KNX Iddero Verso User Manual

Iddero Verso
User manual
Version: 1.0
170119-01
Contents
1 Introduction 5
1.1 Product overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Programming mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2 Functional description 8
2.1 Visualisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.1.2 Home page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.1.3 Menu page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.1.4 Control pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.1.5 Favorites page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1.6 Settings pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1.7 Page layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
2.1.8 Access control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
2.1.9 Power saving mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.1.10 Touch gestures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
2.2 Time schedules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.2.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2.2.2 Timer groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.2.3 Editing of timer programs . . . . . . . . . . . . . . . . . . . . . . . . . 22
2.3 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.3.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
2.3.2 Alarm visualisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
2.3.3 Alarm log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
2.4 Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.4.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.4.2 Room temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.4.3 Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
2.4.4 Heating and Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
2
2.4.5 Control algorithms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
2.4.6 Additional heating and cooling . . . . . . . . . . . . . . . . . . . . . . 39
2.5 Multifunction inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
2.5.1 Binary inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
2.5.2 Temperature probe inputs . . . . . . . . . . . . . . . . . . . . . . . . . 41
2.6 Scene controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
2.6.1 Internal vs. External scenes . . . . . . . . . . . . . . . . . . . . . . . . 41
2.6.2 Scene actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
2.6.3 Recalling scenes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
2.6.4 Storing scenes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3 Configuration 43
3.1 General considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.2 Main . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.2.2 Internal temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . 45
3.2.3 Timer groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.3 User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.3.2 Power saving mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3.3.3 Access control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3.3.4 Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3.3.5 Settings pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3.3.6 Favorites . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
3.3.7 Touch gestures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
3.4 Control Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3.4.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
3.4.2 Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
3.5 Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
3.5.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
3.5.2 Room Temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
3.5.3 Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
3.5.4 Operating Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
3.5.5 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
3.5.6 Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
3.6 Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
3.6.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
3.6.2 Binary - Push button . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
3.6.3 Binary - Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Contents
3
3.6.4 Temperature probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
3.7 Scenes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
3.7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
3.7.2 Scene actuator N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
4 Advanced topics 97
4.1 Product customization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
4.1.1 Background images . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
4.1.2 Custom languages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
4.2 Firmware updates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
5 Annex 99
5.1 Communication Objects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Contents
4

Introduction

1.1 Product overview

Iddero Verso is an advanced room controller with a 4,3" capacitive touch display designed for visualisation and control of KNX installations. It is available in white or black finish, and can be installed in portrait or landscape mode.
Function highlights:
• Up to 48 control functions, organized in 6 configurable pages
• User editable favorites page
• Custom background images
• Weekly time schedules (up to 48 channels, 4 programs / channel)
• Alarm monitoring (up to 48 alarms) with event log
• Touch gestures: Up to 5 quick actions without leaving power saving mode
• Internal scene controller
• Two independent thermostats
Four multi-function inputs, individually configurable as binary or temperature probe inputs
• Built-in temperature sensor
• Real-time clock (RTC) with backup battery
• Integrated KNX bus coupling unit
• Ultra-low power consumption
1
1.2

Connection

The following figure shows connectors and other elements in the backside of Iddero Verso.
5
1. Power supply connector
2. KNX programming button
3. KNX programming LED
4. KNX TP1 bus connector
5. Built-in temperature sensor
6. USB connector
7. Multifunction inputs connector
8. Replaceable RTC backup battery
In order to bring up the device, connect the KNX bus to the KNX TP1 connector (4), and a separate power supply (12-30 VDC) to the power supply connector (1). Please refer to the product datasheet for detailed information on the power supply requirements.
Note
Do not connect the KNX bus directly to the power supply connector (1); a separate power supply is required.
1.3

First boot

As soon as the power supply is connected, the device will boot. Within a few seconds, the Iddero logo will appear on the screen. Then, the Synchronization page will be shown.
1.3
First boot 6
The Synchronization page will remain onscreen as long as the device has not yet been pro­grammed with application data from ETS. This page is also displayed if the KNX bus is discon­nected, or while the device is being reprogrammed.
If the KNX bus is connected and the device has already been programmed, the Synchronization page will disappear and the Home page will be shown automatically.
1.4

Programming mode

In order to put the device in programming mode, press the KNX programming button (2). While the device is in programming mode, the KNX programming LED (3) will be on.
1.4
Programming mode 7

Functional description

Alarms
Settings
pages
Home Menu
Time
schedules
Control
pages
Favorites
Default
page
(configurable)

2.1 Visualisation

2.1.1 Overview

The Iddero Verso user interface is organized into pages. This includes both configurablefunction pages (also called “control pages”) and fixed function pages, such as the Menu or settings pages. The following diagram provides a high level view of the navigation structure:
2
8
The following screenshots show the main elements of the user interface in both portrait and
1
1
3
3
2
2
landscape modes:
The status bar (1) at the top of the screen shows the name of the current page, and, optionally, the current time and temperature.
The main area of the screen (2) shows the icons, buttons, and user interface elements relative to the current menu or function page.
The navigation bar (3) at the bottom of the page shows icons to navigate through the user interface. The set of displayed icons will depend on the available navigation options in each page; these are summarized in the following table:
Icon Meaning
Go to the Menu page. If already in the Menu page, exit to Home page.
Return (go back one step)
Go to the Favorites page
Go to the settings pages
In control pages: Go to previous control page
In control pages: Go to next control page
2.1 Visualisation 9

2.1.2 Home page

Upon startup, the Home page is shown automatically. The Home page can be configured to show the current date and time, and also the current temperature. Tapping anywhere on the screen will automatically switch to the “default page”. The “default page” can be the Menu page, the Favorites page, or any of the configured control pages.
2.1
Visualisation 10

2.1.3 Menu page

The Menu page provides quick and easy access to all pages in the visualisation, including:
• Any of the configured control pages (up to 6)
• The time schedules pages
• The alarms pages
• The Favorites page
• The settings pages
2.1
Visualisation 11

2.1.4 Control pages

Control pages contain up to 8 configurable widgets, known as “components”. Available compo­nent types include the following:
• Indicators
• Indicators with alarm function
• Push buttons
• Double push buttons
• Regulation bars
• Rotary controls
• RGB and RGBW controls
• Numeric keypads
• Dimmer controls
• Shutter controls
• Temperature controls
These are described in detail in section 3.4.2 Components on page 52.
For most component types, a timer function can be enabled. See 2.2 Time schedules on page 21.
Visualisation 12
2.1

2.1.5 Favorites page

In addition to the regular control pages, a “favorites” page allows end users to select up to eight commonly used components for quick access. Any of the configured components can be selected; see 2.1.6.4 Edit favorites page on page 16. The Favorites page can be reached from the Menu page or from any of the control pages.
2.1.6
2.1.6.1

Settings pages

The settings pagesallow end users to configure certaindevice functions, as well as user interface preferences.
Main settings menu
The following buttons are available in this page:
Preferences: Opens the Preferences page. See
System: Opens the System Settings page. See
Favorites: Opens the Edit Favorites page. See
2.1.6.2 Preferences page on page 14.
2.1.6.3 System settings page on page 15.
2.1.6.4 Edit favorites page on page 16.
Visualisation 13
2.1
Clean screen: Temporarily disables the touch screen for cleaning. Use a so cloth to clean the screen. Do not use abrasive cleaners or detergents.
2.1.6.2 Preferences page
The following buttons are available in this page:
Date & time: Allows setting the system date and time.
Language: Allows selection of the user interface language.
Buzzer: By default, the screen will beep when the user touches a user interface element.
• The buzzer is also used to signal that an alarm has been activated. Both beeps can be disabled here.
Brightness: Allows adjusting the brightness of the display.
Passwords: Allows setting the user and/or master passwords. See 2.1.8 Access control on page 19.
Power saving: Allows configuration of the inactivity timeouts used for power saving mode. See 2.1.9 Power saving mode on page 20
2.1
Visualisation 14
2.1.6.3 System settings page
The following buttons are available in this page:
Temperature probe: Allows adjusting the calibration oset for the internal temperature probe. The calibration oset is added to the temperature measured by the probe in order to compensate for the eect of local heat sources or air dras that might aect the measurement.
Info: Shows information about the device and the configuration. The following informa­tion will be shown:
Project name, if parametrized in ETSFirmware and application program versionSerial number of the deviceCurrent KNX address
USB: Allows advanced customization options. See 4.1 Product customization on page 97.
2.1 Visualisation 15
Defaults: Resets all settings to default values. Any user configuration will be discarded, including preferences, timer schedules, scene values, etc. The device will be le in the same state as if it had been just programmed from ETS. Note: The following settings are not aected by this option:
Current date and timeDisplay brightness
Reboot: Reboots the device.
2.1.6.4 Edit favorites page
This page allows end users to select up to eight components that will be shown in the Favorites page. A grid with eight positions will be shown. Touching any of the elements in the grid shows a list of all available components. The special list entry “[None]” can also be selected in order to clear the corresponding position in the grid.
2.1
Visualisation 16

2.1.7 Page layout

3
7
6
5
4
1 2
8
1 2
8
3
76
5
4
Many of the pages in the user interface are arranged as a grid that can contain up to 8 elements. The position of each element in the grid is shown in the following figure:
For certain pages, including the Menu page, the configurable control pages, and the Favorites page, several layout options are available.
Fixed positions: Each element is displayed in its natural position in the grid.
Flexible – center: Each row is horizontally centered. Empty rows are skipped; any remain-
• ing rows are then vertically centered.
Flexible – center + stretch horizontally: Similar to flexible – center, but all rows are horizon-
• tally stretched to fill the available screen width.
Flexible – center + stretch vertically: Similar to flexible – center, but all rows are vertically stretched to fill the available screen height.
Flexible – center + stretch in both directions: Similar to flexible – center, but all rows are
• horizontally stretched to fill the available screen width, then vertically stretched to fill the available screen height.
The following figure shows the resulting layout for each option in a grid where positions 1, 3, 4, 5, and 6 have been used.
2.1
Visualisation 17
1 2
3
4
5
1. Fixed positions
2. Flexible – center
3. Flexible – center + stretch horiz.
4. Flexible – center + stretch vert.
5. Flexible – center + stretch in both directions
2.1 Visualisation 18

2.1.8 Access control

Most pages in the user interface can be password protected with a 4-digit PIN code in order to prevent unauthorized access.
Two access control schemes can be configured: Either one single password is used for all password-protected pages (one access level), or two dierent access levels are defined (“user” and “master”). In the latter case, the minimum access level required for each page must be configured. It must be noted that access levels are hierarchical: The “master” password also allows access to pages that require “user” access level. The opposite is not true: The “user” password does not allow access to pages that require “master” access level.
When the user tries to access a protected page, a password dialog will be shown. A valid PIN code must then be entered in order to gain access to the page.
Current permissions remain in eect until the user returns to the Home page, either manually or automatically due to an inactivity timeout (see 2.1.9 Power saving mode on page 20).
2.1
Visualisation 19

2.1.9 Power saving mode

Aer a certain period of inactivity (no user interaction), the device will automatically return to the Home page. Once on the Home page, and again aer a certain period of inactivity, the device enters power saving mode.
During power saving mode, the display is automatically turned o and power consumption is minimized, even though all functions (such as time schedules, alarm monitoring, etc.) remain operational.
Both of these inactivity timeouts can be adjusted by the end user through the “Power saving” option of the Preferences page, or even disabled altogether.
Note
2.1.10
Disabling the power saving timeout is this may adversely impact the expected display lifetime.
Touching the screen automatically exits power saving mode. It is also possible to configure which page will be shown at this point: Either the Home page or the “default page” defined in the ETS configuration.
not recommended
for normal operation, since

Touch gestures

Iddero Verso supports the use of touch gestures for quickly executing up to five preconfigured actions. Touch gestures can be used while the device is in power saving mode, and also in the Home screen. The following gestures are detected:
• Swipe up
• Swipe down
• Swipe le
• Swipe right
• Multitouch gesture (touch the screen with more than one finger)
2.1
Visualisation 20
A dierent action can be configured for each gesture. When the touch gesture is detected, the associated action will be executed and the device will play a short confirmation sound.
Typical uses for touch gestures include switching on the lights on a dark room (the multitouch gesture makes this specially easy, as users just need to place their hand on top of the screen), or activating a “Welcome” or “Good bye” scene when entering or leaving home.
2.2

Time schedules

2.2.1 Overview

For most components in the visualisation it is also possible to enable a “timer function”. When the timer function is enabled, the end user can setup actions to be run at scheduled times. For example, a dimmer control can be programmed to switch on a lamp at 75% intensity every day from Monday to Friday at 20:00, and to switch it o at 23:00.
Each component for which the timer function is enabled supports up to four separate time programs, each of which in turn supports separate “start” and “end” actions.
2.2
Time schedules 21
The following parameters can be set by the user for each time program:
2.2.2
• Start and end actions
1
• Start and end action times
• Week days (SMTWTFS) when the program is valid
• Optionally, a date range (from-to) when the program is valid
The week days parameter can be used to specify which days of the week the program should apply to. The start and end dates make it possible to limit the weekly schedule to a specific period of the year. For example, users could define a program that would only run on weekends during the months of June, July, and August.

