KOB 3010-1, Pyromat DYN 45, Pyromat DYN 65, Pyromat DYN 85 Spec Sheet

Spec Sheet
Burner System Loader System
PYROMAT-DYN
1
Subject to technical changes
3010-1
2009-03-01_GB
Description:
The PYROMAT-DYN is a boiler with patented double combustion chamber. Which means that the burner system enables optimized operation with automatic loading (shavings, chippings from waste wood, wood chippings, max. W35; G50) and may also be used with logs. A large loading shaft with loading lid and separate grid has been fitted in front of the main combustion chamber to make loading wood easy. In automatic operation, the burner system is suitable for all dry to moist wood fuels (max. W35). The control is integrated into the burner system with connector-ready cabling to the sensors and motors. Which permits simple and rapid installation. The PYROMAT-DYN has been tested and approved in accordance with the latest quality criteria in compliance with EN 303-5 heating boilers for solid fuels, CE certification as per European Machinery Directive and continuous quality assurance by TÜV.
Max. flow temperature: 100°C Max. operating pressure: 3.0 bar Electric connection: 3 x 400V Safety heat exchanger: Built into the boiler
Function:
- In manual operation, chopped wood and waste wood are degassed on the incineration grate situated before the main combustion chamber. Simultaneous operation with automatic loading is not possible.
- In automatic operation the feed auger conveys the material to be burned into the main combustion chamber for degasification.
The fasteners for the burn-back sensor and the thermally operated extinguisher valve are situated on the conveyor
pipe. Above the auger, there is a metering container with a light barrier to ascertain the level of the fuel isolating layer required according to TRD 414.
- In automatic operation the material to be incinerated is ignited automatically by an electric hot air blower.
The combustion gases are entirely burned out in the afterburn chamber together with secondary airflow.
- The ash is mechanically removed from the main combustion chamber.
- In the upright pipe heat exchanger, the thermal energy from the combustion gases is transferred to
the boiler water. The vertical surfaces of the heat exchanger are regularly cleaned by motor-driven, moving coil springs.
- The speed-controlled exhaust blower was specially designed for operation in wood heating systems and is very quiet.
- The negative pressure created by it produces a high degree of safety against burn-back in automatic operation and a
convenient feed function in manual operation.
- An integrated heat management system (accumulator-temperature-guided with return circuit valve) enables the best possible controlled operation.
Scope of delivery:
- Boiler with double combustion chamber, ash pan, kindling and cleaning utensils, coil springs for the heat exchanger cleaning system, mechanical drive with position sensor for removing the ash from the main combustion chamber.
- Exhaust blower, plug-and-play
- Integrated ECOTRONIC control system (decentralised microprocessor system via CAN-bus), consisting of:
Boiler control panel, control module for mounting preferably on a wall, bus cable for the drive motors wired to output plug
- Feed auger with isolating layer, incl. Starttec drive via CAN-bus (including data transmission line) for gentle start-up, automatic reversing and overload safeguard, light barriers for combustion chamber and metering container
- Automatic ignition system
- Burner group ready-installed on connecting flange, consisting of burner pump, two blockage units
Burner control valve, forward and return flow sensors incl. fittings.
- Three KTY heat accumulator sensors, incl. dipping shell (1/2" x 280 mm long) wired together to plug
- Four-pin master switch, uninstalled (for installation near the control module)
ACCESSORIES for PYROMAT-DYN (Article KPM-…) at extra charge:
Name Article Text Sizes Use
Reduction exhaust connection KPM-… 3110 3110 existing chimney 180 mm dia. Exhaust blower-intake port 90° KPM-… 3110 3110 special exhaust gas conveyance Exhaust gas deduster KPM-… 3110 3110 optional De-ashing into the container 20 L KPM-DYN-AS 3200 3200 optional ECO function for PYROMAT-DYN LSR-DYN 3200 - for use with logs; incl. storage Error report 230 V ECO-ZA 3200 - optional External requirements ECO-ANF 3200 - optional Discharge systems ADE/ADF 3300 3300 material transport silo to boiler Heater control, module extensions ECO-… 4000ff - optional Data cable for operating module ECO-… 4020 - required Boiler safety devices K-… 4500 - optional Extinguishing equipment K-… 4550 4550 optional
Spec Sheet
Burner System Loader System
PYROMAT-DYN
1
Subject to technical changes
3010-2
2009-03-01_GB
Schematic diagram with ECOTRONIC
a) DYN with reduced log operation (standard with accumulator as hydraulic switcher)
b) DYN with full ECO-function in log operation (accumulator volume as per EN 303-5 – see Spec Sheet 3950)
With this variation, the heat accumulator is incorporated by a storage control valve [Art. No. LSR-DYN-]
ECOTRONIC with heating control unit
The ECOTRONIC can be expanded by a great number of heating control units (heat consumers, auxiliary heat generators) (refer to spec sheets, Category 4). The operation of the heating control units is all carried out in the control module for the burner system. Each controller is operated by a separate pushbutton.
For ECOTRONIC expansion possibilities, refer to spec sheets, Category 4
PYROMAT-DYN with integrated heat distributor
One heat distributor with two or three consumer groups can be integrated with the PYROMAT-DYN boiler. In this design with the manifold attached, the boiler forms a compact overall system (refer to Spec Sheets 4600).
+
F8
OK
-
F7
>
KÖB
F6F5
>
<
F3 F4F1 F2
>
accumulator as
hydraulic switcher
accumulator
additional
heat generator
3
21
heat consumer control module
control system module
ECO-RM-00
Pyromat-DYN
control module
heat consumer
additional heat generator
1 2 3
control system module
ECO-RM-00
accumulator2accumulator
1
Pyromat-DYN
+
F8
OK
-
F7
>
KÖB
F6F5
>
<
F3
F4F1 F2
>
Loading...