ IG R 1 ½“ IG V Safety heat exchanger 4 x R ½“ AG 8 x R ½“ AG 8 x R ½“ AG 8 x R ½“ AG VI Dipping shell for thermal run-off safety valve 1 x R ½“ IG 2 x R ½“ IG 2 x R ½“ IG 2 x R ½“ IG
Connection for exhaust gas pipe Ø [mm]
A 350 350 450 450
Location of the connections [mm]
a 2359 2491 2444 2639
b 1922 2562 2562 3107
Dimensions of the foundations [mm]
d 4272 4912 5096 5641 e 1400 1400 1630 1630 f 2472 3112 3066 3611 g 1112 1112 1360 1360 h 1912 1912 2160 2160
Dimensions of the boiler [mm]
B 1380 1380 1612 1612 C 1283 1413 1371 1566 D 760 1430 1050 1550 E 4617 5257 5447 5992 F 1380 1380 1612 1612 G 2353 2993 2861 3406 H 577 577 657 657 K 1200 1200 1275 1275 L 2654 2784 2981 3176 M 2702 2834 3035 3230 N 308 308 440 440 O 803 803 929 929 P 453 453 479 479 R 3237 3877 3835 4380 S 3794 4434 4392 4937
Parts for maintenance
1 Fire box door with solid double hinging 2 Boiler door 3 Cleaning lid for burner trough 4 Cleaning lid for external grate 5 Cleaning lid for heat exchanger 6 Pneumatic cleaning system Item KPT-W…-S Spec Sheet 7120
Electric drives; ignition
10 Feed auger 11 Drive for feed grate 12 Ignition device 13 Primary airflow fan 1 14 Primary airflow fan 2 15 Secondary airflow fan 16 Exhaust gas fan Dimensions: / Spec Sheet 7110 17 De-ashing, fire box auger Item KPT-A.-S / Spec Sheet 7120 18 De-ashing, ascending conveyor auger Item KPT-A.-S / Spec Sheet 7120
Switches and sensors These items are part of the Pyrocontrol control system
Item PYR-… / Spec Sheet 7800 20 Light barrier for feed auger 21 Limit switch for maintenance cover 22 Temperature sensor for feed auger 23 Light barrier for embers 24 Fire box temperature sensor (insertion side) 25 Negative pressure sensor (opposite insertion side) 26 Overpressure monitor for fire box 27 Light barrier for de-ashing 28 Limit switch for fire box door 29 Boiler sensor 30 Return flow sensor 31 Temperature-limiting safety switch (TLSS) 32 Exhaust gas sensor Location: Spec Sheet 7110 33 Lambda sensor with measuring transducer Location: Spec Sheet 7110
Page 21
Spec Sheet
PYRTEC Grate Firing System Exhaust Gas Deduster
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes
7110-1
2006-01-02_E
Description:
Exhaust gas de-duster 240 litres [Item no. KPT-E…-2] Exhaust gas de-duster 800 litres [Item no. KPT-E…-8]
The exhaust gas deduster is for minimising dust emissions and is executed as a multi-cyclone with an axial function. The deduster is completely insulated, attractively encased and provided with a total of three lids for cleaning. The crude gas space is cleaned via the cleaning lid on the side. The clean gas chamber is cleaned via the top or rear cleaning lid (fan connection not used).
The ash container has rollers, connects to the deduster by quick-action fasteners and moves out simply for emptying. The exhaust fan (see description of PYRTEC) is mounted on top, either vertically or horizontally, as desired.
Note: One ash bin/ash skip comes with the system. Additional bins/ash skips have to be ordered separately. (Item no: EB-240/ EC-800, Spec Sheet: 7120)
Page 22
Spec Sheet
PYRTEC Grate Firing System Exhaust Gas Deduster
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes
7110-2
2006-01-02_E
Dimensions and data:
Dimensions:
Exhaust gas de-duster [Item no.]
KPT-E530-. KPT-E720-. KPT-E950-. KPT-E1250-.
A 350 350 450 450 a 2359 2491 2444 2639 j 3166 3390 3425 3620 k 1330 1462 1462 1657 l 1250 1250 1300 1300 m 586 678 663 663 n 447 461 546 546 q 1090 1090 943 943 r 614 614 943 943 t 1650 1742 2056 2056
For weights and electrical data, see Spec Sheet 7010
Ash station: Positioning is possible in 4 x 90° (removal of ash skip) The drawing shows removal to the right.
DEDUSTER
(Axial cyclone)
ASH STATION:
EXHAUST GAS FAN
Rotates infinitely variably
- choice of top or side
Choice of 240 l or 800 l
to the
chimney
from the
furnace
zum
Kamin
vom
Kessel
CLEANING LID
Crude gas chamber
- unused connection as cleaning lid, clean gas chamber
Page 23
Spec Sheet
PYRTEC Grate Firing System De-ashing & Cleaning Systems
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7120-1
2006-03-06_E
Preparation System for De-ashing [Item No: KPT-AV]
The trough for later accommodation of the de-ashing auger is covered by fireclay bricks. The ash is removed manually via the fire box door.
De-ashing into ash bin, 240 litres [Item No. KPT-A2-S] De-ashing into ash skip, 800 litres [Item No. KPT-A8-S]
The PYRTEC's moving grate conveys the burnt-out ash into an ash trough recessed deep in the fireclay floor. From there the ash is extracted from the furnace by an auger made of heat-resistant steel. An additional ascending conveyor auger moves the ash into large-volume ash containers. The galvanised ash containers connect easily to the ash station by quick-action fasteners and move on rollers.
Function of the control system: The level of the ash trough is monitored by a light barrier. When the level is exceeded, a certain amount of ash is carried off into the container. Continuous operation can be switched to for cleaning purposes when the furnace is shut down.
The following items come with the system:
- Fire box auger made of heat-resistant steel
- Ascending conveyor auger with container station
- Ash bin or ash skip
- Triggering system for the auger drives
- Infrared light barrier level monitoring system for ash in fire box
Ash bin, 240 l, reserve [Item No. EB-240]
Ash skip, 800 l, reserve [Item No. EC-800]
Extension of ascending conveyor auger, per metre [Item No. KPT-ASM]
Extension of fire box auger, per metre [Item No. KPT-AFM]
Page 24
Spec Sheet
PYRTEC Grate Firing System De-ashing & Cleaning Systems
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7120-2
2006-03-06_E
Pneumatic cleaning system [Item No. KPT-W720-S] Pneumatic cleaning system [Item No. KPT-W1250-S]
The complete pipe-type heat exchanger is cleaned off by periodic blasts of compressed air while the system is in regular operation. The process of cleaning itself takes place in blasting of the individual sections carried out one after another. The ash on the heat exchanger pipes is detached by very short but strong blasts of pressure.
The particles detached are conducted by the flow of gas to the de-duster, where most are eliminated.
The system is built into the furnace door.