Timer groups

Each component enabled as a timer can be optionally added to one of four available “timer groups”.
Timer groups can be locked (temporarily disabled) by sending a KNX telegram to a specific communication object. While a timer group is locked, any scheduled actions for components associated to that timer group will not run. This makes it possible to disable a group of timers temporarily, for example during short vacations.
2.2.3

Editing of timer programs

Components for which the timer function has been enabled will show up in the “Time schedules” page, which can be reached from the Menu page.
1
In some cases, actions are fixed and cannot be modified; for example, in a push button component that has been configured to run a scene, the action is fixed (run the associated scene)
Time schedules 22
2.2
Selecting one component from the list shows the available programs:
2.2 Time schedules 23
The “Enable” checkbox allows to manually enable or disable any configured actions. Note that this checkbox will be disabled if the component belongs to a timer group that is currently locked.
Selecting a program shows the program edit page, where all the parameters for the timer program can be edited.
When a component has any scheduled actions enabled, a small clock icon will be shown both in the component itself and in the corresponding page button in the Menu page.
2.3

Alarms

2.3.1 Overview

Components configured as “Indicator with alarm” combine two functions: On one hand they behave as regular Indicators, and as such they can display status values for an associated communication object. In addition to that, they can also be used to detect alarm or fault conditions.
2.3
Alarms 24
For this, the component provides two additional communication objects: A “trigger” object,
Trigger
"No alarm" value
Acknowledge
Acknowledge
Trigger
OFF
ALARM
WAIT_ACK WAIT_OFF
"No alarm" value
and an “acknowledge” object.
When the “trigger” communication object receives an alarm value from the bus (the “alarm condition”), the alarm is activated. This is signalled both visually, in the user interface, and via the built-in buzzer device. The alarm will remain active until it has been acknowledged by the user and the trigger object has received the “no alarm” value.
Confirmation (acknowledgement) of the alarm can be done either manually, through the user interface, or by writing the acknowledge value to the “acknowledge” communication object.
The following flowchart shows the possible alarm states and the transitions between them:
• Initially all alarms are in the OFF state
• When the alarm condition is triggered, the alarm switches to the ALARM state
If an alarm is in the ALARM state and the alarm condition deactivates (the “no alarm”
value is received), it switches to the WAIT_ACK state until it is acknowledged.
If an alarm is in the ALARM stateand the user acknowledges it, it switches to the WAIT_OFF state until the alarm condition deactivates.
If an alarm is in the WAIT_ACK state and the alarm condition is triggered again, the alarm switches back to the ALARM state.
2.3
Alarms 25

2.3.2 Alarm visualisation

All configured alarms, along with their current state, can be checked at any time from the
“Alarms” page, which is reached from the Menu page.
Alarm state is shown as follows:
Symbols State
ALARM state WAIT_ACK state (waiting for acknowledgement) WAIT_OFF state (waiting for deactivation of the alarm condition) OFF (idle) state
From this page it is also possible to acknowledge individual alarms (by selecting each one and touching the “Acknowledge” ( ) button, or all pending alarms at once with the “Acknowledge all” ( ) button.
The alarm status is also shown in the visualisation with a small status led on the component itself. Also, for any page with active alarms, a small status led will be shown in the corresponding page button in the Menu page.
2.3
Alarms 26

2.3.3 Alarm log

An internal alarm log holds information about the latest 100 alarm events, including the event date and time. The alarm log can be reached from the alarms page (“Alarm log”) button. The following events are logged:
Symbol Meaning
The alarm is triggered The alarm is acknowledged, but the alarm condition persists (the “no alarm” value has not been received yet) The alarm goes idle; it has been acknowledged and the “no alarm” value has been received
The alarm log can be cleared at any time by means of the “Clear” button.
2.3
Alarms 27

2.4 Thermostats

2.4.1 Overview

Iddero Verso implements two independent thermostats for ambient temperature regulation, and thus can be used to control two independent HVAC zones. Each thermostat can be config­ured for heating, cooling, or both heating and cooling. The thermostat continuously compares the current room temperature with the current temperature setpoint, and controls operation of the heating and/or cooling actuators using a variety of control methods.
2.4.2
2.4.3

Room temperature

Current room temperature can be obtained from several sources:
• Temperature measured by the internal (built-in) temperature sensor
Temperature measured by an external temperature probe connected to one of the four available multifunction inputs
• Temperature provided by an external KNX device
For each thermostat, two dierent temperature sources can be selected and their temperature values averaged in order to calculate the actual room temperature. By combining the measure­ments from two dierent sources, it is possible to eectively filter local perturbations, e.g. from heat sources or air streams close to the sensors.

Setpoints

2.4.3.1 Operating Modes
The thermostat has four dierent operating modes: Comfort, Standby, Economy, and Building Protection.
Comfort mode the room at a pleasant temperature.
Standby mode lowered if in Heating mode, or increased if in Cooling mode), for example during short absences. This helps reducing energy consumption, but at the same time allows for quickly returning to the comfort mode at any time.
: The temperature setpoint is set to a value which enables normal use of
: The temperature setpoint is temporarily relaxed (i.e. the setpoint will be
Thermostats 28
2.4
Economy mode
Comfort
mode
Protection
mode
Economy
mode
Standby
mode
Overheating protection setpoint
Frost protection setpoint
Standby setp. (cooling)
Economy setp. (cooling)
Comfort setp. (cooling)
Comfort setp. (heating)
Standby setp. (heating)
Economy setp. (heating)
Temperature
: If the room will not be used for a longer period of time (for example during the night) the temperature setpoint can be relaxed even further in order to achieve higher energy savings.
Building protectionmode
: In this mode, the room thermostat is out of service. The room
will only be heated (or cooled) if the room temperature has reached values so low (or
high) that there is a risk of the installation being damaged from freezing or overheating.
Each of the four operating modes has its own temperature setpoint, as shown in the following diagram:
Setpoints can be defined in two ways: Absolute Setpoints and Relative Setpoints. Both methods are described next.
2.4.3.2 Absolute Setpoints
In the Absolute Setpoints method, setpoints for each operating mode are defined as absolute temperature values.
During operation, setpoints can be adjusted at any time by writing to the “Setpoint” commu­nication object. Note that this may trigger an automatic change of operating mode, if the thermostat determines that there is an operating mode that better fits the requested tempera­ture setpoint.
2.4
Thermostats 29
Example
Let’s assume the following configuration:
• Thermostat is configured for cooling operation
• Comfort setpoint is set to 25ºC
• Standby setpoint is set to 27ºC
If the thermostat is in initially in Comfort mode, and a value of 28ºC is written to the
“Setpoint” communication object, it will automatically switch to Standby mode.
A configuration parameter controls if and when temperature setpoint changes are stored per­manently:
Never: Temperature setpoint changes are never stored permanently.
2.4.3.3
Manually
: A “Save setpoint” communication object is enabled. By writing to this object, the current setpoint value will be stored as the default setpoint for the currently active operating mode, overwriting the initial value that was set in ETS.
Upon mode changes
: The current setpoint value will be automatically stored as the default setpoint for the currently active operating mode whenever there is an explicit change of operating mode, or when the thermostat switches from heating to cooling or
vice-versa2.
Setpoints can be restored to their original values (as defined via ETS parameters) at any time via the “Reset setpoints” communication object.
The above discussion applies to the Comfort, Standby, and Economy operating modes. It is not possible to manually adjust the setpoint for Building protection mode.
Relative Setpoints
In the “Relative Setpoints” method, the eective setpoints for the Comfort, Standby, and Economy operating modes are defined relative to a common base value (the according to the following equation:
base setpoint
),
Eective setpoint = Base setpoint + Mode oset + User oset
2
Additional considerations apply if the thermostat is configured for automatic switching between heating and cooling. See Additional considerations if Absolute Setpoints are used on page 34.
2.4 Thermostats 30
The base setpoint can be modified at any time through the “Base setpoint” communication object. The changed at runtime. The within a configurable range.
The user oset can be modified through two communication objects: Either directly writing an oset value to the “Setpoint oset” object, or by writing a “1” or “0” value to the “Setpoint step” object. The latter will result in progressive adjustments of +/- 0.5ºC in the current user oset.
A configuration parameter, “Reset user oset on operating mode changes” determines whether the current user oset should be reset to zero or carried over when the operating mode changes.
Finally, an additional “Reset oset” communication object allows to reset the user oset to zero at any time.
The above discussion applies to the Comfort, Standby, and Economy operating modes. The setpoint for the Building protection mode is always defined as an absolute setpoint, and cannot be changed at runtime.
mode oset
for each mode is configured via ETS parameters, and cannot be
user oset
allows additional adjustment of the current setpoint
2.4.3.4
Switching of operating modes
It is possible to toggle between operating modes at any time by writing to the associated communication objects. This can be done via a 1-byte object or via four 1-bit objects, one per mode. In turn, the 1-bit objects can be configured to work in “switch mode” or in “trigger mode”:
Trigger mode the corresponding operating mode.
Switch mode the operating mode. The new operating mode will depend on the current value of all four 1-bit switch objects. The possible combinations are shown in the following table (“-” means that the object value is ignored).
Protection object Comfort object Economy object Selected mode
1 - - Protection 0 1 - Comfort 0 0 1 Economy 0 0 0 Standby
: Writing a value “1” to one of the 1-bit objects will trigger the activation of
: Writing a value of “1” or “0” to any of the 1-bit of the objects will update
2.4 Thermostats 31
Note
Writing to the 1-byte mode object will always set the operating mode regardless of the value of the 1-bit objects, and vice-versa.
When a new operating mode is selected, the current temperature setpoint will be set to that of the new operating mode.
2.4.3.5
2.4.4
Forced protection mode
Under certain circumstances, it may be desirable to override the currently selected operat­ing mode, and force the thermostat into Protection mode. This is called “Forced protection” mode.
This could be the case, for example, when windows are opened in an hotel room. For this purpose, an additional “Window status” communication object can be enabled, which could be connected to e.g. a window sensor. When the activation value (“1”) is written to this object, the thermostat automatically switches into Forced protection mode, and will remain in this mode as long as the communication object does not receive the deactivation value (“0”).
If the thermostat receives a request to change operating mode while it is in Forced protection mode, the request will be processed, but the change will not be eective until Forced protection mode is deactivated.

