KNX AQS/TH-UP Touch Installation And Adjustment Manual

Page 1
KNX AQS/TH-UP Touch
Combined indoor sensor
Item numbers 70619 (black), 70620 (pure white)
EN
Installation and Adjustment
Page 2
Page 3
1 Content
Sensor KNX AQS/TH-UP Touch • from ETS programme version 1.0
Status: 23.10.2018 • Technical changes and errors excepted.
1. Description ........................................................................................... 4
1.0.1. Scope of delivery .......................................................................................... 5
1.1. Technical specifications ........................................................................................... 5
1.1.1. Accuracy of the measurement ..................................................................... 6
2. Installation and commissioning ........................................................... 6
2.1. Installation notes ...................................................................................................... 6
2.2. Installation position .................................................................................................. 7
2.3. Composition ............................................................................................................. 8
2.3.1. Housing .......................................................................................................... 8
2.4. Assembly of the sensor ........................................................................................... 8
2.5. Notes on mounting and commissioning ................................................................ 8
3. Display and operation at the device .................................................... 9
3.1. Mode display and manual temperature controller ................................................ 9
3.2. Change ambient temperature with the buttons .................................................. 10
4. Transfer protocol ............................................................................... 12
4.1. List of all communications objects ....................................................................... 12
5. Parameter setting .............................................................................. 23
5.1. Behaviour on power failure/ restoration of power .............................................. 23
5.2. General settings ..................................................................................................... 23
5.3. Temperature value ................................................................................................. 23
5.4. Temperature threshold values .............................................................................. 24
5.4.1. Threshold value 1, 2, 3 ............................................................................... 24
5.4.1.1. Threshold value ............................................................................ 24
5.4.1.2. Switching output .......................................................................... 25
5.4.1.3. Block .............................................................................................. 26
5.5. Temperature PI control .......................................................................................... 26
5.5.0.1. General control ............................................................................. 26
5.5.1. General set point values ............................................................................. 28
5.5.1.1. Set point Comfort ......................................................................... 29
5.5.1.2. Standby setpoint ........................................................................... 30
5.5.1.3. Eco setpoint ................................................................................... 30
5.5.1.4. Setpoint values for frost/heat protection (building protection) 31
5.5.1.5. General control variables ............................................................. 31
5.5.2. Heating control level 1/2 ............................................................................. 32
5.5.3. Cooling control level 1/2 ............................................................................. 34
5.6. Humidity measurement ......................................................................................... 36
5.7. Humidity threshold values .................................................................................... 36
5.7.1. Threshold value 1, 2 ................................................................................... 37
5.7.1.1. Threshold value ............................................................................ 37
5.7.1.2. Switching output .......................................................................... 38
5.7.1.3. Block .............................................................................................. 38
5.8. Humidity PI control ................................................................................................ 39
Page 4
2 Content
Sensor KNX AQS/TH-UP Touch • from ETS programme version 1.0
Status: 23.10.2018 • Technical changes and errors excepted.
5.8.0.1. General control ............................................................................. 39
5.8.0.2. Controller setpoint ........................................................................ 40
5.8.0.3. Dehumidification and/or humidification ..................................... 41
5.9. Dewpoint measurement ........................................................................................ 42
5.9.1. Cooling medium temp. monitoring ........................................................... 42
5.9.1.1. Threshold value ............................................................................ 42
5.9.1.2. Switching output .......................................................................... 43
5.9.1.3. Blocking ......................................................................................... 43
5.10.Absolute humidity ................................................................................................. 44
5.11.Comfort field .......................................................................................................... 45
5.12.CO
2
parameter settings ......................................................................................... 45
5.13.CO2 threshold values ............................................................................................ 46
5.13.1. Threshold value 1, 2, 3, 4 ........................................................................... 46
5.13.1.1.Threshold value ............................................................................ 46
5.13.1.2.Switching output .......................................................................... 47
5.13.1.3.Block .............................................................................................. 48
5.14.CO2 PI-control ........................................................................................................ 49
5.14.0.1.General control ............................................................................. 49
5.14.0.2.Controller setpoint ........................................................................ 49
5.14.0.3.Ventilation control ........................................................................ 50
5.15.Variable comparator .............................................................................................. 51
5.15.1. Control variable comparator 1/2 ................................................................ 51
5.16.Logic ........................................................................................................................ 52
5.16.0.1.AND logic ....................................................................................... 52
5.16.0.2.OR logic ......................................................................................... 52
5.16.1. AND logic 1-4 and OR logic outputs 1-4 ................................................... 52
5.16.1.1.Block .............................................................................................. 54
5.16.2. Connection inputs of the AND logic .......................................................... 54
5.16.3. Connection inputs of the OR logic ............................................................. 56
5.17.Display .................................................................................................................... 56
5.18.Pushbutton ............................................................................................................. 58
5.18.1. Pushbutton for temperature control ......................................................... 59
5.18.2. Pushbutton interface .................................................................................. 59
Page 5
3 Clarification of signs
This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to­date version of the manual is available.