The compressor should preferably be installed in a cool spot in the heating room.
Function of the control system: The number of cleaning cycles within one unit of time (e.g. per hour) is adjusted according to the loading of the furnace. One single, complete cleaning cycle consists of one sequence of blasts over all the sections of the heat exchanger.
The following items come with the system:
- Nozzle element built into the furnace door, incl. connecting piece with heat dissipation plate
- Compressed air distributor with tank and valves; with heat-resistant hoses connected to nozzle element
- Compressor; model 362-100, special-purpose design for municipal uses
Delivery capacity of 202 l/min.; tank: 100-l; pressure: max. 10 bar; motor: 2.2 kW, 1450 RPM, 230V, incl. pressure controller, pressure switch and operating time limiter; plug and play; sound level of normal design: 75 dBA
- Compressed air hose up to max. of 4.0 m in length
- Valves wired tight to terminal strip
- Software component in the control system
To be carried out by customers:
- Provide a mains socket, 230V/ 16A
Technical data:
PYRTEC KPT-530 KPT-720 KPT-950 KPT-1250 [Item No.] KPT-W720-S KPT-1250-S
Number of zones/valves 10 12 Size of the valves 6/4“ 6/4“ Max. air consumption, full load [l/h] 4400 5300
Compressor soundproofed, 64dBA [Item No. KT-WK]
- Compressor in Special design for municipal use with soundproof hood (model 362-100); delivery capacity: 202 l/min
- Tank: 100 l; pressure: max. 10 bar; motor: 2.2 kW, 1450 RPM, 230V; incl. pressure controller and pressure switch, plug and play; sound level: 64 dBA.
When this item is used, the compressor listed in the item "Pneumatic Cleaning System" is omitted.
Reduced charge with compressed air provided by the customer [Item No. KT-WL]
As a result, the compressor listed in the item "Pneumatic Cleaning System" is omitted. The compressor provided by the customer has to deliver at least the amount and quality of air specified and have an adjustable pressure controller as well as a protective device against hose rupture (e.g. operating time limiter).
Page 25
Spec Sheet
PYRTEC Grate Firing System Furnace Accessories
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes
7200-1
2006-06-01_E
Automatic ignition system [Item No. KPT-ZG-S]
Set of displacement rods [Item No. KPT-V720] Set of displacement rods [Item No. KPT-V1250]
Installing the displacement rods in the heat exchanger pipes produces better heat transmission and thus lowering to a great degree of the exhaust gas temperature. The displacement rods are advisable for fuels with water content less than W40 and when the furnace is used to cover the base load.
Recommendation: only use with a pneumatic cleaning system.
Flue gas recirculation system [Item No. KPT-R530-S] Flue gas recirculation system [Item No. KPT-R720-S] Flue gas recirculation system [Item No. KPT-R950-S] Flue gas recirculation system [Item No. KPT-R1250-S]
Function: Exhaust gas is mixed into the combustion air. This increases the proportion of gases not involved in the incineration (nitrogen N
2
and carbon dioxide CO2), with the effect of lowering the fire box temperature. This in turn enables, on the one hand, maximum efficiencies with a low amount of excess air with dry fuels and, on the other hand, the incineration of fuels that tend to form slag.
The following items come with the system:
- Recirculated flue gas fan with a heat-resistant design instead of the two primary airflow fans
- Suction line between furnace outlet and recirculated flue gas fan made of heat-resistant steel no: 1.4401
Incl. valves for regulating fresh air/recirculated gas
- Pressure lines from the recirculated flue gas fan to the firing block
Incl. valves for splitting up the recirculated gas/air mixture to the internal and external grates The two primary air fans for the standard design are omitted.
- Software component in the control system To be carried out by the customer:
- Insulation of the recirculated gas line in the course of the general insulation work (fire tubes, heating tubes, etc)
Page 26
Spec Sheet
PYRTEC Grate Firing System PYRTEC- Pyrocontrol
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7800-1
2006-07-01_E
PYRTEC - Pyrocontrol [Item No: PYR-530] PYRTEC - Pyrocontrol [Item No: PYR-720] PYRTEC - Pyrocontrol [Item No: PYR-950] PYRTEC - Pyrocontrol [Item No: PYR-1250]
An SPS-control system for the complete PYRTEC Boiler Plant, incl. control of the systems for the fuel loading necessary for the articles listed separately. The heat output of the furnace adjusts to the heat consumption in modulating fashion. A regulating circuit for an incineration optimising system is superimposed on the output control circuit with a lambda sensor. Maximum quality criteria are met in terms of fire protection and personal protection.
Functions:
- Output and control circuits with modulating output operation (25%-100%)
- Air-conducted by means of a speed-regulated supply air fan, depending on the forward flow temperature
- Precise resupplying of fuel by the feed auger from the metering container with an isolating layer
- Refilling of the metering container with the use of a level monitoring system
- Limitation and distribution of the mass burning in the fire box by means of a level monitoring system in the
fire box along with movement of the feed grate
- Emissions-optimised control circuit with fine tuning of the fuel/air mixture by a lambda sensor
- Pressure regulation of the fire box with constant negative pressure guaranteed
- Fire box temperature limitation with the required variation of the air index to protect the fire-resistant lining
- Upholding the return flow temperature with the boiler mixer provides for a long service life of the boiler.
- Safety functions for:
Excess temperature, burn-back, opening of the fire box door, opening of a lid in the loading system, excess pressure in the fire box
- Floating output (malfunction indication system)
Operation: Operation is carried out by means of a control panel with a membrane keyboard and plain language display, which are built into the control cabinet door. All the operational data can be read on the display. The set points for all the important parameters can be entered simply using the keyboard. Malfunctions are displayed in plain language and indicated in the order of their occurrence. The following items come with the system:
- Control cabinet (uninstalled), surface powder-coated with RAL 7035 (grey) textured Executed according to ÖVE/VDE-guidelines, ready-wired on series terminals, Feed: 3x400 V 50 Hz; control voltage: 230 V or 24 V
- Freely programmable control system, CE-inspected, programme and real-time clock are battery-backed
- Motor contactor switch for all drives according to the separate items priced separately
- Frequency converter for fan motors
- Protective motor switch for boiler pump
In the door:
- 4-pin master switch
- Control panel with back-lit plain language display
- Documentation, incl. bound circuit diagram, terminal connection diagram with cable designation, operating and maintenance instructions, installation instructions in document sleeve
- Sensors and switches mounted on the feed auger
- Infrared light barrier level monitoring system, insulating layer for feed auger
- Safety limit switch on the maintenance lid for the feed auger
- PT-100 temperature sensor feed auger
- Sensors and switches on the firing block for firing and in the exhaust gas nozzle (installation on site)
- NiCrNi fire box sensor
- Infrared light barriers for level monitoring of fuel in the fire box
- Negative pressure sensor
- Overpressure monitor
- Zirconium dioxide sensor with instrument reading converter (lambda sensor)
- PT-100 exhaust gas sensor
- Sensors and switches mounted on the boiler on top
- PT-100 boiler sensor in the connecting piece, forward flow
- PT-100 return flow sensor in the connecting piece, return flow
- Temperature-limiting safety switch (TLSS)
- Sensor, uninstalled
- One PT-100 sensor with dipping shell, 1/2 " x 280 mm (B28.1, see Spec Sheet 7960-1)
Page 27
Spec Sheet
PYRTEC Grate Firing System PYRTEC- Pyrocontrol
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7800-2
2006-07-01_E
Extensions available for the PYRTEC Pyrocontrol (article PYR-…) at an extra charge:
PYRTEC single-unit system:
Designation Article Text Use
Heat generator, bivalent PYR-KP0 7810 Integration System for Electric Boiler Heat generator, bivalent PYR-KP1 7810 Integration system for oil/gas-fired boiler Output Management System PYR-… 7810 Additional heat generation functions Visualisation system, internal PYR-KVI 7810 optional (for customer’s PC workplace) Remote transmission PYR-… 7820 Visualisation, remote maintenance
The control system components for the fuelling system are included in the articles for the various loader systems. The PYRTEC single-unit system is not designed to control heat consumers. (Such control is carried out by customer­provided building instrumentation and control equipment.)