Heating and Cooling

2.4.4.1
Each thermostat can be configured to operate in heating mode only, in cooling mode only, or in combined heating and cooling mode.
If combined heating and cooling operation is selected, switching between heating and cooling can be done either manually (by means of an associated communication object) or automati­cally.
Automatic switching
If automatic switching of heating/cooling is selected, the thermostat will automatically deter­mine the heating/cooling mode depending on the current room temperatureand the configured temperature setpoints.
Thermostats 32
2.4
If the thermostat is in
cooling mode
, it will automatically switch to Heating if the room
temperature falls below the corresponding setpoint3for Heating mode.
If the thermostat is in
heating mode
, it will automatically switch to Cooling if the room
temperature rises above the corresponding setpoint for Cooling mode.
Example
If the thermostat is in heating / standby mode, it will automatically switch to cooling when the room temperature rises above the setpoint configured for cooling / standby mode.
Changeover protection band
In order toavoid situations where the thermostatis continuously switching betweenheating and cooling, an additional parameter is introduced that allows defining a “Changeover protection band”. The thermostat will not switch between heating and cooling until the dierence between the room temperature and the current setpoint is greater than the protection band.
Example
Let’s assume the following configuration:
• Thermostat is currently in Cooling mode
• Current operating mode is Comfort
• Comfort setpoint for cooling is set to 25ºC
• Comfort setpoint for heating is set to 24ºC
• Changeover protection band is set to 2ºC
• Initial room temperature is 26ºC
Normally, the thermostat would switch to heating mode as soon as the room temperature falls below 24ºC. However, because the changeover protection band parameter is set to 2ºC, the switch to heating mode will only happen when the room temperature falls below 23ºC.
3
The setpoint that is considered is the one corresponding to the same operating mode that is currently active
(comfort, standby, economy, protection) but for Heating mode.
Thermostats 33
2.4
Additional considerations if Absolute Setpoints are used
In order to avoid malfunction of the thermostat, if the Absolute Setpoints method is used with automatic switching between heating and cooling, an additional limitation is introduced regarding permanent storage of setpoint changes. Namely, the device will always ensure that the comfort setpoint for cooling mode is never lower than the comfort setpoint for heating mode.
2.4.5

Control algorithms

The main function of the Iddero Verso thermostats is to compare the current room temperature with the desired temperature (setpoint) and send appropriate commands to the KNX actuators (relay outputs, valve motors, etc.) that control the actual HVAC equipment.
To this end, Iddero Verso thermostats support dierent control algorithms:
• Two-point control with hysteresis
• P-I control with continuous (analogue) output
• P-I control with PWM (switched) output
These algorithms are described next.
Note
If a thermostat is configured for both heating and cooling, a dierent control algorithm can be configured for each function. Thus, for example, a thermostat can be setup to use two-point control with hysteresis for cooling, and P-I control with PWM output for heating.
2.4.5.1
Two-point Control with Hysteresis
Two-point control with hysteresis is a simple and well-known control algorithm that is some­times also referred to as “On/o control”. In this algorithm, the thermostat turns on the heating when the current room temperature is below the desired setpoint, and turns it o when the room temperature rises above the desired setpoint. The opposite holds true for cooling.
In order to prevent the output from quickly switching on and o when the room temperature is close to the setpoint value, dierent thresholds are considered for switching on and o. This behaviour is controlled with the Hysteresis configuration parameters (upper and lower hysteresis).
Thermostats 34
2.4
In Heating mode:
Lower
hyst.
Upper
hyst.
Output ON
Output OFF
Setpoint Temperature
Lower
hyst.
Upper
hyst.
Output ON
Output OFF
Setpoint Temperature
The output is switched on when the room temperature is less than or equal to Setpoint -
lower hysteresis
The output is switched o when the room temperature is greater than or equal to Setpoint
+ upper hysteresis
In Cooling mode:
The output is switched on when the room temperature is greater than or equal to Setpoint
+ upper hysteresis
The output is switched o when the room temperature is less than or equal to Setpoint -
lower hysteresis
2.4 Thermostats 35
Two-point control with hysteresis is easy to setup and can be used with regular switching
Time
Setpoint
ON OFF ON ONONOFF OFF OFF
Setpoint +
upper hyst.
Setpoint -
lower hyst.
actuators. However, it is also sub-optimal in terms of power consumption and comfort, due to the typical fluctuations of the room temperature around the setpoint which arise as a result of the simple control algorithm.
2.4.5.2 P-I Control with Continuous Output
Proportional-Integral (P-I) Control is a more complex control algorithm where the thermostat constantly measures the dierence between the current room temperature and the desired setpoint (the error term), and computes an appropriate correction value based on the current dierence, and also on the previous history of the system. This correction value (e.g. 0-100%) is periodically sent to a proportional HVAC actuator device.
When configuring a thermostat to use P-I Control, the following parameters must be consid­ered:
Cycle time:
with the desired setpoint, and computes the correction values to be applied. The cycle
time determines how oen this is done. Longer cycle times (typically 15-20 minutes) should be chosen for HVAC systems with high thermal inertia, such as radiant floor heating, and shorter cycle times (typically 10-15 minutes) for HVAC systems with low thermal inertia, such as as air convection heating and cooling.
Proportional band: nitude of the output value relative to the error term. For example, a proportional band of 5ºC means that the output will be set to 100% when the error (the dierence between the
The control algorithm periodically compares the current room temperature
The proportional band (measured in degrees) determines the mag-
2.4 Thermostats 36
current temperature and the desired setpoint) reaches 5ºC. If the dierence is only 1ºC
(20% of the proportional band), the output will be set to 20%, and so on.
Integral time:
The P-I control algorithm not only considers the current value of the error term at any given time, but also the “history” of the system; that is, the past values of the error term. This makes it possible to react faster to changes in ambient conditions that impact the room temperature. Short integral times allow for fast reactions to such changes, but a too short integral time introduces a risk of permanent oscillations around the setpoint. Long integral times eliminate the risk of oscillations, but the reaction to external changes will be slower.
Note
Every time the desired temperature setpoint changes, the current cycle is interrupted, the new values are processed, and a new cycle is started. This allows the system to reach its steady state more quickly.
If the P-I control parameters are properly adjusted, the control algorithm may be able to ef­ficiently control all common types of heating and cooling systems, thus making the room temperature control work as fast as possible and without deviation. However, tuning of the P-I control parameters is not straightforward, and even small changes to the parameters values can result in noticeable changes to the control performance: An incorrectly configured system may be too slow, needing a long time to reach the desired temperature setpoint, or it may fluctuate above or below the setpoint.
For this reason, a set of predefined parameters that correspond to the most common types of heating and cooling systems are available and can be easily selected, as shown in the following table. For expert users, the option of entering custom parameter values is also provided.
Application
(heating)
Proportional band
(K)
Integral time
(min)
Recommended
cycle time (min)
Warm water heating 5 150 15 Floor heating 5 240 15-20 Electric heating 4 100 10-15 Convection heating 4 90 10-15
Application
(cooling)
Proportional band
(K)
Integral time
(min)
Recommended
cycle time (min)
Cooling ceiling 4 240 15-20 Convection cooling 4 90 10-15
2.4 Thermostats 37
2.4.5.3 P-I Control with PWM Output
Time
Cycle time Cycle time
Duty cycle Duty cycle
ON OFF ON ONOFF
In the P-I Control algorithm described in the previous section (P-I Control with Continuous Output) the control variable that is periodically sent to the HVAC actuatoris an analogue variable (0-100%). Thus, a proportional HVAC actuator is required.
In some cases, however, it is desirable to benefit from the advantages of P-I control, while still being able to use standard (lower cost) switching actuators, such as relays and actuators for zone valves. For this, the P-I Control algorithm with PWM Output can be used.
This is exactly the same as P-I Control with continuous output, except that proportional output values are implemented by switching a binary output on and o for certain time periods. The control algorithm operates periodically over a cycle (the cycle time); in each period, the output is switched on for a time that is proportional to the value of the control variable, and then switched o for the remaining of the period. For example, if the cycle time is 15 minutes, and the control variable should be set to 20%, the controller will keep the output on for 3 minutes (20% of the cycle time), and o for 12 minutes (80% of the cycle time).
By varying the ratio between the on and o times, also known as the duty cycle, the average time of activation of the output, and in turn the average supply of heating or cooling power, can be eectively controlled.
Note
In order to avoid damage to the switching actuator, if the computed on or o time is shorter than 5 seconds, a fixed time of 5 seconds is used instead.
2.4
Thermostats 38

2.4.6 Additional heating and cooling

Some HVAC systems, such as radiant floor heating systems, exhibit a very high thermal inertia, which translates to slow response times at start-up, or when there are changes in the working conditions (ambient temperature or desired setpoint).
In order to improve response times for such systems, auxiliary heating or cooling systems with lower thermal inertia are oen installed. These auxiliary systems, oen called “second stage” systems, are temporarily switched on when there is a large dierence between the room temperature and the setpoint, thus contributing to a faster heating or cooling of the room, and are switched o when this dierence becomes smaller and can be handled by the main system.
The Iddero Verso thermostats can be configured to control these auxiliary heating or cooling systems, if they are installed. For this, it is necessary to define a temperature range where the auxiliary system will kick in. This is configured through the “Additional heating (or cooling) band” parameter:
In Heating mode:
2.5
Additional heating is switched on when the room temperature is less than or equal to
Setpoint - additional heating band
Additional heating is switched o when the room temperature is greater than or equal to
Setpoint - additional heating band + 0.5 ºC
In Cooling mode:
Additional cooling is switched on when the room temperature is greater than or equal to
Setpoint + additional cooling band
Additional cooling is switched o when the room temperature is less than or equal to
Setpoint + additional cooling band - 0.5 ºC

Multifunction inputs

Iddero Verso features four multifunction inputs, each of which can be individually configured in one of the following ways:
• Binary - Push button
• Binary - Switch/sensor
• Temperature probe
2.5
Multifunction inputs 39
For a detailed description of the available configuration options for each type of input, see 3.6
Inputs on page 90.

2.5.1 Binary inputs

2.5.1.1 Push button inputs
Push button inputs are typically connected to external push buttons, and can be configured to trigger dierent actions upon detection of “short” and “long” presses. For example, a push button input can be connected to a physical push button to control a light dimmer. Short presses can be configured to toggle the light on and o, while a long press can be configured to start a dimming operation.
For each input configured as a push button input, a configuration parameter allows to customize the minimum press time to dierentiate between short and long press operations.
2.5.1.2
2.5.1.3
Switch/sensor inputs
Switch/sensor inputs are typically connected to external switches or sensors, and can be config­ured to trigger dierent actions when the input contact closes and when the contact opens.
A typical use case for switch/sensor inputs is to connect external alarm sensors; for example, a fire detector, or a magnetic door/window sensor. Dierent actions can be triggered when the alarm conditions is detected, and also when the alarm condition deactivates.
Input locking
For each binary input, an optional “Input lock” communication object is available. This object allows to temporarily disable operation of the associated input. While an input is locked, short and long presses (for push button inputs) or state transitions (for switch/sensor inputs) are ignored, and the corresponding actions are not triggered.
2.5
Multifunction inputs 40

2.5.2 Temperature probe inputs

Temperature probe inputs can be used to measure temperature from connected temperature probes.
A configurable oset can be added to the measured value in order to compensate for the eect of local heat sources or air dras that might be close to the probe location.
Temperature values are made available through an associated communication object. Values can be sent to the bus periodically, and/or when a certain change between the current value and the last value sent to the bus is detected. If the temperature cannot be read (for example, if the probe is broken, or if it is physically disconnected from the input) an error condition is signalled through a separate error object.
An
alarm function
configured to detect high temperatures, low temperatures, or both high and low temperatures. When the temperature value exceeds the configured limits, an alarm condition is signalled through a specific “alarm” communication object.
can be enabled for each temperature probe input. The alarm function can be
2.6

Scene controller

2.6.1 Internal vs. External scenes

Many of the functions in Iddero Verso (such as touch gestures, or components used in the visualisation) can be configured to trigger so called “external” scenes. External scenes are managed by external KNX devices, which are in charge of storing the scene values, and recalling them when the scene is triggered. In this case, Iddero Verso simply sends a KNX telegram indicating the scene to be recalled or stored.
In addition to this, Iddero Verso features an internal scene controller. “Internal” scenes are managed internally, and can be recalled or stored in response to internal actions, and also if requested by external KNX devices.

2.6.2 Scene actuators

Up to 8 scene actuators can be enabled. Each actuator is associated with a communication object, and can be configured to respond to up to 8 dierent scenes (which need not be the same for all actuators).
Scene controller 41
2.6
Scenes can be recalled and stored in a variety of ways:
When the user activates a scene push button or double push button component in the
visualisation
• Through the “Run/save internal scene” communication object
• As a response to certain actions, such as touch gestures
2.6.3

Recalling scenes

When the internal scene controller receives a request to recall a given scene, all scene actuators are checked. For each scene actuator that has been configured to respond to the corresponding scene number, the value associated with that scene number will be sent to the bus.