Clarification of signs used in this manual
Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician.
Safety advice.
Safety advice for working on electrical connections, components, etc.
DANGER!
... indicates an immediately hazardous situation which will lead to death or severe injuries if it is not avoided.
WARNING!
... indicates a potentially hazardous situation which may lead to death or severe injuries if it is not avoided.
CAUTION!
... indicates a potentially hazardous situation which may lead to trivial or minor injuries if it is not avoided.
ATTENTION!
... indicates a situation which may lead to damage to property if it is not avoided.
ETS In the ETS tables, the parameter default settings are marked by
underlining.
Page 6
4 Description
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
1. Description
The Sensor KNX AQS/TH-UP Touch measures CO2 concentration, temperature and humidity and calculates the dew point. The sensor can receive external measured values via the bus and process them with the own data to overall values (mixed values, e. g. room average). The KNX AQS/TH-UP Touch offers two push buttons that may be used for changing the ambient temperature (target value), for switching between operating modes or as free programmable bus push buttons.
The KNX AQS/TH-UP Touch provides switching outputs with adjustable threshold values. The switching outputs and further communication objects can be linked by AND and OR logic gates. Additionally, an integrated actuating variable comparator can compare and output values that are received via communication objects.
Integrated PI controllers allows for control of a ventilation (depending on CO
2
concentration and air humidity) and a heating/cooling system (depending on temperature). The KNX AQS/TH-UP Touch can emit a warning to the bus as soon as the area of optimum comfort (according to DIN 1946) is left.
The integrated display shows the own values and data received from the bus (e.g. date, time). The device is completed with a frame of the switching series installed in the building and thus merges with the interior.
Functions:
Measurement of CO
2
concentration of the air, of temperature and air
humidity (absolute and relative), calculation of the dew point
Mixed values from own measured values and external values (proportions can be set in percentage)
Display 1-3 rows (own values or values received from the bus) or display of temperature control (see Mode display and manual temperature controller)
2 push buttons. Configuration as bus push button or for changing ambient temperature and switching between operating modes (see Change ambient temperature with the buttons)
PI controller for heating (one or two step) and cooling (one or two step) depending on temperature. Control according to separate target values or basic target temperature
PI controller for ventilation depending on humidity and CO
2
concentration: dehumidification/humidification (one step) or dehumidification (one or two step)
Threshold values can be adjusted per parameter or via communication objects: 3 × temperature, 2 × humidity, 4 × CO
2
4 AND and 4 OR logic gates with each 4 inputs. Every switching incident as well as 16 logic inputs in the form of communication objects, may be used as inputs for the logic gates. The output of each gate may optionally be configured as 1 bit or 2 x 8 bits
2 actuating variable comparators for output of minimum, maximum or average values. Each with 5 inputs (for values received via communication objects)
Page 7
5 Description
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Configuration is made using the KNX software ETS 5. The product file can be downloaded from the ETS online catalogue and the Elsner Elektronik website on
www.elsner-elektronik.de in the “Service” menu.
1.0.1. Scope of delivery
Housing with display
Base plate
You will need in addition (not supplied):
Socket Ø 60 mm, 42 mm deep
Frame (for element 55 x 55 mm), suitable for the switching programme used in the building
1.1. Technical specifications
Housing ABS plastic material Colours • similar to RAL 9005 jet black
• similar to RAL 9010 pure white
Mounting
In-wall (wall mounting in socket Ø 60 mm, 42 mm deep, resp. cavity wall socket for hole Ø 68 mm)
Protection category IP 20 Dimensions Housing approx. 55 x 55 (W x H, mm), mounting depth
approx. 8 mm, base plate approx. 71 x 71 (W x H, mm) Total weight approx. 55 g Ambient temperature Operation 0…+50°C, storage -10…+60°C Ambient air humidity max. 95% RH, avoid bedewing Operating voltage KNX bus voltage Bus current max. 20 mA Data output KNX +/- bus terminal plug BCU type Own micro controller PEI type 0 Group addresses max. 254 Allocations max. 254 Communication objects 224 CO2 measurement range 300...5000 ppm
CO2 resolution 1 ppm
CO2 accuracy ± 50 ppm plus ± 3% of the measured value (Mind the
notes on Accuracy of the measurement) Temperature measurement
range
0…+50°C
Temperature resolution 0.1°C Temperature accuracy ± 0,5°C at 0…+50°C (Mind the notes on Accuracy of the
measurement)
Page 8
6 Installation and commissioning
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
The product conforms with the provisions of EU guidelines.