PYRTEC Double-unit System
The Mastercontrol control system (see Spec Sheet 7850) is mandatory for the installation of a PYRTEC double­unit system.
The PYRTEC double-unit system is a heat-generating facility, in which the load allocated to the biomass is distributed to two PYRTEC boilers. The entire thermal load generated is conducted to a joint accumulator in the form of a hydraulic switcher. It is necessary to comply with the following for this type of system:
1. Joint fuelling system: Mastercontrol The control of the joint fuelling system for the PYRTEC double-unit system is carried out by the Mastercontrol control
system. The control system components for the fuelling system are included in the articles for the various loader systems.
2. Additional heat generators: Mastercontrol Extensions for controlling additional heat generators are only allowed in the Mastercontrol (additional control cabinet)
and not in the individual boiler control system (PYR-530/ -720/ -950/ -1250).
3. PYRTEC Ecotronic control system, as an individual boiler control system Only the extensions listed in Spec Sheet 7850 are possible in the Mastercontrol control system.
The PYRTEC double-unit system is not designed to control heat consumers. (Such control is carried out by customer­provided building instrumentation and control equipment.) Using a Mastercontrol turns the PYRTEC Ecotronic control system into an individual boiler control system, without any further extensions being possible.
Page 28
Spec Sheet
PYRTEC Pyrocontrol Output Management System
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7810-1
2006-07-01_E
Note: The control system components below are reserved for the PYRTEC single-unit system. With the PYRTEC double-unit system, these functions are included in the Mastercontrol.
Accumulator Management System, 5 Sensors (QM) [Art. No.: PYR-KSF5]
Function: Using a heat accumulator improves the modulating output operation of the PYROT grate heating system. In addition, sudden heat requirement peaks are covered. The accumulator's load of heat is detected by the temperature sensors. The instruction for the accumulator's degree of loading is carried out by the external sensor in weather-guided fashion. The firing power is adapted to the accumulator's degree of loading. Includes:
- 4 additional PT100 sensors with dipping shell, 1/2" x 280 mm (B28.2, B28.3; see Spec Sheet 7960-1)
- 1 weather sensor, PT100, uninstalled
Operational Message [Art.-Nr. PYR-KBM]
Function: Output of the "Operating Load" operating condition; starting from any overstepping of the minimum exhaust gas temperature, to higher-level instrumentation and control equipment for further processing Includes:
- Floating output (operational message)
Output signals 0 V - 10 V [Item No: PYR-KLS]
Function: The system includes output of the boiler output in the form of a voltage signal and preparation for connection to receive a maximum limitation of the boiler output. The following items come with the system:
- Output of the boiler output, 0 V - 10 V
- Reception and processing of an external output limitation
0 V - 0.5 V... OFF
0.6 V - 3 V... Maintain embers
3.1 V - 10 V... 30% to 100% output operation
Note: Installation of "Output signals 0 V - 10 V" are possible according to "QM for Wood Heating Systems" irrespective of any additional control system components to be used.
Page 29
Spec Sheet
PYRTEC Pyrocontrol Output Management System
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes.
7810-2
2006-07-01_E
Requirement for additional heat generator [Item No: PYR-KP0]
Function: Either individually or together with the PYRTEC biomass boiler, the additional heat generator supplies the heat accumulator, executed as a hydraulic switcher (see Spec Sheet 7960). The triggering is carried out such that the additional heat generator covers the peak required, and the biomass boiler does so for the base load, the sluggishness of the biomass boiler being taken into account. While the additional heat generator is in the operational phase, the boiler pump is in operation and the motor-driven shut-off device open. This system comes with the following items:
- Selector button
- Contactor and motor contactor for boiler pump for the additional heat generator
- Triggering system for motor for shut-off device; OPEN/SHUT regulation
- Floating output contact for the triggering system for the burner
Requirement for additional heat generator [Item No: PYR-KP1]
Function: Either individually or together with the PYRTEC biomass boiler, the additional heat generator supplies the heat accumulator, executed as a hydraulic switcher (see Spec Sheet 7960). The triggering is carried out such that the additional heat generator covers the peak required, and the biomass boiler does so for the base load, the sluggishness of the biomass boiler being taken into account. While the additional heat generator is in the operational phase, the boiler pump is in operation and the regulation is activated for the boiler mixer. This system comes with the following items:
- Selector button
- Contactor and motor contactor for the boiler pump for the additional heat generator
- Controller for the motor for the boiler mixer; continuously regulated to a constant return flow temperature
- Floating output contact for the triggering system for the burner
- PT100 sensor, incl. dipping shell, 1/2 " x 280 mm, uninstalled, (installation, return flow, additional heat generator)
Visualisation system, internal [Item No: PYR-KVI]
All the data is conducted to the PC via an RS 232 serial interface in the control cabinet over a data line (max. 30 m) to the PC. The current operational data for the boiler plant is visually shown on a function display with all the possibilities for entering values and functions as well as reading out the operational states (exception: "Start Boiler"). All the operational data is archived on a cyclical basis and can be graphically evaluated in a very simply fashion. The PC and data line are not included in the price. This system comes with the following items:
- Serial interface, RS 232
- CD with visualisation software and installation instructions
Note: regarding data line for "Visualisation system, internal", see Spec Sheet 4090. Note requirements for PC provided by the customer: Operating system: Windows 98 / 2000 / XP Available hard disk storage space: at least 50 MB RAM: at least 128 MB RAM Per boiler: 1 available serial interface
Page 30
Spec Sheet
PYRTEC Rotation Firing System
Mastercontrol
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Technische Änderungen vorbehalten
7850-1
2006-07-01_E
Mastercontrol [Art. No. ECO-M2] Mastercontrol [Art. No. ECO-M3]
Mastercontrol improves the overall generation of heat by two biomass boilers (PYRTEC double-unit system), incl. the control of a bivalent boiler (oil-fired boiler, gas-fired boiler or electric boiler) as a redundant unit and/or as a peak-load boiler.