2.6.4 Storing scenes

When the internal scene controller receives a request to store a given scene, all scene actuators are checked. For each scene actuator that has been configured to respond to the corresponding scene number, the current value of the associated communication object will be stored as the new value for that scene number (as long as the parameter “Allow saving” is enabled for that scene).
The following must also be considered:
If the associated communication object has not been updated since startup (either by the
1. device itself or by reception of a value from the bus), then the actuator will be skipped, and the value associated with the corresponding scene number will remain unchanged.
If the parameter Send read requests at startup is enabled, the device will send read
2. requests for all scene actuators’ communication objects at startup. Values received as a response to these read requests will be used as default values to store when a
“store request” is processed, if no other value has been written to the corresponding
communication object by that time.
2.6
Scene controller 42
Configuration

3.1 General considerations

This chapter describes the configuration parameters available in the ETS product database.
Configurationparameters are organized in groups, or configuration sections; this chapterfollows the same structure. For each section, the corresponding configuration parameters are shown in table format. For each parameter, available options are listed. The default value is indicated in bold.
Some parameters allow entering text values. These are labeled as [Text field] in parameter tables. Regular text fields have a maximum length of 20 bytes. Text fields used for units in numerical values have a maximum length of 6 bytes.
Note
All texts are stored using Unicode UTF-8 encoding. Encoding of ASCII characters requires 1 byte per character; however, encoding of characters outside the ASCII range requires more than 1 byte per character. Thus the maximum number of characters allowed will depend on the actual characters used in the text. It is recommended to check that the full texts are actually visible on the screen aer programming.
3
Some parameters allow selecting an icon. These are labeled as [Icon selection]. For a complete list of available icons, please refer to the Iddero Verso icon list, available for download from
www.iddero.com.
43

3.2 Main

3.2.1 General

Parameter name Values
Project name [Text field] Display orientation Portrait / Landscape Enable date/time objects [Checkbox] Date/time sending period
(If date/time objects are enabled)
Thermostat 1 [Checkbox] Thermostat 2 [Checkbox] Inputs [Checkbox] Internal scenes [Checkbox]
The Project name field can be used to enter a descriptive project name. This will be shown in the System Settings > Info page.
0 . .. 255 (x 1 min, 0 = Disabled)
The Display orientation parameter allows selecting the configuration of the user interface (por­trait or landscape).
The Enable date/time objects parameter determines whether the Date (DPT 11.001) and Time (DPT 10.001) communication objects will be enabled. When enabled, writing to these objects will update the internal date and time of the device. Conversely, when the date/time is modified through the user interface (Preferences > Date & time), the objects will be updated with the new setting.
If the Date/time sending period parameter is set to a non-zero value, date and time will also be sent periodically to the bus.
The Thermostat 1, Thermostat 2, Inputs, and Internal scenes parameters enable the correspond­ing configuration sections (see 3.5 Thermostats on page 83, 3.6 Inputs on page 90, and 3.7
Scenes on page 94).
3.2
Main 44

3.2.2 Internal temperature sensor

Parameter name Values
Calibration oset -50 . .. 0 ... 50 (x 0.1ºC) Sending period 0 ... 255 (x 10 s, 0 = Disabled) Send when change is greater than 0 . .. 255 (x 0.1ºC, 0 = Disabled)
This section allows configuration of the internal temperature probe.
The Calibration oset parameter defines the initial value of the calibration oset to be added to the measured temperature values. This oset can also be adjusted from the user interface (System settings > Temperature Probe)
The corrected temperature values are made available through the Internal temperature com­munication object (DPT 9.001). The Sending period and Send when change is greater than parameters can be used to control when this object is updated (and its value sent to the bus)

3.2.3 Timer groups

Parameter name Values
Timer group 1 lock object [Checkbox] Timer group 2 lock object [Checkbox] Timer group 3 lock object [Checkbox] Timer group 4 lock object [Checkbox]
As described in 2.2 Time schedules on page 21, timers can optionally be added to one of four available timer groups. This allows to temporarily lock (disable) groups of timers with a single operation.
The parameters in this section control whether the corresponding lock objects (Timer group 1 lock ... Timer group 4 lock) are available.
3.2
Main 45

3.3 User Interface

3.3.1 General

Parameter name Values
Page 1 [Checkbox] ... Page 6 [Checkbox] Favorites [Checkbox] Default language English / Deutsch / Español / Français Show time in title bar No / Yes Show temperature in title bar No / Yes Show date/time in home page No / Yes Show temperature in home page No / Yes Source for temperature display
(Only if temperature is displayed in title bar
and/or home page)
Default page aer home page Menu / Page 1 ... Page 6 / Favorites
Internal sensor
Temperature Probe IN1 Temperature Probe IN2 Temperature Probe IN3 Temperature Probe IN4 External object
Checkboxes Page 1 ... Page 6 and Favorites enable the corresponding pages.
Parameter Default language selects the default language for system texts. This settings can be modified from the user interface at any time (Preferences > Language).
Parameters Show time in title bar and Show temperature in title bar control what information will be shown in the title bar, besides the name of the current page.
Parameters Show date/time in home page and Show temperature in home page control what information will be shown in the Home page.
If the temperature is set to be displayed in the title bar and/or in the Home page, an additional parameter Source for temperature display allows selecting the source for the displayed temper­ature: The internal temperature probe, an external probe connected to one of the multifunction inputs, or an external communication object. If the latter is selected, communication object External temperature (DPT 9.001) will be enabled.
3.3
User Interface 46
Note
When using an external probe connected to one of the multifunction inputs as a tempera­ture source, make sure to configure the input accordingly.
Parameter Default page aer home page controls which page will be the first one shown imme­diately aer the Home page. This can be the Menu page, any of the configured control pages, or the Favorites page.
3.3.2

Power saving mode

Parameter name Values
Timeout for home page 0 . .. 5 ... 60 (x 1 min, 0 = Disabled) Timeout for power saving mode 0 . .. 5 ... 60 (x 1 min, 0 = Disabled) Page to show when leaving power saving mode Enable wake up object [Checkbox]
This section controls the behaviour of the power saving mode (see 2.1.9 Power saving mode on page 20). The Timeout for home page and Timeout for power saving mode parameters define the initial timeout values. Both of them can be adjusted from the user interface (Preferences > Power saving).
Parameter Page to show when leaving power saving mode determines which page will be shown when leaving power saving mode. This can be either the Home page or the “default” page defined in the previous section.
Home page / Default page
A special Wake up communication object can optionally be enabled with the Enable wake up object parameter. Writing the value “1” to this object wakes the device from power saving mode.
3.3
User Interface 47

3.3.3 Access control

Parameter name Values
Restricted access levels One level / Two levels
Additional parameters for “One level”:
Default password:
- Digit 1 0 . .. 1 ... 9
- Digit 2 0 . .. 1 ... 9
- Digit 3 0 ... 1 ... 9
- Digit 4 0 ... 1 ... 9
Additional parameters for “Two levels”:
Default User password:
- Digit 1 0 . .. 1 ... 9
- Digit 2 0 . .. 1 ... 9
- Digit 3 0 ... 1 ... 9
- Digit 4 0 ... 1 ... 9 Default Master password:
- Digit 1 0 . .. 2 ... 9
- Digit 2 0 . .. 2 ... 9
- Digit 3 0 ... 2 ... 9
- Digit 4 0 ... 2 ... 9
Pages in the user interface can be password protected with 4-digit PIN codes (see 2.1.8 Access
control on page 19). The parameter Restricted access levels defines whether one single password
is used for all protected pages (“One level”), or whether separate user and master passwords are used (“Two levels”).
The setting of this parameteralso determines the available options for configuration parameters that relate to access control for individual pages. These are labeled as [Access control options] in parameter tables. The available options in each case are:
• If “One level” is selected: No / Yes
• If “Two levels” is selected: No / User password / Master password
Default (initial) passwords are also defined in this section. Passwords can be modified at any time through the user interface (Preferences > Passwords).
3.3
User Interface 48

3.3.4 Main menu

Parameter name Values
Menu page layout Fixed positions
Restrict access to Menu page [Access control options] Restrict access to Alarms page [Access control options] Restrict access to Timers page [Access control options]
This section allows configuration of the Menu page layout, and access control for the Menu page, as well as for the Alarms and Timers page.

3.3.5 Settings pages

Flexible – center Flexible – center + stretch horizontally Flexible – center + stretch vertically Flexible – center + stretch in both directions
3.3.6
Parameter name Values
Restrict access to Settings page [Access control options] Restrict access to User Preferences page [Access control options] Restrict access to System settings page [Access control options]
This section allows configuration of access control for settings pages.

Favorites

Parameter name Values
Favorites page layout Fixed positions
Flexible – center Flexible – center + stretch horizontally Flexible – center + stretch vertically
Flexible – center + stretch in both directions Restrict access to Favorites page [Access control options] Restrict access to Edit Favorites page [Access control options]
3.3 User Interface 49
This section allows configuration of the Favorites page layout, and access control for the Fa­vorites and Edit Favorites page.

3.3.7 Touch gestures

Parameter name Values
Gesture: Up Disabled / Send binary value / Run scene Value to send
(Only for “Send binar y value”)
Scene type
(Only for “Run scene”)
Scene number
(Only for “Run scene”)
Gesture: Down Same parameters as for Gesture: Up Gesture: Le Same parameters as for Gesture: Up Gesture: Right Same parameters as for Gesture: Up Gesture: Multitouch Same parameters as for Gesture: Up
0 / 1
External / Internal
1 . .. 64
Configuration of touch gestures is carried out in this section (see 2.1.10 Touch gestures on page 20). A dierent action can be configured for each of the five supported touch gestures. This can be either sending a binary value to the bus (“0” or “1”), or triggering a scene.
If a binary action is configured, a communication object (Gesture: Up, Gesture: Down, Gesture: Le, Gesture: Right, or Gesture: Multitouch) will be enabled. The selected value (Value to send) will be written to this communication object.
If a scene action is configured, this can be either an external scene or an internal scene. For external scenes, a scene recall request will be sent through the Run/save external scenes object. For internal scenes, the selected scene will be run directly.
Note
If an internal scene shall be run, make sure to enable and configure the “Internal scenes” function (see 3.2.1 General on page 44 and 3.7 Scenes on page 94).
3.3
User Interface 50

3.4 Control Pages

3.4.1 General

Parameter name Values
Name [Text field] Icon [Icon selection] Page layout Fixed positions
Restrict page access [Access control options] Component 1 [Checkbox] ... Component 8 [Checkbox]
Flexible – center
Flexible – center + stretch horizontally
Flexible – center + stretch vertically
Flexible – center + stretch in both directions
Each page has a Name and optionally an Icon. The name and icon are shown in the Menu page. Additionally, the name is shown in the title bar when the page is displayed.
The Page layout can also be selected, along with the access control setting (Restrict page access).
Additionally, a set of checkboxes are provided to enable or disable each of the eight components that can be used in each page.
3.4
Control Pages 51