1.1.1. Accuracy of the measurement
Measurement variations from permanent sources of interference (see chapter Installation position) can be corrected in the ETS in order to ensure the specified accuracy of the sensor (offset).
To ensure a correct CO
2
measurement, the device must be installed in a windproof
socket.
When measuring temperature, the self-heating of the device is considered by the electronics. The heating is compensated by the software.
2. Installation and commissioning
2.1. Installation notes
Installation, testing, operational start-up and troubleshooting should only be performed by an electrician.
CAUTION! Live voltage!
There are unprotected live components inside the device.
National legal regulations are to be followed.
Ensure that all lines to be assembled are free of voltage and take precautions against accidental switching on.
Do not use the device if it is damaged.
Take the device or system out of service and secure it against unintentional use, if it can be assumed, that risk-free operation is no longer guaranteed.
The device is only to be used for its intended purpose. Any improper modification or failure to follow the operating instructions voids any and all warranty and guarantee claims.
After unpacking the device, check it immediately for possible mechanical damage. If it has been damaged in transport, inform the supplier immediately.
Humidity measurement range
0% RH …95% RH
Humidity resolution 0.1% Humidity accuracy ±7,5% RH at 0...10% RH
±4,5% RH at 10...90% RH ±7,5% RH at 90...95% RH
Humidity drift ± 0.5% R.H. per year in normal air
Page 9
7 Installation and commissioning
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
The device may only be used as a fixed-site installation; that means only when assembled and after conclusion of all installation and operational start-up tasks and only in the surroundings designated for it.
Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions.
2.2. Installation position
The Sensor KNX AQS/TH-UP Touch is made for wall mounting in a socket (Ø 60 mm, 42 mm deep).
May be installed and operated in dry interior rooms only. Avoid condensation.
When selecting an installation location, please ensure that the measurement results are affected as little as possible by external influences. Possible sources of interference include:
Direct sunlight
Drafts from windows and doors
Draft from ducts which lead from other rooms or from the outside to the junction box in which the sensor is mounted
Warming or cooling of the building structure on which the sensor is mounted, e.g. due to sunlight, heating or cold water pipes
Connection lines and ducts which lead from warmer or colder areas to the sensor
Measurement variations from permanent sources of interference can be corrected in the ETS in order to ensure the specified accuracy of the sensor (offset).
To ensure a correct CO
2
measurement, the device must be installed in a windproof
socket.
Fig. 1: Sectional drawing. The Sensor KNX AQS/TH-UP Touch fits into a standard socket (Ø 60 mm, depth 42 mm).
The frame is not included!
Page 10
8 Installation and commissioning
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
2.3. Composition
2.3.1. Housing
2.4. Assembly of the sensor
First of all fit the windproof socket with connection. Also seal inlet pipes to avoid infiltration. Screw the base plate onto the socket and position the frame of the switching programme. Connect the bus line +/- to the black-red plug. Pin the housing with the notches on to the metal frame, so that device and frame are fixed.
2.5. Notes on mounting and commissioning
Never expose the device to water (e.g. rain) or dust. This can damage the electronics. You must not exceed a relative humidity of 95%. Avoid condensation.
After the bus voltage has been applied, the device will enter an initialisation phase lasting a few seconds. During this phase no information can be received or sent via the bus.
1
2
6
3
4
5
Fig. 2 1 Base plate 2 Openings for air circulation 3 Touch sensitive buttons 4 Catches 5 Programming LED (recessed) 6 Programming button (recessed) for teaching device 7 KNX terminal BUS +/-
7
Page 11
9 Display and operation at the device
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
3. Display and operation at the device
Detailed specifications for the display and the use of the push buttons are set in the ETS.