Function:
- Heat management system: optimum breakdown of the necessary heating capacity among the two biomass boilers
with the main load on the primary boiler and the remaining load on the secondary boiler, this being done by means of output specification. The output specification is carried out in weather-guided fashion, depending on the desired temperature set in a joint hydraulic switcher. Automatic change between the two boilers to guarantee even loading of the boilers over a long operating period. (Example: weekly changeover)
- Loader system: If the fuel for the two biomass boilers is taken from a joint fuel storage unit, then the loader system is
controlled by the Mastercontrol system up to the fuel distribution.
- Data management system:
A complete package for transferring all the data to an external customer-provided IT-workplace for visualisation, remote maintenance and archiving of operational data for the PYRTEC boiler system. Hardware, incl. modem and software, are integrated in the Mastercontrol system. All the adjustable parameters can be changed from the external IT-workplace.
Operation: Operation is carried out either by means of a touch screen built into the control cabinet (extra charge for touch screen) or by the monitor, keyboard and PC-mouse provided by the customer.
Includes:
- Switch cabinet, uninstalled; surface powder-coated in RAL 7035 (grey) texture Designed in accordance with ÖVE/VDE guidelines, ready-wired on series terminals Feed: 3 x 400V 50 Hz; control voltage 230V or 24V
- Freely programmable control system, CE-tested; battery-buffered programme and real-time clock
- Industrial PC
- Starttec for all loader system drives (3 x 400V) in accordance with the separate price items
- DVI-interface for a TFT monitor and USB-interface for keyboard, mouse and printer built into the cable lead­through bar on the control cabinet.
- Floating output (error report) In the door:
- 4-pin master switch
- Documentation, including bound circuit diagram, terminal connection plan with cable identification in document sleeve
- Accumulator management system, 5 sensors (QA)
- 5 PT100 sensors, with dipping shell 1/2" x 280 mm
- Output specifications for both biomass boilers
- Output specifications for both biomass boilers for further processing in the lower-level boiler control systems via serial interface
- Visualisation per modem
- Analogue modem in switch cabinet
- Windows operating system, pc-Anywhere remote-maintenance software and visualization/archiving software
installed and tested on an industrial PC Screen images:
- Three-dimensional boiler cross-section with display fields
- Installation diagram, heat generation, with display fields
- Parameter table (with editing feature)
To be carried out by the customer:
- Electric connection from telephone line to modem
[Art. No.] Mastercontrol
Boiler 1 Control
system for Boiler 1
Boiler 2 Control
system for Boiler 2
ECO-M2
PYRTEC PYR-… PYRTEC PYR-…
ECO-M3
PYRTEC PYR-… PYROT ECO-…
Touch Screen [Art. No. ECO-TSC]
The touch screen (15") is built into the door of the control cabinet and can be used to call up and change all the relevant boiler and loader system parameters.
Page 31
Spec Sheet
PYRTEC Rotation Firing System
Mastercontrol
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Technische Änderungen vorbehalten
7850-2
2006-07-01_E
Extensions available for the Mastercontrol (article ECO-M1/2) at an extra charge:
Designation Article Text Dimensions Use
Prompt for additional heat generator ECO-KP0 4030 - Integration System for Electric Boiler Prompt for additional heat generator ECO-KP1 4030 - Integration System for Oil/gas-fired Boiler Output signals, 0-10V ECO-KLS 6810 - For higher-level building instrumentation and control equipment Malfunction indication by modem (wire) ECO-SMD 6820 - optional (advisable) Export operational data ECO-SED 6820 - For higher-level building instrumentation and control equipment Touch Screen ECO-TSC 6850 - optional Fuel Conveyance System …-1.. 8000ff 8000ff For joint loader system
Diagram (top: hydraulic system; bottom: loader system):
Note: Water-bearing installation and electrical installation are provided by the customer:
MASTER-
CONTROL
PYRO-
CONTROL
PYRO-
CONTROL
MASTER-
CONTROL
PYRO-
CONTROL
PYRO-
CONTROL
(ECOTRONIC)
Page 32
Spec Sheet
Installation Services
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
We reserve the right to make technical changes.
1120/b-1
2005-01-31_E
Installation (one fitter with helper provided by the customer) [Art. No. IMO-1]
Performance provided by the contractor (supplier): Furnishing the entire scope of the delivery. Installing the burner system, incl. all the machinery parts and facility components contacted by fuel and exhaust gas for the scope of delivery cited. Also included is the installation of all the limit switches, thermostats, probes and sensors supplied (exceptions: weather sensors and heat consumers).
The installation will be carried out by an experienced fitter (a qualified helper being required). Price, incl. travel, expenses and overnight accommodation. Performance provided by the client (buyer):
1.) Prior to installation of the burner system
a) Equipping of construction site as follows:
Paved access road to the construction site; 230-V current supply line and, if necessary, 400 V for electric installation tools (welding apparatus); b) General construction work, as follows:
Making all the installation holes required for the installation;
Making the cement foundations and recesses for refill access lids and casings of extraction equipment;
Pits and breakthroughs for fuel conveying equipment c) Construction work in particular as follows: Hydraulic sliding bar extraction system: Moving and setting in concrete the securing brackets supplied (if included in the scope of the delivery); Making the securing brackets (if not in the scope of the delivery). Due to the great forces that develop, this
performance should be furnished according to the instructions of an expert (architect or structural engineer) in
accordance with the supplier's specifications; Making the chimney system with the connecting hole for the exhaust pipe (exception: metal chimney included
in the scope of the delivery); d) Draining the heating room and silo room with all the ducts and shafts required for installing the entire facility. e) Unloading the scope of the delivery from the truck unless the delivery has been expressly agreed with a crane
truck.
2.) Helpers during the installation of the burner system Providing a qualified helper to be available during the entire duration of the installation. Requirements for the helper:
a) Qualified
for installation work in steel and machinery construction (skilled at using hand tools)
b) Physically sturdy
no restriction to lifting loads, no restrictions to working up to heights of 3.0 m above the floor, no restrictions to hearing or sight
c) Communicative and mentally stable
good knowledge of German and mentally stable such that he can immediate follow the installation supervisor's verbal safety instructions
d) Available
during the agreed week days (Monday to Friday) from 7:00 AM until 6:00 PM
e) Equipped
with protective equipment according to the applicable regulations on industrial safety
3.) After the installation of the burner system
a) Installation of the control cabinets delivered and/or the control modules Unless expressly agreed otherwise, these must be installed by the authorised electrician. b) Installation of weather sensor and probes for the heat consumers in the scope of delivery: These have to be installed by the authorised electrician. c) Establishing the supply of electric current and carrying out the wiring unless expressly agreed otherwise:
Electric input, 3 x 400 V, PE, N with fuses on control cabinet.