3.4.2 Components

Parameter name Values
Name [Text field] Component type Indicator
All components have a Name, which is displayed in the visualization.
Indicator with Alarm
Push Button
Double Push Button
Regulation Bar
Rotary Control
Numeric Keypad
Dimmer Control
Shutter Control
RGBW Control
Temperature Control
3.4.2.1
A Component type must also be selected. All the remaining configuration options are specific to each component type, and are described separately in the following sections.
Note that there is no need for a dedicated “Timer” component type, as most component types support a timer function can be enabled (see 3.4.2.12 Timer function on page 81).
Indicator
Parameter name Values
Indicator type Binary
Enumerated
Numerical
Level bar
Level dial
Indicators can be used for the visualisation of status values. They display the current value of an associated communication object.
3.4
Control Pages 52
Several indicator types are supported. Each type is described separately.
Binary
Parameter name Values
Text for 0/O [Text field] Icon for 0/O [Icon selection] Text for 1/On [Text field] Icon for 1/On [Icon selection]
Binary indicators display the state of an associated binary (DPT 1) object, Binary indicator.
Both an icon and/or a text label can be associated to each of the two possible states of the communication object (“1”/On and “0”/O).
Enumerated
Parameter name Values
Number of states 1 ... 6 Value for state 1 0 . .. 255 Text for state 1 [Text field] Icon for state 1 [Icon selection] States 2 ... 6 Same parameters as for state 1 Define fallback state [Checkbox] Text for fallback state
[Text field]
(If fallback state is enabled)
Icon for fallback state
[Icon selection]
(If fallback state is enabled)
Enumerated indicators can display several dierent states, depending on the value of an associ­ated 1-byte (DPT 5.010) communication object. Values can range from 0 to 255.
3.4
Control Pages 53
Up to 6 states can be defined. Each of these states is associated with a specific value of the communication object. For each state, it is possible to define both an icon and/or a text label. The icon and/or text will be shown when the corresponding value is received through the communication object.
Additionally, it is possible to define the icon and/or text label for a so called “fallback state”. The fallback state icon and/or text will be shown when a value that is not associated to any other state is received through the communication object.
If no fallback state is defined, received values that do not match any state will be ignored.
Numerical
Parameter name Values
Data type 1-byte unsigned int
1-byte signed int
Percentage
2-byte unsigned int
2-byte signed int
2-byte float Decimal places
Automatic / 0 / 1 / 2
(Only for “2-byte float” data type)
Units
[Text field]
(Except for “Percentage” data type)
Numerical indicators display the value of the associated communication object as a number. The following table shows the available data types for the communication object and the corresponding value ranges:
Data type Value range
1-byte unsigned int 0 . .. 255 1-byte signed int -128 ... 127 Percentage 0% . .. 100% 2-byte unsigned int 0 ... 65535 2-byte signed int -32768 ... 32767 2-byte float -671088.64 ... 670760.96
3.4 Control Pages 54
For the 2-byte float data type, it is possible to define the number of decimal places to show (Decimal places parameter). This can be set to 0, 1, 2, or Automatic; with the “Automatic” option, the number of decimal places to show is determined automatically by the device, depending the actual object value:
• Two decimal places if the absolute value is less than 1
• One decimal place if the absolute value is 1 or greater, and less than 100
• No decimal places if the absolute value is 100 or greater
Finally, for all data types except “Percentage”, a text suix (Units parameter) can be added to represent value units, such as “ºC”. This suix will be displayed immediately aer the numeric object value.
Level bar
Parameter name Values
Data type 1-byte unsigned int
1-byte signed int
Percentage
2-byte unsigned int
2-byte signed int
2-byte float Decimal places
Automatic / 0 / 1 / 2
(Only for “2-byte float” data type)
Units
[Text field]
(Except for “Percentage” data type)
Minimum bar value [See description] Maximum bar value [See description]
Level bar indicators are similar to numerical indicators, and support the same data types, but the value of the associated communication object is represented as a level bar. In addition, the value is also displayed in textual form above the level bar.
The Minimum bar value and Maximum bar value parameters allow to limit the eective range of values that are used to determine the bar level. Values that are outside this eective range will be represented as an empty or full bar, respectively. The textual representation of the value is not aected by these parameters.
3.4
Control Pages 55
Example
A level bar with the data type set to 2-byte float can be used to represent temperature values. The “minimum bar value” and “maximum bar value” parameters can be used to define the range of temperatures to be represented in the level bar; for example, 0 to 60ºC. If a value of 80ºC is received, the level bar would be represented as full (as for any value above 60ºC), however the actual numeric value (80ºC) would still be displayed above the bar.
The range of valid values for the Minimum bar value and Maximum bar value parameters equals the range of the selected data type. The default value for the parameter will be the minimum or maximum value of the valid range, respectively.
Level dial
Parameter name Values
Data type 1-byte unsigned int
1-byte signed int
Percentage
2-byte unsigned int
2-byte signed int
2-byte float Decimal places
Automatic / 0 / 1 / 2
(Only for “2-byte float” data type)
Units
[Text field]
(Except for “Percentage” data type)
Minimum dial value [See description] Maximum dial value [See description]
Level dial indicators are completely equivalent to level bar indicators. The only dierence is that for the graphical representation of the value, a circular dial is used instead of a level bar.
3.4.2.2 Indicator with Alarm
Parameter name Values
Alarm trigger value 0 / 1 Alarm acknowledge value 0 / 1
3.4 Control Pages 56
Indicators with Alarm function are regular indicator components that in addition can be used to detect alarm or fault conditions.
For this, two additional communication objects are enabled: Alarm trigger and Alarm acknowl- edge. The activation value for both objects is selected via the parameters Alarm trigger value and Alarm acknowledge value, respectively.
See 2.3 Alarms on page 24 for a detailed description of the alarm function.
3.4.2.3 Push Button
Parameter name Values
Push Button type Binary
Choice
Numerical
Scene
Push button components allow sending predefined values to the bus through an associated communication object.
Several push button types are supported. Each type is described separately.
3.4
Control Pages 57
Binary
Parameter name Values
Action Send 0
Send 1
Toggle
Short 0, long 1
Short 1, long 0
Press 0, release 1
Press 1, release 0
Parameters for “Send 0” and “Send1”:
Button text [Text field] Button icon [Icon selection]
Parameters for all other actions:
Button text for 0/O [Text field] Button icon for 0/O [Icon selection] Button text for 1/On [Text field] Button icon for 1/On [Icon selection]
When binary push buttons are pressed, a value is sent to the bus through the associated binary (DPT 1) communication object, Binary control.
The specific behaviour of the button depends on the Action parameter. The following choices are available:
Send 0: Sends the value “0” (o) when the button is pressed.
Send 1: Sends the value “1” (on) when the button is pressed.
Toggle: Alternates sending “0” (o) and “1” (on) on each button press (the first time, the
• value “1” (on) is sent).
Short 0, Long 1: Sends “0” on a short press, “1” on a long press.
Short 1, Long 0: Sends “1” on a short press, “0” on a long press.
Press 0, Release 1: Sends “0” when the user starts pressing the button, and “1” when the
button is released.
Press 1, Release 0: Sends “1” when the user starts pressing the button, and “0” when the button is released.
3.4
Control Pages 58
For actions that send a single fixed value (Send 0 and Send 1), it is possible to define both an icon and/or text label that will be shown in the push button component.
For actions that can send two dierent values (all other actions), it is possible to define separate icons and/or text labels for the values “0” and “1”. The component will show the icon and/or text corresponding to the last value that was sent.
Choice
Parameter name Values
Number of options 1 . .. 6 Option 1 value 0 ... 255 Option 1 text [Text field] Option 1 icon [Icon selection] Options 2 ... 6 Same parameters as for option 1 Show fixed icon/text No / Yes Button text
[Text field]
(If fixed icon/text is selected)
Button icon
[Icon selection]
(If fixed icon/text is selected)
Choice Push Buttons can be used to send one of several predefined values to the bus through the associated 1-byte (DPT 5.010) communication object. Values can range from 0 to 255.
Up to 6 options can be defined. Each of these options is associated with a value to be sent to the bus. For each option, it is possible to define both an icon and/or a text label. When the button is pressed, a pop-up dialog will be shown allowing the user to select one of the available options. The value associated with the selected option will then be sent to the bus.
3.4
Control Pages 59
By default, the push button will show the icon and/or text corresponding to the last option that was selected. However, if the Show fixed icon/text parameter is set to “Yes”, a fixed icon and/or text will be displayed on the component instead.
3.4
Control Pages 60
Numerical
Parameter name Values
Data type 1-byte unsigned int
1-byte signed int Percentage 2-byte unsigned int 2-byte signed int 2-byte float
Action Send fixed value
Send A/B values on short/long press
Parameters for “Send fixed value”:
Value [See description] Button text [Text field] Button icon [Icon selection]
Parameters for “Send A/B values...”:
Value A [See description] Text for value A [Text field] Icon for value A [Icon selection] Value B [See description] Text for value B [Text field] Icon for value B [Icon selection]
Numerical push buttons are similar to binary push buttons, but allow sending either a fixed nu­meric value, or one of two possible numeric values to the associated communications object.
The supported data types are the same as for numerical indicators (see 3.4.2.1 Indicator on page 52).
The specific behaviour of the button depends on the Action parameter. The following choices are available:
Send fixed value: Sends a fixed value when the button is pressed.
Send values A/B on short/long press: Sends a configured value (A) on short press, and another value (B) on long press.
The range of valid values for the Value, Value A, and Value B parameters equals the range of the selected data type. The default value for all three parameters is 0.
3.4
Control Pages 61
Scene
Parameter name Values
Scene type External / Internal Scene number 1 . .. 64 Allow saving scene No / Yes Button text [Text field] Button icon [Icon selection]
Scene push buttons allow activating or saving a scene. The scene can be external or internal (Scene type parameter). The Scene number parameter allows specifying the target scene (1-
64).
For external scenes, the scene recall or store request will be sent through the global Run/save external scenes object. For internal scenes, the request is not sent to the bus; instead, it is processed internally (the internal scene controller will recall or store the selected scene).
Note
If an internal scene shall be run, make sure to enable and configure the “Internal scenes” function (see 3.2.1 General on page 44 and 3.7 Scenes on page 94).
Further, the Allow saving scene parameters controls whether the push button will allow only activation of the associated scene, or whether it will also allow saving. If saving of scenes is allowed, then a short press will trigger activation of the scene, while a long press will trigger saving of the scene. If saving of scenes is not allowed, then pressing the button will always activate the scene.
The Button text and Button icon parameters can be used to set a text label and/or icon to be displayed on the component.
3.4
Control Pages 62
3.4.2.4 Double Push Button
Parameter name Values
Double push button type Binary
Le button icon [Icon selection] Right button icon [Icon selection]
Double push buttons combine the function of an Indicator component with an additional pair of buttons.
The indicator displays the value of the associated “indicator” communication object. The le and right buttons are used to select values to be sent to the bus through an additional “control” communication object. Whenever a value is sent to the bus through the “control” object, the indicator display is also updated automatically.
Enumerated Numerical Scene
Several types of double push button components are supported. Each type is described sepa­rately.
Binary
Parameter name Values
Action Le 0, right 1 / Le 1, right 0 Text for 0/O [Text field] Icon for 0/O [Icon selection] Text for 1/On [Text field] Icon for 1/On [Icon selection]
Double push buttons of type “Binary” are based on Binary Indicators. The indicator function is configured in the same way as for the corresponding indicator component.
3.4
Control Pages 63
When the le or right buttons are pressed, a fixed value will be sent to the bus through the Binary control communication object (DPT 1). The specific values sent depend on the setting of the Action parameter. The following choices are available:
Le 0, Right 1: Pressing the le button sends the value “0” (o). Pressing the right button sends “1” (on)
Le 1, Right 0: Pressing the le button sends the value “1” (on). Pressing the right button
sends “0” (o)
Enumerated
Parameter name Values
Number of states 1 ... 6 Value for state 1 0 . .. 255 Text for state 1 [Text field] Icon for state 1 [Icon selection] States 2 ... 6 Same parameters as for state 1 Define fallback state [Checkbox] Text for fallback state
[Text field]
(If fallback state is enabled)
Icon for fallback state
[Icon selection]
(If fallback state is enabled)
Double push buttons of type “Enumerated” are based on Enumerated Indicators. The indicator function is configured in the same way as for the corresponding indicator component: Up to 6 options (“states”) can be defined, each associated with a specific value, along with an optional
“fallback state”.
The le and right buttons allow users to select one of available options. Once an option is selected, the associated value is sent to the bus through the “control” communication object (DPT 5.010).
3.4
Control Pages 64
Numerical
Parameter name Values
Action Le decrease, right increase
Le increase, right decrease
Data type 1-byte unsigned int
1-byte signed int Percentage 2-byte unsigned int 2-byte signed int 2-byte float
Decimal places
Automatic / 0 / 1 / 2
(Only for “2-byte float” data type)
Units
[Text field]
(Except for “Percentage” data type)
Short step [See description] Long step [See description] Minimum value [See description] Maximum value [See description] Initial value [See description]
Double push buttons of type “Numerical” are based on Numerical Indicators. The indicator function is configured in the same way as for the corresponding indicator component. The same data types are supported.
The le and right buttons allow the user to select a value from a given (configurable) range. By default, the le button is used to decrease the value, and the right button to increase it; however the opposite behaviour can also be selected through the Action parameter.
Minimum and maximum values for the allowed range must be defined (Minimum value and Maximum value parameters). The component will not allow the user to select a value outside this range. Also, the Short step and Long step values must be configured. The short step determines the increment or decrement that is applied to the current value on a short press of any of the two buttons. The long step determines the increment or decrement that is applied (repeatedly) to the current value when any of the two buttons is kept pressed, and until it is released.
Once a value is selected, it will be sent to the bus through the “control”communication object.
3.4 Control Pages 65
The valid range for the Short step, Long step, Minimum value, Maximum value, and Initial value parameters equal the range of the selected data type. The default values for each parameter is listed next:
• Short step: 1
• Long step: 5
• Minimum value: Minimum valid value for the selected data type
• Maximum value: Maximum valid value for the selected data type
• Initial value: 0
Scene
Parameter name Values