Basically the display can show a two-row or three-row text (e. g. for measured values) or a temperature controller. You can switch between the two types by pressing one of the buttons, if this has not been disabled in the ETS.
3.1. Mode display and manual temperature
controller
Depending on the ETS setting selected, the mode display will only display show the current target value, or the base target value setting with scale display. The manually adjustable range can be set in the ETS.
The following display options are available:
Fig. 3
Mode display with current target value and/or base target value
Fig. 4
Mode display with scale display for adjusting the base target value. The control position in the image reads "Base target value reduced".
Fig. 5
Mode display with scale display and number. Shows the set target value change. The control position in the image reads "Base target value reduced to 1.0°".
Fig. 6
Mode display with scale display and range. Shows the possible adjustment range (as set in the ETS). The control position in the image reads "Base target value reduced".
Page 12
10 Display and operation at the device
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Symbols
Priority (points)
One point: Priority 1/priority control. It is not possible to adjust the temperature automation system manually. Neither the target temperature nor the operating modes can be changed using the buttons on the unit.
Two points: Priority 2. The target temperature and operating mode can be changed using the buttons.
3.2. Change ambient temperature with the
buttons
If the mode display is active, the target ambient temperature and the operating mode can be changed manually using the buttons. The button functions can be blocked in the ETS or be suppressed for Priority 1 operating modes. The individual operating modes can also be locked for manual selection in the ETS.
Comfort mode. Comfort (present) target temperature will be used.
Standby mode. Standby (absent during day) target temperature will be used.
Eco mode. Night target temperature will be used.
Building protection mode. Building protection target temperature will be used. The symbol will blink when the mode has been activated but the activation delay has not yet expired.
Heating mode. Heating will be provided.
Cooling mode Cooling will be provided.
Fig. 7
Mode display with scale display, range and number. Displays the possible adjustment range (as set in the ETS) and the set target value change. The control position in the image reads "Base target value reduced to 1.0°".
Fig. 8
In "HVAC mode with 2x 8 bits" control mode, points are shown under the symbol, to indicate the running priority of the current mode.
Page 13
11 Display and operation at the device
Sensor KNX AQS/TH-UP Touch as of software 0.1.0 • Version: 23.10.2018 • Technical changes and errors excepted.
Decrease target temperature (-)
briefly press left button
Ambient temperature in the current mode is decreased. The sep-size is defined in the ETS (0.1°C to 5°C).
Increase target temperature (+)
briefly press right button
Ambient temperature in the current mode is increased. The sep-size is defined in the ETS (0.1°C to 5°C).
Change mode press
left or right button longer than 2 secs.
Changes between the operating modes Comfort, Standby, Eco and Building Protection (if deblocked in the ETS).
Extend Comfort mode
in Eco mode: press both buttons at the same time longer than 2 secs.
Switches from Eco to Comfort mode again for a certain time (e. g. if the rooms are used longer in the evening). The period is defined in the ETS (up to 10 hours). The time remaining in Comfort mode is displayed.
Page 14
12 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
4. Transfer protocol
Units:
Temperatures in degrees Celsius Air humidity in % Absolute air humidity in g/kg and/or g/m
3
CO2 content in ppm Variables in %
4.1. List of all communications objects
Abbreviation flags:
C Communication R Read WWrite T Transfer UUpdate
No Name Function Flags Data Point Type Size
0 Software version readable R-CT [217.1]
DPT_Version
2 Bytes
1 Temperature/humidity malfunction
sensor
Output R-CT [1.1]
DPT_Switch
1 Bit
2 CO2 sensor malfunction Output R-CT [1.1]