Connecting cables between the control cabinet and the various motors and control units, connected on both
ends so as to be ready for operation. d) Installation of the uninstalled water-bearing components included in the scope of delivery: Water-bearing components included in the scope of delivery not factory connected, such as pumps, valves,
thermal run-off safety valves, accumulators, etc., must all be installed by the authorised heating engineer. e) Sealing all the openings between the burner room and the fuel storage space, doing so according to the fire
prevention regulations.
Page 33
Spec Sheet
Installation Services
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
We reserve the right to make technical changes.
1120/b-2
2005-01-31_E
Installation (two KÖB fitters) [Art. No. IMO-2]
Performance provided by the contractor (supplier): Furnishing the entire scope of the delivery. Installing the burner system, incl. all the machinery parts and facility components contacted by fuel and exhaust gas for the scope of delivery cited. Also included is the installation of all the switches, probes and sensors supplied (exceptions: weather sensors and heat consumers).
The installation will be carried out by two experienced fitters. Price, incl. travel, expenses and overnight accommodation. Performance provided by the client (buyer):
1.) Prior to installation of the burner system a) Equipping of construction site as follows: Paved access road to the construction site; 230-V current supply line and, if necessary, 400 V for electric installation tools (welding apparatus); b) General construction work, as follows:
Making all the installation holes required for the installation; Making the cement foundations and recesses for refill access lids and casings of extraction equipment;
Pits and breakthroughs for fuel conveying equipment c) Construction work in particular as follows: Hydraulic sliding bar extraction system: Moving and setting in concrete the securing brackets supplied (if included in the scope of the delivery); Making the securing brackets (if not in the scope of the delivery). Due to the great forces that develop, this
performance should be furnished according to the instructions of an expert (architect or structural engineer) in
accordance with the supplier's specifications; Making the chimney system with the connecting hole for the exhaust pipe (exception: metal chimney included
in the scope of the delivery); d) Draining the heating room and silo room with all the ducts and shafts required for installing the entire facility. e) Unloading the scope of the delivery from the truck unless the delivery has been expressly agreed with a crane
truck.
2.) After the installation of the burner system a) Installation of the control cabinets delivered and/or the central control modules Unless expressly agreed otherwise, these must be installed by the authorised electrician. b) Installation of weather sensor and probes for the heat consumers in the scope of delivery: These have to be installed by the authorised electrician. c) Establishing the supply of electric current and carrying out the wiring unless expressly agreed otherwise:
Electric input, 3 x 400 V, PE, N with fuses on control cabinet.
Connecting cables between the control cabinet and the various motors and control units, connected on both
ends so as to be ready for operation. d) Installation of the uninstalled water-bearing components included in the scope of delivery: Water-bearing components included in the scope of delivery not factory connected, such as pumps, valves,
thermal run-off safety valves, accumulators, etc., must all be installed by the authorised heating engineer. e) Sealing all the openings between the burner room and the fuel storage space, doing so according to the fire
prevention regulations.
Page 34
Spec Sheet
Wood Fuels
Minimum Requirements / Information
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes
1010/d-1
2005-10-01_E
A prerequisite for approval is the express permission for such by the public authority responsible. For claims to the warranty according to Section 11 of our General Terms and Conditions of Delivery, wood fuels have to meet the following conditions. If those conditions are not met, then approval is possible with restrictions (warranty, maintenance, operational safety) with a written statement by the manufacturer in reference to the facility.
1) Non-combustible substances contained
No wood fuels may contain any foreign bodies, such as pieces of metal, stones, masonry remnants or plastics. Nor must the following limits (per kg of dry fuel) for non-combustible substances contained (ash analysed at a temperature of 815°C) be exceeded or fallen short of: Limit Comparison with untreated forest wood
1.1) Chlorine Cl: max. 300 mg/kg 10 mg/kg
1.2) Sulphur S: max. 1000 mg/kg
120 mg/kg
1.3) Total Cl, S: max. 1000 mg/kg 130 mg/kg
1.4) Ash content, total: max. 15.0 g/kg 5.0 g/kg
1.5) Alkali oxides in the ash (K
2
O and Na2O): max. 1.0 g/kg 0.35 g/kg
1.6) Sintering point of the ash: min. 1000°C approx. 1200°C Consequence of substantial overstepping of limits (1.1, 1.2, 1.3, 1.5, 1.6): a) Hot-gas corrosion in the heat exchanger Special maintenance instructions for heat exchanger Shortened service life of heat exchanger b) Early sintering and melting of the ash Special maintenance instructions for firing, Increased maintenance costs (firing, boiler door) If the maintenance instructions are not followed, a process will be created that builds up in a negative fashion with: Cinders change the airflow Temperature peaks more slag etc, until there is fast destruction of the refractory materials
1.7) Additives in remnant and used wood: Free of heavy metals and halogen compounds
2) Superfines & dust (wood particles smaller than 1.0 mm as per ÖNORM M 7133)
2.1) Without pre-dryer, max. 10.0% of the total mass; consequence of substantial overstepping of limit: Temperature peaks Slag formation Even higher temperature etc, to the point of destruction; Special maintenance instructions for firing; Elevated values are especially critical for remnant wood in combination with elevated values as per 1.1, 1.2
2.2) For forest wood chips with pre-dryer, max 4.0% of the total mass; consequence of substantial overstepping of
limit: Moving the exhaust air lines Special maintenance instructions for cleaning exhaust air line
3) Origin and treatment
3.1) Forest wood and plantation wood (complete trees and trunk wood untreated)
Mature wood from trunks and branches, untreated, chopped as billet wood or chips
3.2) Compressed wood, pellets (conforming to standards, such as: ÖNORM M 7135)
Untreated wood with limited bark content, compressed by machine and calibrated
3.2) Increased proportion of bark, tree cuttings from roadside trees (untreated)
Remnants from the forestry and sawmill industries or from conservation of the countryside (elevated ash content).
3.3) Remnants from derived timber products
Usually a mixture of untreated and treated wood in the form of shavings from processing machinery and chips from choppers that run slowly. In cases of elevated proportions of dust and/or limited storage volumes, these shavings are compressed into briquettes.
3.4) Used wood
This is essentially untreated wood that has been used prior to its energetic utilisation (e.g. pallets). It is reduced in size by shredders for thermal utilisation. The metal parts have to be removed afterwards (by magnetic separators).