Le: Scene type External / Internal Le: Scene number 1 ... 64 Le: Allow saving No / Yes Right: Scene type External / Internal Right: Scene number 1 . .. 64 Right: Allow saving No / Yes
Double push buttons of type “Scene” behave exactly in the same way as Scene Push Button components, except that each of the two buttons (le and right) can be individually configured for a dierent scene.
3.4
Control Pages 66
3.4.2.5 Regulation Bar
Parameter name Values
Data type 1-byte unsigned int
Decimal places
(Only for “2-byte float” data type)
Units
(Except for “Percentage” data type)
Minimum bar value [See description] Maximum bar value [See description]
Regulation Bars are based on Indicators of type “Level bar”. They display the current value of the associated communication object as a level bar, and their configuration parameters are exactly the same as for the corresponding indicator component.
1-byte signed int Percentage 2-byte unsigned int 2-byte signed int 2-byte float Automatic / 0 / 1 / 2
[Text field]
Additionally, when the component area is pressed, a window will pop up, containing an interac­tive regulation bar that allows the user to select values to be sent to the bus.
3.4
Control Pages 67
Values are sent to the bus through an additional “control” communication object. Whenever a value is sent to the bus through the “control” object, the indicator display is also updated automatically.
Note
The interactive regulation bar only allows the selection of values within the range config­ured through the Minimum bar value and Maximum bar value parameters.
3.4
Control Pages 68
3.4.2.6 Rotary Control
Parameter name Values
Data type 1-byte unsigned int
Decimal places
(Only for “2-byte float” data type)
Units
(Except for “Percentage” data type)
Minimum dial value [See description] Maximum dial value [See description]
Rotary Controls are based on Indicators of type “Level dial”. They display the current value of the associated communication object as a level dial, and their configuration parameters are exactly the same as for the corresponding indicator component.
1-byte signed int Percentage 2-byte unsigned int 2-byte signed int 2-byte float Automatic / 0 / 1 / 2
[Text field]
Additionally, when the component area is pressed, a window will pop up, containing an interac­tive rotary control that allows the user to select values to be sent to the bus.
3.4
Control Pages 69
Values are sent to the bus through an additional “control” communication object. Whenever a value is sent to the bus through the “control” object, the indicator display is also updated automatically.
Note
The interactive rotary control only allows the selection of values within the range config­ured through the Minimum bar value and Maximum bar value parameters.
3.4
Control Pages 70
3.4.2.7 Numeric Keypad
Parameter name Values
Data type 1-byte unsigned int
Decimal places
(Only for “2-byte float” data type)
Units
(Except for “Percentage” data type)
Minimum input value [See description] Maximum input value [See description] Error text for invalid input [Text field]
1-byte signed int Percentage 2-byte unsigned int 2-byte signed int 2-byte float Automatic / 0 / 1 / 2
[Text field]
Numeric Keypads are based on Indicators of type “Numerical”. They display the current value of the associated communication object as a number, and can be configured in a similar way as the corresponding indicator component.
Additionally, when the component area is pressed, a window will pop up, containing an interac­tive numeric keypad that allows the user to enter values to be sent to the bus.
3.4
Control Pages 71
Values are sent to the bus through an additional “control” communication object. Whenever a value is sent to the bus through the “control” object, the indicator display is also updated automatically.
Three additional parameters are defined: The Minimum input value and Maximum input value parameters limit the range of valid values that can be entered through the numeric keypad. If users enter a value that is outside this range, the value will not be accepted; instead, an error message will be shown. The error text can be customized through the Error text for invalid input parameter.
The range of valid values for the Minimum input value and Maximum input value parameters equals the range of the selected data type. The default value for the parameter will be the minimum or maximum value of the valid range, respectively.
3.4
Control Pages 72
3.4.2.8 Dimmer Control
Parameter name Values
Dimmer type Relative dimmer / Absolute dimmer Action Le o, right on / Le on, right o Dimming step
(Only for relative dimmers)
Le button icon [Icon selection] Right button icon [Icon selection]
Dimmer Controls are specialized components that can be used to control light dimmer actua­tors.
The following communication objects are available:
Dimming level indicator (DPT 5.001)
Light on/o (DPT 1.001)
• One of:
100% / 50% / 25% / 12.5% / 6.25% / 3.1% /
1.6%
Relative dimming control (DPT 3.007)Absolute dimming control (DPT 5.001)
Dimmer controls are represented as double push buttons in the visualization. The current light intensity value is displayed as a percentage (0...100%), and is updated whenever a new value is received through the Dimming level indicator communication object (note that the displayed value is not updated automatically upon user actions).
The le and right buttons are used to switch the light on and o, and to adjust light intensity. The Action parameter allows selecting the function of each button (Le o, right on, or Le on, right o ).
A short press on any of the buttons sends an On / O command to the bus through the Light on/o communication object.
Handling of long presses depend on the type of dimmer being controlled (as defined by the Dimmer type parameter):
Control Pages 73
3.4
Relative dimmers
A long press on any of the buttons starts an increase / decrease light intensity operation. A dimming command will be sent to the dimmer actuator through the Relative dimming control communication object, requesting that the light intensity is increased (or decreased) by the amount defined by the Dimming step parameter. When the button is released, however, a “stop” command will be sent to the dimmer; if the dimming operation was still in progress, it will be interrupted.
Note
It is common to set the Dimming step to 100%. This way, a long press on any of the buttons will initiate a dimming operation which spans the entire dimming range, all the way up to 100% or down to 0%. As soon as the light intensity reaches the desired value, the user can release the button and the dimming operation will be interrupted.
Absolute dimmers
A long press on any of the buttons will bring up a window with a regulation bar. The regulation bar allows precise selection of light intensity values (0...100%). The selected value will be sent to the bus through the Absolute dimming control communication object.
3.4 Control Pages 74
3.4.2.9 Shutter Control
Parameter name Values
Shutter actuator type Basic / With absolute positioning Action Le down, right up / Le up, right down Le button icon [Icon selection] Right button icon [Icon selection]
Shutter controls are specialized components that can be used to control shutter or blind actua­tors.
The following communication objects are available:
Shutter position indicator (DPT 5.001)
Shutter step/stop (DPT 1.007)
• One of:
Shutter up/down (DPT 1.008)Shutter position control (DPT 5.001)
Shutter controls are represented as double push buttons in the visualization. The current shutter / blind position is displayed as a percentage (0...100%), with 0% corresponding to the
“completely open” position, and 100% to the “completely closed” position. This is updated
whenever a new value is received through the Shutter position indicator communication object (note that the displayed value is not updated automatically upon user actions).
The le and right buttons are used to control the shutter actuator. The Action parameter allows selecting the function of each button (Le down, right up, or Le up, right down).
A short press on any of the buttons sends an step up or step down command to the bus through the Shutter step/stop communication object. If a move operation was in progress, it will be interrupted. Otherwise, a single step operation is performed.
Handling of long presses depend on the type of shutter actuator being controlled (as defined by the Shutter actuator type parameter).
3.4
Control Pages 75
Basic shutter actuators
A long press on any of the buttons starts a move up or move down operation through the Shutter up/down communication object. This operation will ultimately open or close the shutter completely, unless it is interrupted.
Shutter actuators with absolute positioning
A long press on any of the buttons will bring up a window with a regulation bar. The regulation bar allows precise selection of shutter position values (0...100%). The selected value will be sent to the bus through the Shutter position control communication object.
3.4.2.10 RGBW Control
Parameter name Values
Use white channel No / Yes RGB object type Three separate R,G,B objects (DPT 5.001)
Le button function Switch o / Toggle Le button icon [Icon selection]
One combined RGB object (DPT 232.600)
3.4 Control Pages 76
RGBW Controls are specialized components that can be used to control both RGB and RGBW (RGB + White) LED dimmer actuators.
The RGB object type parameter sets whether the RGBW control should use three separate 1-byte R, G, B communication objects (one per channel), or one combined 3-byte RGB object.
The Use white channel parameter selects whether a white channel should also be controlled, in addition to the Red, Green, and Blue channels. If a white channel is enabled, then the RGB object type parameter is forced to “One combined RGB object”, and an additional 1-byte object is used for white channel control.
Operation
The RGBW Control shows two button; an action button (le) and the color selection button (right):
The function of the action button is configured through the Le button function parameter: Either switch all channels o (sets all channels to 0%), or toggle between switching all channels o and recalling the previously selected color.
The color selection button shows the current color. Pressing this button brings up an interactive color selection window. This allows selecting dierent colors and sending them to the bus. The user can also save their “favorite” colors for later use. For each RGBW Control, up to ten favorite colors can be saved.
3.4
Control Pages 77
2
4
3
1
5
5
6 6
While the color selection window is open:
Use the “view switch” button (1) to toggle between the “color wheel” and “color bars”
views. This is only available if white channel control is not enabled; if the component is
configured to control a white channel, the color bars view is always used.
Color wheel: Use the wheel (2) to select a base color; then use the bar (3) to select the
level of brightness.
• Color bars: Use the bars (4) to select the desired value for each channel.
• Press the Send button (5) to send the current value to the bus
Perform a long press on any of the “favorite color” positions (6) in order to save the
currently selected color in that position.
Perform a short press on one of the “favorite color” positions (6) in order to recall the stored color.
3.4
Control Pages 78
3.4.2.11 Temperature Control
Parameter name Values
Temperature control type Absolute
Le button icon [Icon selection] Right button icon [Icon selection]
Temperature controls are specialized components that can be used to adjust a temperature value, for example the setpoint in a thermostat.
Temperature controls are represented as double push buttons in the visualization. The compo­nent displays the current temperature from the Temperature indicator communication object. The le and right buttons allow selecting new values to be sent to the bus. The actual operation details depend on the Temperature control type parameter; each type is described separately.
Relative (oset control) Relative (binary stepping)
Absolute
Parameter name Values
Action Le decrease, right increase
Le increase, right decrease Short step 0 . .. 5 ... 255 (x 0.1ºC) Long step 0 . .. 10 ... 255 (x 0.1ºC) Minimum value -30 ... 15 ... 100 (ºC) Maximum value -30 ... 40 ... 100 (ºC) Initial value -30 ... 22 ... 100 (ºC)
Communication objects:
Temperature indicator (2-byte float)
Temperature control (2-byte float)
3.4
Control Pages 79
The le and right buttons allow selection of an absolute temperature value that will be sent to the bus. It is possible to configure the minimum and maximum temperature values that can be selected, as well as the increment or decrement that is applied on a short or long press of the buttons.
Whenever a temperature value is selected, it will be written to the Temperature control object.
Relative (Offset Control)
Parameter name Values
Action Le decrease, right increase
Le increase, right decrease Short step 0 . .. 5 ... 255 (x 0.1ºC) Long step 0 . .. 10 ... 255 (x 0.1ºC) Minimum oset -20 ... -10 ... 20 (ºC) Maximum oset -20 .. . 10 ... 20 (ºC) Initial base value -30 ... 22 ... 100 (ºC)
Communication objects:
Temperature indicator (2-byte float)
Temperature oset control (2-byte float)
Temperature oset status (2-byte float)
In this case, the actual temperature value is assumed to be the sum of two components: A
base
temperature, and a temperature oset:
Absolute temperature = Base temperature + temperature oset
This type of temperature control allows adjusting the oset value. Oset values are sent to the bus through the Temperature oset control object (2-byte float). However, the displayed temperature value is always the absolute temperature value. Thus, as far as the end user is concerned, the user interface is identical to the Absolute temperature control case: The user simply selects a new temperature value and need not be aware of the fact that the control is internally updating the oset value only.
It is possible to configure the minimum and maximum oset values that can be sent, as well as the increment or decrement that is applied on a short or long press of the buttons.
3.4
Control Pages 80
When new values are received from the bus through the Temperature indicator object, the internal temperature oset value remains unchanged, and the internal base temperature value is updated so that the resulting absolute temperature matches the received value.
Additionally, a Temperature oset status object is available in order to externally update the internal temperature oset value.
Relative (Binary Stepping)
Parameter name Values
Action Le decrease, right increase
Le increase, right decrease Step 0 . .. 5 ... 255 (x 0.1ºC) Initial value -30 ... 22 ... 100 (ºC)
Communication objects:
Temperature indicator (2-byte float)
Temperature step control (binary)
3.4.2.12
On each press of the le or right button, a “decrease” (0) or “increase” (1) command is transmit­ted to the bus through the Temperature step control object. The displayed temperature value will be decremented or incremented by the amount defined through the Step parameter, thus providing immediate feedback in the visualization.
Timer function
Parameter name Values
Enable timer function [Checkbox] Add to timer group
(Only if timer function is enabled)
For most components in the visualisation, a timer function can be enabled. When the timer function is enabled for a component, users can setup actions to be run at scheduled times.
The Enable timer function checkbox enables the timer function for the component. The Add to timer group parameter allows adding a component to one of the four available timer groups. See 2.2 Time schedules on page 21 for a detailed functional description of timers and timer groups.
None
/ Group 1 / Group 2 / Group 3 / Group 4
3.4 Control Pages 81
Note
If timer groups shall be used, make sure to enable the corresponding communication objects. See 3.2.3 Timer groups on page 45.
Timer function support
The timer function is supported for most component types.
Component type Timer function support Additional notes
Indicator Not applicable Indicator with Alarm Not applicable Push Buttons Yes See note 1 Double Push Buttons Yes Regulation Bars Yes Rotary Controls Yes Numeric Keypads Yes Dimmer Controls Yes See note 2 Shutter Controls Yes See note 3 RGBW Controls Yes Temperature Controls Yes See note 4
Notes:
1. The timer function is supported for the following subtypes:
• Binary: Send 0 / Send 1 / Toggle
• Numeric: Send fixed value
• Choice
• Scene
2.
For absolute Dimmer Controls, the timer function allows scheduling of any dimming action. For relative Dimmer Controls, only on / o actions can be scheduled.
For Shutter Controls with absolute positioning, the timer function allows scheduling of
3. any positioning action. For basic Shutter Controls, only simple move up / move down actions can be scheduled.
4. The timer function is supported for absolute Temperature Controls.
3.4
Control Pages 82