DPT_Switch
1 Bit
3 Outside temperature reading Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
4 Inside temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
5 Overall temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
6 Min./max. temperature value
request
Input -WC- [1.17]
DPT_Trigger
1 Bit
7 Minimum temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
8 Maximum temperature reading Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
9 Reset min./max. temperature value Input -WC- [1.17]
DPT_Trigger
1 Bit
10 Temp. threshold value 1: Absolute
value
Input/ Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
11 Temp. threshold value 1: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
12 Temp. threshold value 1:
Switching delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
Page 15
13 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
13 Temp. threshold value 1:
Switching delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
14 Temp. threshold value 1: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
15 Temp. threshold value 1:
Switching output block
Input -WC- [1.2]
DPT_Bool
1 Bit
16 Temp. threshold value 2: Absolute
value
Input/ Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
17 Temp. threshold value 2: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
18 Temp. threshold value 2:
Switching delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
19 Temp. threshold value 2:
Switching delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
20 Temp. threshold value 2: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
21 Temp. threshold value 2:
Switching output block
Input -WC- [1.2]
DPT_Bool
1 Bit
22 Temp. threshold value 3: Absolute
value
Input/ Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
23 Temp. threshold value 3: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
24 Temp. threshold value 3:
Switching delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
25 Temp. threshold value 3:
Switching delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
26 Temp. threshold value 3: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
27 Temp. threshold value 3:
Switching output block
Input -WC- [1.2]
DPT_Bool
1 Bit
29 TR_1_ Eco-Standby HVAC 1 Input -WC- [20.102]
DPT_HVACMode
1 Byte
30 TR_1_ Comfort Activation HVAC 2 Input RWCT[20.102]
DPT_HVACMode
1 Byte
31 TR_1_ Frost/Heat activation Input RWCT[1.1]
DPT_Switch
1 Bit
32 TR_1_ Blocking object (active at
value = 1)
Input -WC- [1.1]
DPT_Switch
1 Bit
33 TR_1_ Target value, current Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
34 TR_1_ Switching object (0:Heat |
1:Cool)
Input -WC- [1.1]
DPT_Switch
1 Bit
35 TR_1_ Target value, comfort heat-
ing
Input/ Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
No Name Function Flags Data Point Type Size
Page 16
14 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
36 TR_1_ Target value, comfort heat-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
37 TR_1_ Target value, comfort cool-
ing
Input/ Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
38 TR_1_ Target value, comfort cool-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
39 TR_1_ Target value_Basic offset
16 Bit
Input/ Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
40 TR_1_ Target value, Standby heat-
ing
Input/ Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
41 TR_1_ Target value, Standby heat-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
42 TR_1_ Target value, Standby cool-
ing
Input/ Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
43 TR_1_ Target value, Standby cool-
ing (1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
44 TR_1_ Target value, Eco heating Input/
Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
45 TR_1_ Target value, Eco heating
(1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
46 TR_1_ Target value, Eco cooling Input/
Output
RWCT[9.1]
DPT_Value_Temp
2 Bytes
47 TR_1_ Target value, Eco cooling
(1:+ | 0:-)
Input -WC- [1.1]
DPT_Switch
1 Bit
48 TR_1_ Control variable heating
(stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
49 TR_1_ Control variable heating
stage 2
Output R-CT [5.1]
DPT_Scaling
1 Byte
50 TR_1_ Control variable cooling
(stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
51 TR_1_ Control variable cooling
stage 2
Output R-CT [5.1]
DPT_Scaling
1 Byte
52 TR_1_ Status heating 1 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
53 TR_1_ Status heating 2 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
54 TR_1_ Cooling status 1 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
55 TR_1_ Cooling status 2 (1=ON |
0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
56 TR_1_ Comfort Delay Status Input/
Output
RWCT[1.1]
DPT_Switch
1 Bit
57 TR_1_Comfort extension time (in
sec)
Input/ Output
RWCT[7.5]
DPT_TimePeriodSec
2 Bytes
No Name Function Flags Data Point Type Size
Page 17
15 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
58 TR_1_Belimo_Control variable Output R-CT [5.1]
DPT_Scaling
1 Byte
59 Outside humidity reading Input -WC- [9.7]
DPT_Value_Humidity
2 Bytes
60 Inside humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
61 Overall humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
62 Min./max. humidity value request Input -WC- [1.17]
DPT_Trigger
1 Bit
63 Minimum humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
64 Maximum humidity reading Output R-CT [9.7]
DPT_Value_Humidity
2 Bytes
65 Reset min./max. humidity value Input -WC- [1.17]
DPT_Trigger
1 Bit
66 Humidity threshold value 1: Abso-
lute value
Input/ Output
RWCT[9.7]
DPT_Value_Humidity
2 Bytes
67 Humidity threshold value 1: (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
68 Humidity threshold value 1: Switch-
ing delay from 0 to 1
Input -WC- [[9.010]
DPT_Value_Time
2 Bytes
69 Humidity threshold value 1: Switch-
ing delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
70 Humidity threshold value 1: Switch-
ing output
Output R-CT [1.1]
DPT_Switch
1 Bit
71 Humidity threshold value 1: Switch-
ing output block
Input -WC- [1.2]
DPT_Bool
1 Bit
72 Humidity threshold value 2: Abso-
lute value
Input/ Output
RWCT[9.7]
DPT_Value_Humidity
2 Bytes
73 Humidity threshold value 2: (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
74 Humidity threshold value 2: Switch-
ing delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
75 Humidity threshold value 2: Switch-
ing delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
76 Humidity threshold value 2: Switch-
ing output
Output R-CT [1.1]
DPT_Switch
1 Bit
77 Humidity threshold value 2: Switch-
ing output block
Input -WC- [1.2]
DPT_Bool
1 Bit
78 Humidity controller: Blocking object Input -WC- [1.2]
DPT_Bool
1 Bit
79 Humidity controller: Target value Input/
Output
RWCT[9.7]
DPT_Value_Humidity
2 Bytes
No Name Function Flags Data Point Type Size
Page 18
16 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
80 Humidity controller: Target value
(1:+ | 0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
81 Humidity controller: Control varia-
ble dehumidification (stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
82 Humidity controller: Control varia-
ble dehumidification stage 2
Output R-CT [5.1]
DPT_Scaling
1 Byte
83 Humidity controller: Control varia-
ble humidification
Output R-CT [5.1]
DPT_Scaling
1 Byte
84 Humidity controller: Dehumidifica-
tion 1 status (1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
85 Humidity controller: Dehumidifica-
tion 2 status (1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
86 Humidity controller: Humidification
status (1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
87 Dewpoint temperature Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
88 Coolant temp.: Threshold value Output R-CT [9.1]
DPT_Value_Temp
2 Bytes
89 Coolant temp.: Actual value Input -WC- [9.1]
DPT_Value_Temp
2 Bytes
90 Coolant temp.: Offset change (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
91 Coolant temp.: Switching delay
from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
92 Coolant temp.: Switching delay
from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
93 Coolant temp.: Switching output Output R-CT [1.1]
DPT_Switch
1 Bit
94 Coolant temp.: Switching output
block
Input -WC- [1.2]
DPT_Bool
1 Bit
95 Absolute humidity [g/kg] Output R-CT [14.5]
DPT_Value_Ampli­tude
4 Bytes
96 Absolute humidity [g/m³] Output R-CT [14.17]