4) Particle size: adjustment of the conveyor augers
4.1) G30/G50 chips from untreated wood as per ÖNORM M 7133:
made by fast-running and cutting tools; max. coarse fraction with cross-section and length G 30 of 20% max. 3 cm
2
max. 8.5 cm;
G 50 of 20% max. 5 cm
2
max. 12 cm; Required cross-sections of the loading: depends on the boiler output: up to 150 kW up to 500 kW from 500 kW Conveyor auger D min. 12 cm; min. 15 cm; min. 20 cm Drop cross-section A min. 175 cm2 min. 300 cm2 min. 600 cm
2
Page 35
Spec Sheet
Wood Fuels
Minimum Requirements / Information
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
Subject to technical changes
1010/d-2
2005-10-01_E
4.2) Chips not from the forest; origin as per 3.2, 3.3, 3.4; briquettes, origin as per 3.3
Size essentially as per ÖNORM M 7133 G50, additionally, however:
- Fraction of one-offs max. 5% with cross-section of max. 5 cm² up to a length of max. 16 cm
- Frayed surface by chopping tools (shredders) or slow-running choppers
- Briquettes, diameter max. D 60 mm (hydraulic compressors, pressure geared to loading system) Conveyor augers diameter min. 20 cm; drop-off route, rotary valve cross-section min. 600 cm
2
Consequence of overstepping particle size:
- Extra expenditures for correcting malfunctions
- Shortened service life of the conveyor augers and drives
5) Bulk density S (kg/m³), water content W (%), size G (mm) as per ÖNORM M 7133
In automatically loaded boiler plants, the wood fuels that come to be used should be individually listed in offers and
orders as follows: a) S 130 W10 to W20 G30/50 Sawdust, untreated (planing shop) b1) S 200 W20 to W35 G30/50 Sawdust, untreated (sawmill) b2) S 200 W20 G30/50 Forest wood chips, soft, untreated c1) S 250 W20 to W35 G30/50 Forest wood chips, soft, untreated c2) S 250 W35 to W50 G30/50 Sawdust, untreated (sawmill) d1) S 300 W20 to W35 G30/50 Forest wood chips, soft/hard, untreated d2) S 300 W35 to W50 G30/50 Forest wood chips, soft, untreated e1) S 350 W20 to W35 G30/50 Forest wood chips, hard, untreated e2) S 350 W35 to W50 G30/50 Forest wood chips, soft/hard, untreated e3) S 350 W50 to W60 G30/50 Forest wood chips, soft, untreated f1) S 400 W35 to W50 G30/50 Forest wood chips, hard, untreated f2) S 400 W50 to W60 G30/50 Forest wood chips, soft/hard, untreated g) S 130 less than W15 G30/50 Shavings & chips from wood remnants, dry, mixed h) S 200 less than W15 G30/50 Shavings & chips from wood remnants, dry, mixed i) S 250 less than W15 G30/50 Shavings & chips from wood remnants, dry, mixed j) S 350 less than W15 G30/50 Briquettes from wood remnants D 40 to 60 mm k1) S 650 less than W10 Pellets conforming to standards, untreated D 6 to 10 mm k2) S 650 less than W10 Pellets conforming to standards, untreated D 11 to 15 mm
6) Maximum water content allowed, W, (percentage by weight of the total mass)
The maximum water content allowed in the fuel when entering the furnace should be taken from the spec sheets for the furnace series. With a pre-dryer installed between the furnace and the fuel storage site, extra water content can be in the fuel stored (see specifications in reference to the order). The water content influences the maximum furnace output possible, the heat emission required to the pre-dryer and thus the maximum heat emission possible to the consumers.
7) Other information
7.1) Ash and cleaning
Untreated wood without bark has a proportion of ash less than 0.5% of the fuel mass supplied. All the specifications regarding cleaning involved are based on untreated wood with bark attached with an ash amount of 0.8%. The cleaning and maintenance involved for other wood fuels should be adapted according to the amount, the specific weight and the behaviour of the ash.
7.2) Changing fuels
A great change in fuel quality, such as bulk density, water content, dust proportion or ash content might make a manual correction of the firing parameters necessary (see Operating Manual).
8) Non-woody fuels from biomass
Non-woody fuels from biomass, such as needles, foliage, grain, straw, fruit pits, etc, are usually unsuited as fuel for trouble-free operation and thus are not approved.
9) Wood fuels: rules, regulations and standards
Germany: 1
st
BImSchV1 dated 14 Mar 97, amended on 2 Aug 2001; page: Fuels nos. 5 to 7 Austria: FAV dated 18 Nov 1997 "Feuerungsanlagenverordnung" (Furnaces Act § 3.(1) 3. Solid Fuels Switzerland: Luftreinhalteverordnung LRV (Swiss Clean Air Act) dated 16 Dec 1985 (Standing: 28 Mar 2000) DIN 51731 Compressed Wood from Untreated Wood (1993) ÖNORM M 7135 Compressed Wood from Untreated Wood or Untreated Bark (1998) ÖNORM M 7136 Wood Pellets, Quality Assurance, Transport Logistics and Storage Logistics ÖNORM M 7133 Wood Chips for Energetic Purposes (1998) EN 303-5 Heating Boilers for Solid Fuels, Table 8 "Test Fuels“ CEN/TS 14961 Solid Organic Fuels
1
BImSchV = Bundes-Immissionsschutzverordnung [German Federal Emissions Control Act]
Page 36
Data sheet
General Terms of Delivery
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
All rights reserved for technical changes
1000-1
2005-01-31_E
1) Liability on Orders of Confirmation, Altering and Cancelling Orders
1.1) If no other agreement exists, the confirmation of order determines the contents and the time of delivery. If the technical specifications of individual parts deliv­ered are not restated in the confirmation of order, then the technical specifications stipulated in the last bid are valid.
1.2) Should in addition to the confirmation of order, the customer's order be valid, it is noted on the supplier's confirmation of order according to priority.
1.3) If within 10 days of sending the confirmation of order, no objection is raised, then the order is regarded as accepted. With terms of deliveries of less than 30 days, the window for objections is narrowed to 30% of the terms of delivery.
1.4) Altering and cancelling orders after the term of objec­tion has expired, is only possible with the written con­sent of the supplier. Any additional cost is to the buyer's account.
2) Prices
2.1) The listed prices of the supplier (price lists) may be changed at any time without prior notice.
2.2) The listed prices of the supplier are ex-factory prices and do not include Value Added Taxes (VAT).
3) Illustrations, Properties and Technical Terms
All technical data, illustrations, measurements, dia­grams and weights specified in bids, remain non­binding until they are part of a binding documentation delivered in connection with an order of confirmation. All rights for construction related changes remain re­served. Materials may be replaced by equivalent al­ternatives.
4) Copyrights and Ownership of Technical Drawings and Documentations
Technical drawings and documentation that are handed to the buyer but do not form an integral part of the equipment and its applications, remain the property of the supplier. Only with the written consent of the supplier, may documents be passed on to third parties in a changed form or in the original form.
5) Copyrights and Ownership of Control Programs
Control programs used to control the equipment re­main the property of the supplier. With the full pay­ment of the equipment, the buyer receives life-long, unrestricted user rights to the control programs.