3.5 Thermostats

The Thermostat 1 and Thermostat 2 configuration sections will be available if the corresponding functions have been enabled in the Main configuration section.
Both thermostats are completely identical in terms of functionality and configuration. For a detailed functional description, see 2.4 Thermostats on page 28.

3.5.1 General

Thermostat function
Parameter name Values
Thermostat function Heating only / Cooling only / Heating and
Heating / Cooling switching
(Only if “Heating and cooling” is selected)
Changeover protection band
(Only for Automatic switching of Heating /
Cooling)
Heating / Cooling mode aer programming
(Only if “Heating and cooling” is selected)
cooling
Manual / Automatic
5 . .. 100 (x 0.1ºC)
Heating / Cooling
The thermostat function parameter allows selecting the thermostat function: Heating only, cool­ing only, or both heating and cooling. Depending on the selected option, additional “Heating” and “Cooling” configuration sections will be enabled.
If “Heating and cooling” is selected, the Heating / Cooling switching parameter determines whether switching between heating and cooling will be done manually or automatically.
Manual switching: Switching is done through a Heating / Cooling mode communication object. Writing a “1” to this object switches to Heating mode; writing a “0” switches to Cooling mode.
Automating switching: The thermostat automatically manages the changeover between
• heating and cooling. In this case, the Changeover protection band parameter is also enabled. See 2.4.4 Heating and Cooling on page 32 for a detailed description of the automatic switching logic.
3.5
Thermostats 83
In both cases, the current thermostat function (heating or cooling) is available at any time through the Heating/Cooling mode (status) communication object.
Also, the Heating / Cooling mode aer programming parameter defines the initial mode (either
“Heating” or “Cooling”) aer an ETS download.
Thermostat on/off control
Parameter name Values
Thermostat always ON No / Yes State aer bus recovery
Last state / O / On
(Only if thermostat is NOT always ON)
Switch ON upon operating mode reception
No / Yes
(Only if thermostat is NOT always ON)
The Thermostat always ON parameter determines whether the thermostat should always be on, or whether it should be possible to switch it on and o through an associated communication object.
If the thermostat is NOT always ON:
Two communication objects are enabled (On/O and On/O (status)) to control operation of the thermostat.
A parameter State aer bus recovery is available to define the state of the thermostat aer
• at startup, or aer a bus recovery event (On, O, or the last known state)
A parameter Switch ON upon operating mode reception determines if the thermostat should automatically switch on when it receives a request to change the current operating mode.
Sending of status values
Parameter name Values
Status sending delay aer bus recovery 0 ... 255 (x 1s, 0 = Disabled)
Parameter Status sending delay aer bus recovery controls whether the initial value of the thermostat’s status objects is sent to the bus at startup or aer a bus recovery event. Values can be sent aer a configurable delay (1-255 seconds) or this function can be disabled by setting the parameter to 0.
Thermostats 84
3.5

3.5.2 Room Temperature

Parameter name Values
Room temperature Temperature Source 1
Temperature Source 1 Internal sensor
Temperature Source 2
(If enabled)
75% Temp. Source 1 - 25% Temp. Source 2 50% Temp. Source 1 - 50% Temp. Source 2 25% Temp. Source 1 - 75% Temp. Source 2
Temperature Probe IN1 Temperature Probe IN2 Temperature Probe IN3 Temperature Probe IN4 External object Internal sensor
Temperature Probe IN1
Temperature Probe IN2 Temperature Probe IN3 Temperature Probe IN4 External object
3.5.3
These parameters allow selection of the temperature sources used to measure room temper­ature. If more than one source is selected, their values can be averaged in a configurable proportion (75% / 25%, 50% / 50%, or 25% / 75%).
For each temperature source it is possible to select the internal temperature sensor, an external temperature probe connected to one of the four available multifunction inputs (IN1...IN4), or (for temperature source 1), an external communication object. If the latter is selected, a com­munication object External temperature source (DPT 9.001) will be enabled for this purpose.
Note
When using an external probe connected to one of the multifunction inputs as a tempera­ture source, make sure to configure the input accordingly.

Setpoints

Parameter name Values
Setpoint method Absolute / Relative
3.5 Thermostats 85
The Setpoint method parameter determines which method will be used to define setpoints for the thermostat operating modes: Either the Absolute Setpoints method, or the Relative Setpoints method.
See 2.4.3 Setpoints on page 28 for a detailed description of operating modes, absolute setpoints, and relative setpoints.
Absolute Setpoints
Parameter name Values
Comfort setpoint (heating) 0 ... 22 ... 50 (ºC) Standby setpoint (heating) 0 ... 20 ... 50 (ºC) Economy setpoint (heating) 0 . .. 18 ... 50 (ºC) Frost protection setpoint -10 ... 7 ... 15 (ºC) Comfort setpoint (cooling) 0 ... 24 ... 50 (ºC) Standby setpoint (cooling) 0 ... 26 ... 50 (ºC) Economy setpoint (cooling) 0 ... 28 ... 50 (ºC) Overheating protection setpoint 30 ... 35 ... 100 (ºC) Make setpoint changes permanent Manually / Upon mode changes / Never
In the Absolute Setpoints method, setpoints for each operating mode are defined as absolute temperature values. Setpoints for the heating function and for the cooling functions can be defined separately, if the thermostat has been setup to operate in both heating and cooling mode.
3.5
Thermostats 86
Relative Setpoints
Parameter name Values
Base setpoint aer programming 0 . .. 23 ... 50 (ºC) User oset (min.) -10 ... -5 ... 0 (ºC) User oset (max.) 0 ... 5 ... 10 (ºC) Comfort oset (heating) -10 . .. -1 ... 0 (ºC) Standby oset (heating) -10 ... -3 ... 0 ( ºC) Economy oset (heating) -10 ... -5 ... 0 (ºC) Frost protection setpoint -10 ... 7 ... 15 (ºC) Comfort oset (cooling) 0 . .. 1 ... 10 (ºC) Standby oset (cooling) 0 ... 3 ... 10 (ºC) Economy oset (cooling) 0 ... 5 ... 10 (ºC) Overheating protection setpoint 30 ... 35 ... 100 (ºC) Reset user oset on operating mode changes
In the Relative Setpoint method, setpoints for each operating mode (except for the building protection modes) are defined as osets relative to a common base setpoint.
No / Yes
3.5.4

Operating Modes

Parameter name Values
1-bit operating mode objects Disabled / Switch / Trigger Window status object Disabled / Enabled
The operating mode of the thermostat (comfort, standby, economy, or building protection) can be changed at any time through the Operating mode 1-byte communication object (always available), or through four 1-bit communication objects, one per mode (enabled via the 1-bit operating mode objects parameter). Additionally, the Window status communication object can be used to enter a “Forced protection” mode, regardless of the current operating mode selected by the user.
3.5
Thermostats 87

3.5.5 Heating

This section is only shown if the thermostat is setup for heating, or for both heating and cool­ing.
Parameter name Values
Control method Two-point control / P-I control
The Control method parameters determines the algorithm to use for thermostatic control: Either two-point control with hysteresis (Two-point control) or proportional-integral control (P-I control). The latter includes both P-I control with continuous output and P-I control with PWM output.
Two-point control
Parameter name Values
Upper hysteresis 1 ... 10 ... 100 (x 0.1ºC) Lower hysteresis 1 ... 10 ... 100 (x 0.1ºC) Resending period 0 ... 255 (x 1 min, 0 = Disabled)
When the two-point control method is selected, on/o commands are sent through the 1-bit
Output variable (heating) communication object. The meaning of the upper hysteresis and lower hysteresis parameter is described in detail in section 2.4.5 Control algorithms on page 34.
The value of this communication object may be resent to the bus periodically, according to the value of the Resending period parameter. Setting this parameter to 0 disables periodic resending.
3.5
Thermostats 88
P-I control
Parameter name Values
Output type Continuous (1 byte) / PWM (1 bit) Cycle time 1 ... 15 ... 255 (x 1 min) Control parameters Custom parameters
Warm water heating (5K/150min)
Floor heating (5K/240min) Electric heating (4K/100min) Convection heating (4K/90min)
Proportional band
1 . .. 4 ... 15 (K)
(Only if “custom parameters” is selected)
Integral time
5 . .. 150 ... 255 (x 1 min)
(Only if “custom parameters” is selected)
Resending period 0 ... 255 (x 1 min, 0 = Disabled)
If the proportional-integral (P-I) control method is selected, control commands will be sent through the Output variable (heating) communication object. This will be a 1-bit object or a 1-byte object, depending on the setting of the Output type parameter.
For proper operation of the P-I control method, the Cycle time, Proportional band, and Integral time parameters need to be defined. The latter two can be defined explicitly, or (more conve­niently) one of the available predefined options may be selected from the Control parameters list.
See 2.4.5 Control algorithms on page 34 for a detailed description of all control parameters involved.
Additional heating
Parameter name Values
Additional heating No / Yes Additional heating band
-100 . .. -25 ... -5 (x 0.1ºC)
(Only if additional heating is enabled)
Resending period
0 . .. 255 (x 1 min, 0 = Disabled)
(Only if additional heating is enabled)
These parameters enable control of auxiliary heating systems. For more information, please refer to 2.4.6 Additional heating and cooling on page 39.
Thermostats 89
3.5

3.5.6 Cooling

This section is only shown if the thermostat is setup for cooling, or for both heating and cooling. The available configuration parameters and communication objects are equivalent to the parameters and objects described in the to Cooling operation instead.
Heating
configuration section, except that they apply
3.6

Inputs

3.6.1 General

Parameter name Values
Input 1 type Disabled
Input 2 type Same options as for Input 1 Input 3 type Same options as for Input 1 Input 4 type Same options as for Input 1
Each of the four available multifunction inputs can be configured as a binary input (in either push button or switch/sensor mode) or as a temperature probe input via the corresponding Input N type parameter. Depending on the selection, additional parameters will be enabled. These are described in the following sections.
Binary - Push button Binary - Switch Temperature probe
3.6
Inputs 90