6) Terms of Delivery
6.1) Agreed upon terms of delivery are binding.
6.2) Equipment related preparations of the delivery site must be made before delivery of the equipment. Clarifications on the dimensions of the site (to adapt mountings and fittings of the equipment to the site, the following minimum terms of delivery are required:
14 days for feed worm up to D 150 mm
42 days for all other parts
Should it not be possible to make these preparations within the stated minimum terms and should the sup-
plier not be at fault, then the supplier is relieved of all liabilities of the term of delivery.
6.3) The supplier reserves the rights to hold back on the delivery should the agreed terms of payment not be met by the buyer.
6.4) Should any additional cost arise due to the delay in delivery, a mutually acceptable settlement of the cost to the buyer should be negotiated between the con­tract partners.
6.5) Should ordered equipment not be accepted at the agreed term of delivery, the supplier has the right to invoice the equipment to the buyer. Any additional cost arising from storage should be negotiated and settled between the contract partners
6.6) With on demand orders, the supplier reserves the right to only start with the production of the equipment after the receipt of the on demand order.
7) Shipment /Transportation
7.1) The supplier uses the type of packaging materials and means of transportation he deems suitable.
7.2) If no other agreement exists, the equipment is sold ex-factory. Furthermore, the INCOTERMS of the day of the contract signing is valid.
7.3) Should parts of the equipment be shipped individually at the buyer's request, then the additional cost will be to his account.
8) Installations by the Supplier
8.1) Has the mode of transportation and installation of the equipment been agreed upon, then the buyer is obli­gated to prepare the installation site on time and in the manner stipulated. These required preparations are listed in the confirmation of order under the posi­tion "Installation".
8.2) In general, a paved pathway suited for trucks that bring the equipment to the site must be prepared.
8.3) Furthermore, before installation starts, the masonry, carpentry and other preparatory work has to be moved along far enough so that upon delivery of the equipment, the installation technicians can take up their duties right away and carry them out without in­terruptions.
8.4) Should installation have to be interrupted due to lack of preparedness of masons, carpenters, etc. the buyer then must properly store the uninstalled equipment and protect it as if it was his own property
The cost arising from the delay and additional travel expenses of the installation technicians are to the buyer's account.
9) Inspection/Complaints during Handover
9.1) The buyer is obligated to inspect the goods immedi­ately upon receipt.
Should the goods not correspond to the items on the delivery note, or in case of visible damage to the de­livered goods, the buyer has to mark it on the delivery note. His failing to do so, validates the shipment of the items delivered.
9.2) A complaint outside of the terms voids the supplier's warranty.
Page 37
Data sheet
General Terms of Delivery
KÖB & SCHÄFER GmbH, Flotzbachstr. 33, A-6922 Wolfurt, Tel. +43/5574/6770-0, Fax 65707, E-Mail: office@koeb-schaefer.com
All rights reserved for technical changes
1000-2
2005-01-31_E
9.3)Should the buyer desire a handover inspection, he has to have a written agreement to that end and all additional cost is to his account.
Should the handover inspection for whatever reasons (that the supplier needs not stipulate), be delayed, then the specifications that are to be checked shall count as met until the opposite is proven. Complaints do not void terms of payment.
10) Complaints on goods where the damage was not discernable at delivery
Complaints on goods where the damage was not dis­cernable at delivery (analogue to the procedure in point 9), should be made as soon as detected, latest however before the warranty runs out according to point 11.
11) Warranty/Starting Point and Duration
The equipment can only function correctly within the warranty period, if the operational guidelines are ad­hered to.
The operational guidelines are an intrinsic part of the delivered equipment and essential to its correct op­erations. The operational guidelines are: a) The operating manual with the instructions on
operating the equipment.
b) The specifications of compatible fuels for the
burner. (Refer to 1010-1, minimum requirements on wood fuels, notices).
c) The handover protocol with the installation report
and the specifications of the fuel used at the
point of handover. d) Maintenance and service plan. e) Fulfilling and adhering to the legal framework. If these are maintained, the following warranty peri­ods are valid:
11.1) 5 years on seal warranty for burners and tanks
Warranty on water tightness of water bearing, welded construction such as the burner, heat storage tank and utility water heater (electric heater not included), is 5 years as of date of delivery.
11.2) 3 years on movable parts Warranty on the all movable parts, such as firebox door, fire-proof materials for coatings, grills, dedust­ers etc. is 3 years as of the date of delivery.
11.3) 2 years electrical, motorized movable parts
Warranty on all electrical parts, such as controls, con­trollers, sensors for drives and motorized movable parts such as drive motors, hydraulic units, hydraulic cylinders, pushrods, extraction and feed worm, sluice wheels, movable grills, valves, pumps, step down gearing, chain drives, blowers, fire protection door, motor covers etc. is 2 years as of the date of delivery.
11.4) Normal Wear, Oils and Lubricants
There is no warranty on parts subjected to normal wear such as seals, etc. Also oils and lubricants, such as hydraulic oils etc. carry no warranty. Normal wear is also present in the fireproof coatings (surface wear, wear around the edges, cracks etc) that do not
lead to any malfunction of the equipment- are not covered by warranty.
New parts carry the stipulated new parts warranty. No warranty extension on original parts that had no com­plaints.
12) Payment
12.1) Payment is done in accordance with the terms of payment. It is not acceptable to withhold or suspend payment because of complaints, outstanding credit notes or not agreed upon charges to the account of the supplier.
12.2) The terms of payment must be adhered to, even if minor, non-essential parts are missing in the delivery or must be reworked after delivery, as long as they do not impair the operations of the equipment.
12.3) Should the buyer fall behind in the payment schedule or not live up to certain agreed upon stipulations,
a) then the supplier may insist on the payment of
the outstanding amount in rates or delay agreed services
b) extend the terms of payment on the outstanding
amount
c) invoice the buyer with the entire outstanding
amount for immediate settlement
d) add the usual bank interest rates t the out-
standing amount or step away from the contract after granting the buyer a reasonable period of respite.
13) Liabilities
The supplier is not liable to the buyer for any losses occurred due to interruptions in production, financial losses, missed opportunities, breakdowns, lost con­tracts or any other economical transaction or for any indirectly occurred losses.
14) Limits of Liabilities
Acts of God are unpredictable occurrences beyond the control of either party and may be the cause the contract not being partially nor totally fulfilled. Neither party is then liable for breach of contract. Acts of God in this case are: Fire, conscription, confiscation, embargos, prohibition of currency transfers, rebellion, unavailable means of transportation, general lack of supply goods, limits set to energy consumption, plane crash, volcanic erup­tion, earth quake, avalanche, landslides, hurricanes, tidal waves, etc.
Page 38
EC-Declaration of Conformity
The PYRTEC underfeed heating system (burners for solid fuels)
The models: Pyrtec 530, Pyrtec 720, Pyrtec 950, Pyrtec 1250
were developed, constructed and manufactured solely by
KÖB & SCHÄFER GmbH Flotzbachstraße 33 A-6922 Wolfurt
The PYRTEC underfeed heating systems with solid fuel automatic feeder systems meet the requirements of the following guideline:
98/37/EC Machine guidelines  73/23/EWG Low voltage guidelines  89/336/EWG EMC guidelines
Applied standards:
EN 303-5, DIN 4702
Solid fuel burners, manual and automatic feeder systems.
EN 60335-1 / A-14:98 Safety standards for appliances for household and similar purposes.  EN50081 Part 1 and part 2, EN50082 part 1 and Part 2, EN55011, ENV50140, ENV50141,
EN61000-4-2, EN61000-4-4, ENV50140, ENV50141 Electro magnetic compatibility.
TRD 702
A complete technical documentation is included. The operation and installation manual is included in the language it was originally published in and in the language of the country to which it is delivered.
Wolfurt 01.01.2005
Date
Signed
Ing. Siegfried Köb
First name, Name
Manager
Function
Page 39
Page 40
Köb & Schäfer GmbH, Flotzbachstrasse 33, A-6922 Wolfurt
Tel +43 55 74 / 67 70-0, Fax +43 55 74 / 65 7 07
office@koeb-schaefer.com, www.koeb-schaefer.com
Verkaufs-Niederlassungen und dazugehörige Service-Außenstellen:
ZENTRALE:
Flotzbachstrasse 33, A-6922 Wolfurt Tel +43 55 74 / 67 70-0 Fax +43 55 74 / 65 7 07 office@koeb-schaefer.com
ÖSTERREICH – NORD / OST
A-4906 Eberschwang Tel +43 77 53 / 32 65 Fax +43 77 53 / 32 65 helmut.fuchsberger@koeb-schaefer.com
ÖSTERREICH – SÜD / OST
A-8230 Hartberg Greinbach Tel +43 33 32 / 64 2 12 Fax +43 33 32 / 63 6 16 martin.nussdorfer@koeb-schaefer.com
VERTRIEBSTOCHTER SCHWEIZ
KÖB Wärmetechnik AG CH-9430 St. Margrethen Tel +41 848 / 87 08 10 Fax +41 848 / 87 08 11
SCHWEIZ – ZENTRAL / OST
CH-9243 Jonschwil Tel +41 71 / 92 38 2 80 Fax +41 71 / 92 38 2 82 josef.meier@koeb-schaefer.com
SCHWEIZ – ZENTRAL / NORD
CH-4704 Niederbipp Tel +41 32 / 63 30 7 10 Fax +41 32 / 63 30 7 11 adrian.rippstein@koeb-schaefer.com
DEUTSCHLAND – SÜD / WEST
D-72639 Neuffen Tel +49 70 25 / 80 42 Fax +49 70 25 / 83 69 6 gerald.sieler@koeb-schaefer.com
DEUTSCHLAND – SÜD / MITTE
D-89278 Nersingen Tel +49 73 08 / 91 00 10 Fax +49 73 08 / 52 66 hans.amann@koeb-schaefer.com
DEUTSCHLAND – SÜD / OST
D-82549 Königsdorf Tel +49 8179 / 92 95 65 Fax +49 8179 / 92 95 66 roland.metzner@koeb-schaefer.com
DEUTSCHLAND – NORD / WEST
D-44579 Castrop-Rauxel Tel +49 23 05 / 7 38 91 Fax +49 23 05 / 8 37 62 koeb-nw@t-online.de
DEUTSCHLAND – MITTE / NORD
D-37242 Bad Sooden-Allendorf Tel +49 56 52 / 95 80 35 Fax +49 56 52 / 91 90 214 w.schneider.kuelte@t-online.de
DEUTSCHLAND – NORD / OST
D-16727 Oberkrämer/ OT Eichstätt Tel +49 33 04 / 31 70 8 Fax +49 33 04 / 31 70 8 wolfgang.ratzka@koeb-schaefer.com
ITALIA-Koeb & Schaefer Italia S.r.l.
I-36063 Marostica Tel +39 0424 8 10 50 Fax +39 0424 47 34 45 italia@koeb-schaefer.com
LUXEMBOURG
D-72639 Neuffen Tel +49 70 25 / 80 42 Fax +49 70 25 / 83 69 6 gerald.sieler@koeb-schaefer.com
FRANCE
F-04300 Forcalquier Tel. +33 492 / 73 10 80 Fax: +33 492 / 73 10 80 france@koeb-schaefer.com
FRANCE - OVEST
F-79160 Coulonges/L‘Autize Tel. +33 549 / 06 06 60 Fax +33 549 / 06 00 60 energie79@wanadoo.fr
1 Serviceleitstelle Zentrale Wolfurt
Köb & Schäfer GmbH, Flotzbachstrasse 33, A-6922 Wolfurt Tel +43 55 74 / 67 70-0, Fax +43 55 74 / 65 7 07, office@koeb-schaefer.com
2 Serviceleitstelle für Italien
Köb & Schäfer Italia S.r.l., I-36063 Marostica Tel +39 0424 78 10 50, Fax +39 0424 47 34 45, italia@koeb-schaefer.com
3 Serviceleitstelle für Frankreich
F-04300 Forcalquier, Tel. +33 492 / 73 10 80, Fax: +33 492 / 73 10 80 france@koeb-schaefer.com
SERVICE – EST: Electromatic – sarl, F-67550 Vendenheim Tel +33 607 / 64 06 31, Fax +33 38 / 86 93 7 60. servicefance@koeb-schaefer.com
Verkaufsorganisation mit eigenem Service
NORGE AS Morgan
N-3933 Porsgrunn Tel. +47 355 / 693 00 Fax: +47 355 / 693 15 fyk@asmorgan.no
NEDERLAND / BELGIE LVB Wood Drying + Energy Systems BV
NL-4141 BE Leerdam Tel. +31 345 / 61 97 88 Fax: +31 345 / 61 69 05 office@lvb-wood.nl
UNITED KINGDOM 3G Energi
UK – TD5 7BH, Kelso Tel. +44 1573 22 91 98 Fax. +44 870 706 2555 enquiries@3genergi.co.uk
SVERIGE FBP Fastbränslepannor Bengt Nilsson AB
S-65350 Karlstad Tel. +46 54 53 69 87 Fax. +46 54 53 18 43 bengt.nilsson@fbp.se
IRLAND Clearpower Ltd.
Dublin 2 Tel. +35 31 66 90 979 Fax. + 35 31 66 90 978 info@clearpower.ie
CANADA Fink Machine Inc.
Enderby B.C Tel. (001) 250 83 80 077 Fax. (001) 250 83 800 68 fink@jetstream.net
1
1
1
1
1
1
1
1
1
1
2
3
1
Loading...