3.6.2 Binary - Push button

Parameter name Values
Long press time 1 ... 10 ... 50 (x 0.1 s) Short press action None
Long press action Same options as for Short press action Enable locking object [Checkbox]
Binary inputs in push button mode can trigger dierent actions for “shortpress” and “long press” operations. The Long press time parameter defines the minimum press time to dierentiate between short and long presses.
The specific actions to be triggered are configured with the Short press action and Long press action parameters. Additional options for each type of action are described next.
Send binary values Dimmer control Shutter control Scene control
The Enable locking object checkbox enables an additional communication object that can be used to lock operationof this input. While the input is locked, short and long presses are ignored, and no actions are triggered.
Send binary values
Parameter name Values
Send value Send 0 / Send 1 / Toggle
If the “Send binary values” action is selected, a binary value will be sent to the bus when the action is triggered. The Send value parameter determines the value to send: This can be 0, 1, or
“Toggle” (alternates between 0 and 1).
3.6
Inputs 91
Dimmer control
Parameter name Values
Operation On
O Alternate on/o Brighter Darker Alternate brighter/darker
Dimming step
(Only for dimming operations)
100% / 50% / 25% / 12.5% / 6.25% / 3.1% /
1.6%
If the “Dimmer control” action is selected, the Operation parameter determines the exact operation to perform: A switching operation (on, o, or alternate between on and o) or a dimming operation (brighter, darker, or alternate between brighter and darker).
For dimming operations, the Dimming step parameter determines how much should the light intensity be increased or decreased. When the action is triggered, a dimming command will be sent to the bus requesting that the light intensity is adjusted (increased or decreased) by this amount.
Shutter control
Parameter name Values
Operation Move up
Move down Alternate move up/down Step up Step down Alternate step up/down
If the “Shutter control” action is selected, the Operation parameter determines the exact opera­tion to perform: A move operation (move up, move down, or alternate between move up and move down) or a step operation (step up, step down, or alternate between step up and step down).
3.6
Inputs 92
Scene control
Parameter name Values
Scene operation Recall scene / Save scene Scene number 1 . .. 64 Scene type External / Internal
If the “Scene control” action is selected, a specific scene will be recalled or saved when the action is triggered, depending on the Scene operation parameter. The Scene number and Scene type parameter select the scene that will be aected by this operation.
3.6.3

Binary - Switch

Parameter name Values
Action when contact CLOSES None / Send 0 / Send 1 / Toggle 0/1 Action when contact OPENS Same options as for Action when contact
CLOSES
Evaluate initial state No / Yes Enable locking object [Checkbox]
Binary inputs in switch/sensor mode can trigger actions when the state of the input changes. A dierent action (send 0, send 1, or toggle between 0 and 1) can be associated to each state (Action when contact CLOSES and Action when contact OPENS).
Additionally, the Evaluate initial state parameter determines whether the state of the input should be evaluated (and the corresponding action triggered) at application startup time, and also aer bus voltage recovery.
The Enable locking object checkbox enables an additional communication object that can be used to lock operation of this input. While the input is locked, any changes in the input state are ignored, and no actions are triggered.
3.6
Inputs 93

3.6.4 Temperature probe

Parameter name Values
Calibration oset -50 . .. 0 ... 50 (x 0.1ºC) Sending period 0 ... 255 (x 10 s, 0 = Disabled) Send when change is greater than 0 . .. 255 (x 0.1ºC, 0 = Disabled) Alarm function Disabled
High temperature alarm threshold
(If high temperature alarm is enabled)
Low temperature alarm threshold
(If low temperature alarm is enabled)
The Calibration oset, Sending period, and Send when change is greater than parameters are equivalent to the corresponding parameters for the internal temperature probe (see 3.2.2
Internal temperature sensor on page 45).
High temperature alarm Low temperature alarm High/low temperature alarms
-30 . .. 30 ... 125 (ºC)
-30 . .. 10 ... 125 (ºC)
If the temperature cannot be read (for example because the temperature probe is broken, or disconnected from the input) an error is signalled through a separate [INx] Probe error communication object.
An alarm function can be enable to detect high and/or low temperatures. This is done through the Alarm function parameter. Also the thresholds for high and low temperature alarms can be defined. The alarm condition is signalled through the [INx] Temperature alarm communication object.
3.7

Scenes

3.7.1 General

Parameter name Values
Send read requests at startup No / Yes Scene actuator 1 [Checkbox] ... Scene actuator 8 [Checkbox]
3.7 Scenes 94
Up to 8 scene actuators can be enabled through the corresponding checkboxes. The configura­tion parameters for each scene actuators are described in the next section.
The parameter Send read requests at startup determines whether read requests will be sent at application startup (and aer bus voltage recovery) for the actuators’ communication objects. See 2.6.4 Storing scenes on page 42.
3.7.2

Scene actuator N

Parameter name Values
Object type Switching
1-byte unsigned int 1-byte signed int Percentage 2-byte unsigned int 2-byte signed int 2-byte float
3-byte RGB color Scene #1 number Disabled / 1 ... 64 Scene #1 allow saving
(Only if scene not disabled)
Scene #1 initial value
(Only if scene not disabled)
Scene #2 Same parameters as for scene #1 ... Scene #8 Same parameters as for scene #1
No / Yes
[See note 1]
The Object type parameter determines the data type of the communication object for the scene actuator. The following table shows supported data types and the corresponding value ranges.
3.7
Scenes 95
Data type Value range
Binary 0 (o) / 1 (on) 1-byte unsigned int 0 . .. 255 1-byte signed int -128 ... 127 Percentage 0% . .. 100% 2-byte unsigned int 0 ... 65535 2-byte signed int -32768 ... 32767 2-byte float -671088.64 ... 670760.96 3-byte RGB color #000000 ... #
Each scene actuator can participate in up to 8 dierent scenes, identified through the Scene #X number parameters.
For each scene in which the actuator is participating, an initial value for the actuator in that scene can be defined (Scene #X initial value). This is the value that will be sent to the scene actuator’s communication object when the specified scene number is recalled.
Finally, the Scene #X allow saving parameter determines whether this value should be updated when a “store request” is received for the specified scene number. See 2.6.4 Storing scenes on page 42 for additional information regarding storing of scenes.
3.7
Scenes 96

Advanced topics

4.1 Product customization

4.1.1 Background images

The appearance of the user interface of the Iddero Verso touch panel can be customized by
using custom background images. Custom background images are uploaded to the device through the USB connection.
Background images should be in PNG or JPEG format. Resolution should be 272x480 pixels in portrait mode, or 480x272 pixels in landscape mode. File names should be as shown in the following table (if using JPEG images, the extension should be .png):
File name Aected pages
.jpgor.jpeg
4
instead of
home.png Home page favs.png Favorites and Edit favorites pages page1.png . .. page6.png Control pages 1 ... 6 default.png Default (all other pages)
In order to upload the images to the device:
1. Copy the images to the root directory of a FAT32-formatted USB flash drive
Connect the USB flash drive to the Iddero Verso (use the Iddero USB extension cable, part
2. number E-KUSB1)
3.
Go to the System settings page, then select USB > Copy images The new images will be used immediately.
Existing images can be discarded at any time by selecting USB > Discard installed images.
97

4.1.2 Custom languages

It is possible to install a custom language file in order to translate any system texts to a new lan­guage. Please contact Iddero technical support (support@iddero.com) for further information on this topic.
4.2

Firmware updates

If you need to update the firmware of the Iddero Verso touch panel, you can do so through the device’s USB connection.
First, you will need to download the firmware release that you want to use. This will typically be a file with FAT32-formatted USB flash drive. Specifically, do not change the filename, as otherwise it will not be recognized as a valid firmware file.
Connect the USB flash drive to the Iddero Verso touch panel (use the Iddero USB extension cable, part number E-KUSB1) and power on (or reboot) the device.
During the boot process, the USB flash drive will be automatically detected, and the firmware update applied. The whole process takes only a few seconds; the device will beep three times once the update is complete, and will boot with the new firmware automatically.
Note
Iddero Verso will not perform the firmware update if the version of the firmware file found in the USB flash drive matches the version of the currently installed firmware.
.bin
extension. This file should be copied unmodified to the root directory of a
You can check the current firmware version at any time in the Info page located in the System
Settings menu (see 2.1.6.3 System settings page on page 15).
4.2
Firmware updates 98

Annex

5.1 Communication Objects

Miscellaneous
Num. Name Type Flags
0 [Misc] Date DPT_Date CTRWU
1 [Misc] Time DPT_TimeOfDay CTRWU 2 [Misc] Internal temperature DPT_Value_Temp CTR-- 3 [Misc] External temperature DPT_Value_Temp C--WU 4 [Misc] Run/save external scene DPT_SceneControl CT--- 5 [Misc] Wake up DPT_Trigger C--W- 8 [Misc] Timer group 1 lock DPT_Enable C--W- 9 [Misc] Timer group 2 lock DPT_Enable C--W-
10 [Misc] Timer group 3 lock DPT_Enable C--W- 11 [Misc] Timer group 4 lock DPT_Enable C--W- 12 [Misc] Gesture: Up DPT_Switch CT--- 13 [Misc] Gesture: Down DPT_Switch CT--- 14 [Misc] Gesture: Le DPT_Switch CT--- 15 [Misc] Gesture: Right DPT_Switch CT--- 16 [Misc] Gesture: Multitouch DPT_Switch CT---
5
99
Components
Num. Name Type Flags
[Cx.y] Binary indicator DPT_Switch C--WU [Cx.y] Enumerated indicator DPT_Value_1_Ucount C--WU [Cx.y] 1-byte unsigned int indicator DPT_Value_1_Ucount C--WU [Cx.y] 1-byte signed int indicator DPT_Value_1_Count C--WU [Cx.y] Percentage indicator DPT_Scaling C--WU [Cx.y] 2-byte unsigned int indicator DPT_Value_2_Ucount C--WU
17, 20, 23, 26 ... 158
[Cx.y] 2-byte signed int indicator DPT_Value_2_Count C--WU [Cx.y] 2-byte float indicator DPT 9.xxx C--WU [Cx.y] Dimmer level indicator DPT_Scaling C--WU [Cx.y] Shutter position indicator DPT_Scaling C--WU [Cx.y] RGB colour DPT_Colour_RGB CTRWU [Cx.y] RGB red channel DPT_Scaling CTRWU [Cx.y] Temperature indicator DPT_Value_Temp C--WU
[Cx.y] Binary control DPT_Switch CTR-- [Cx.y] Enumerated control DPT_Value_1_Ucount CTR-- [Cx.y] 1-byte unsigned int control DPT_Value_1_Ucount CTR-- [Cx.y] 1-byte signed int control DPT_Value_1_Count CTR-- [Cx.y] Percentage control DPT_Scaling CTR-- [Cx.y] 2-byte unsigned int control DPT_Value_2_Ucount CTR-- [Cx.y] 2-byte signed int control DPT_Value_2_Count CTR-- [Cx.y] 2-byte float control DPT 9.xxx CTR--
18, 21, 24,
27 ... 159
[Cx.y] Light on/o DPT_Switch CTR-- [Cx.y] Shutter step/stop DPT_Step CT--- [Cx.y] White channel DPT_Scaling CTRWU [Cx.y] RGB green channel DPT_Scaling CTRWU [Cx.y] Temperature control DPT_Value_Temp CTR-- [Cx.y] Temperature oset control DPT_Value_Tempd CTR-- [Cx.y] Temperature step control DPT_Step CT--- [Cx.y] Alarm trigger DPT_Alarm C--WU
[Cx.y] Relative dimming control DPT_Control_Dimming CT--- [Cx.y] Absolute dimming control DPT_Scaling CTR-- [Cx.y] Shutter up/down DPT_UpDown CT---
19, 22, 25,
28 ... 160
[Cx.y] Shutter position control DPT_Scaling CTR-- [Cx.y] RGB blue channel DPT_Scaling CTRWU [Cx.y] Temperature oset status DPT_Value_Tempd C--WU [Cx.y] Alarm acknowledge DPT_Ack CT-W-
5.1 Communication Objects 100
Loading...