DPT_Value_Density
4 Bytes
97 Ambient climate status: 1 = com-
fortable | 0 = uncomfortable
Output R-CT [1.2]
DPT_Bool
1 Bit
98 Outside CO2 reading Input -WC- [9.8]
DPT_Value_AirQua­lity
2 Bytes
99 Inside CO2 Internal reading Output R-CT [9.8]
DPT_Value_AirQua­lity
2 Bytes
No Name Function Flags Data Point Type Size
Page 19
17 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
100 Total CO2 reading Output R-CT [9.8]
DPT_Value_AirQua­lity
2 Bytes
101 CO2 maximum value request Input -WC- [1.17]
DPT_Trigger
1 Bit
102 Maximum CO2 reading Output R-CT [9.8]
DPT_Value_AirQua­lity
2 Bytes
103 Reset CO2 maximum value Input -WC- [1.17]
DPT_Trigger
1 Bit
104 CO2 threshold value 1: Absolute
value
Input/ Output
RWCT[9.8]
DPT_Value_AirQua­lity
2 Bytes
105 CO2 threshold value 1: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
106 CO2 threshold value 1: Switching
delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
107 CO2 threshold value 1: Switching
delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
108 CO2 threshold value 1: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
109 CO2 threshold value 1: Switching
output block
Input -WC- [1.2]
DPT_Bool
1 Bit
110 CO2 threshold value 2: Absolute
value
Input/ Output
RWCT[9.8]
DPT_Value_AirQua­lity
2 Bytes
111 CO2 threshold value 2: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
112 CO2 threshold value 2: Switching
delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
113 CO2 threshold value 2: Switching
delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
114 CO2 threshold value 2: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
115 CO2 threshold value 2: Switching
output block
Input -WC- [1.2]
DPT_Bool
1 Bit
116 CO2 threshold value 3: Absolute
value
Input/ Output
RWCT[9.8]
DPT_Value_AirQua­lity
2 Bytes
117 CO2 threshold value 3: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
118 CO2 threshold value 3: Switching
delay from 0 to 1
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
119 CO2 threshold value 3: Switching
delay from 1 to 0
Input -WC- [9.010]
DPT_Value_Time
2 Bytes
No Name Function Flags Data Point Type Size
Page 20
18 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
120 CO2 threshold value 3: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
121 CO2 threshold value 3: Switching
output block
Input -WC- [1.2]
DPT_Bool
1 Bit
122 CO2 threshold value 4: Absolute
value
Input/ Output
RWCT[9.8]
DPT_Value_AirQua­lity
2 Bytes
123 CO2 threshold value 4: (1:+ | 0:-) Input -WC- [1.2]
DPT_Bool
1 Bit
124 CO2 threshold value 4: Switching
delay from 0 to 1
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
125 CO2 threshold value 4: Switching
delay from 1 to 0
Input -WC- [7.5]
DPT_TimePeriodSec
2 Bytes
126 CO2 threshold value 4: Switching
output
Output R-CT [1.1]
DPT_Switch
1 Bit
127 CO2 threshold value 4: Switching
output block
Input -WC- [1.2]
DPT_Bool
1 Bit
128 CO2 controller: Blocking object Input -WC- [1.2]
DPT_Bool
1 Bit
129 CO2 controller: Target value Input/
Output
RWCT[9.8]
DPT_Value_AirQua­lity
2 Bytes
130 CO2 controller: Target value (1:+ |
0:-)
Input -WC- [1.2]
DPT_Bool
1 Bit
131 CO2 controller: Control variable
ventilation (stage 1)
Output R-CT [5.1]
DPT_Scaling
1 Byte
132 CO2 controller: Control variable
ventilation (stage 2)
Output R-CT [5.1]
DPT_Scaling
1 Byte
133 CO2 controller: Ventilation 1 status
(1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
134 CO2 controller: Ventilation 2 status
(1=ON | 0=OFF)
Output R-CT [1.1]
DPT_Switch
1 Bit
135 Comparator 1 actuating variable:
Input 1
Input -WC- [5.1]
DPT_Scaling
1 Byte
136 Comparator 1 actuating variable:
Input 2
Input -WC- [5.1]
DPT_Scaling
1 Byte
137 Comparator 1 actuating variable:
Input 3
Input -WC- [5.1]
DPT_Scaling
1 Byte
138 Comparator 1 actuating variable:
Input 4
Input -WC- [5.1]
DPT_Scaling
1 Byte
139 Comparator 1 actuating variable:
Input 5
Input -WC- [5.1]
DPT_Scaling
1 Byte
140 Comparator 1 actuating variable:
Output
Output R-CT [5.1]
DPT_Scaling
1 Byte
No Name Function Flags Data Point Type Size
Page 21
19 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
141 Comparator 1 actuating variable:
Block
Input -WC- [1.2]
DPT_Bool
1 Bit
142 Comparator 2 actuating variable:
Input 1
Input -WC- [5.1]
DPT_Scaling
1 Byte
143 Comparator 2 actuating variable:
Input 2
Input -WC- [5.1]
DPT_Scaling
1 Byte
144 Comparator 2 actuating variable:
Input 3
Input -WC- [5.1]
DPT_Scaling
1 Byte
145 Comparator 2 actuating variable:
Input 4
Input -WC- [5.1]
DPT_Scaling
1 Byte
146 Comparator 2 actuating variable:
Input 5
Input -WC- [5.1]
DPT_Scaling
1 Byte
147 Comparator 2 actuating variable:
Output
Output R-CT [5.1]
DPT_Scaling
1 Byte
148 Comparator 2 actuating variable:
Block
Input -WC- [1.2]
DPT_Bool
1 Bit
149 AND logic 1: 1-bit switching output Output R-CT [1.1]
DPT_Switch
1 Bit
150 AND logic 1: 8-bit output A Output R-CT [5]
5.xxx
1 Byte
151 AND logic 1: 8-bit output B Output R-CT [5]
5.xxx
1 Byte
152 AND logic 1: Block Input -WC- [1.2]
DPT_Bool
1 Bit
153 AND logic 2: 1-bit switching output Output R-CT [1.1]
DPT_Switch
1 Bit
154 AND logic 2: 8-bit output A Output R-CT [5]
5.xxx
1 Byte
155 AND logic 2: 8-bit output B Output R-CT [5]
5.xxx
1 Byte
156 AND logic 2: Block Input -WC- [1.2]
DPT_Bool
1 Bit
157 AND logic 3: 1-bit switching output Output R-CT [1.1]
DPT_Switch
1 Bit
158 AND logic 3: 8-bit output A Output R-CT [5]
5.xxx
1 Byte
159 AND logic 3: 8-bit output B Output R-CT [5]
5.xxx
1 Byte
160 AND logic 3: Block Input -WC- [1.2]
DPT_Bool
1 Bit
161 AND logic 4: 1-bit switching output Output R-CT [1.1]
DPT_Switch
1 Bit
162 AND logic 4: 8-bit output A Output R-CT [5]
5.xxx
1 Byte
No Name Function Flags Data Point Type Size
Page 22
20 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
163 AND logic 4: 8-bit output B Output R-CT [5]
5.xxx
1 Byte
164 AND logic 4: Block Input -WC- [1.2]
DPT_Bool
1 Bit
181 OR logic 1: 1-bit switching output Output R-CT [1.1]
DPT_Switch
1 Bit
182 OR logic 1: 8-bit output A Output R-CT [5]
5.xxx
1 Byte
183 OR logic 1: 8-bit output B Output R-CT [5]
5.xxx
1 Byte
184 OR logic 1: Block Input -WC- [1.2]
DPT_Bool
1 Bit
185 OR logic 2: 1-bit switching output Output R-CT [1.1]
DPT_Switch
1 Bit
186 OR logic 2: 8-bit output A Output R-CT [5]
5.xxx
1 Byte
187 OR logic 2: 8-bit output B Output R-CT [5]
5.xxx
1 Byte
188 OR logic 2: Block Input -WC- [1.2]
DPT_Bool
1 Bit
189 OR logic 3: 1-bit switching output Output R-CT [1.1]
DPT_Switch
1 Bit
190 OR logic 3: 8-bit output A Output R-CT [5]
5.xxx
1 Byte
191 OR logic 3: 8-bit output B Output R-CT [5]
5.xxx
1 Byte
192 OR logic 3: Block Input -WC- [1.2]
DPT_Bool
1 Bit
193 OR logic 4: 1-bit switching output Output R-CT [1.1]
DPT_Switch
1 Bit
194 OR logic 4: 8-bit output A Output R-CT [5]
5.xxx
1 Byte
195 OR logic 4: 8-bit output B Output R-CT [5]
5.xxx
1 Byte
196 OR logic 4: switching output block Input -WC- [1.2]
DPT_Bool
1 Bit
200 Logic input 1 Input -WC- [1.2]
DPT_Bool
1 Bit
201 Logic input 2 Input -WC- [1.2]
DPT_Bool
1 Bit
202 Logic input 3 Input -WC- [1.2]
DPT_Bool
1 Bit
203 Logic input 4 Input -WC- [1.2]
DPT_Bool
1 Bit
No Name Function Flags Data Point Type Size
Page 23
21 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
204 Logic input 5 Input -WC- [1.2]
DPT_Bool
1 Bit
205 Logic input 6 Input -WC- [1.2]
DPT_Bool
1 Bit
206 Logic input 7 Input -WC- [1.2]
DPT_Bool
1 Bit
207 Logic input 8 Input -WC- [1.2]
DPT_Bool
1 Bit
208 Logic input 9 Input -WC- [1.2]
DPT_Bool
1 Bit
209 Logic input 10 Input -WC- [1.2]
DPT_Bool
1 Bit
210 Logic input 11 Input -WC- [1.2]
DPT_Bool
1 Bit
211 Logic input 12 Input -WC- [1.2]
DPT_Bool
1 Bit
212 Logic input 13 Input -WC- [1.2]
DPT_Bool
1 Bit
213 Logic input 14 Input -WC- [1.2]
DPT_Bool
1 Bit
214 Logic input 15 Input -WC- [1.2]
DPT_Bool
1 Bit
215 Logic input 16 Input -WC- [1.2]
DPT_Bool
1 Bit
220 Display contrast (1 = higher | 0 =
lower)
Input -WC- [1.1]
DPT_Switch
1 Bit
230 Date for display Input -WCT [11.1]
DPT_Date
3 Bytes
231 Time for display Input -WCT [10.1]
DPT_TimeOfDay
3 Bytes
232 8-bit object 1 for display Input -WC- [5]
5.xxx
1 Byte
233 8-bit object 2 for display Input -WC- [5]
5.xxx
1 Byte
234 8-bit object 3 for display Input -WC- [5]
5.xxx
1 Byte
235 16-bit object 1 for display Input -WC- [9]
9.xxx
2 Bytes
236 16-bit object 2 for display Input -WC- [9]
9.xxx
2 Bytes
237 Text message 1 for display Input -WC- [16.0]
DPT_String_ASCII
14 Bytes
238 Text message 2 for display Input -WC- [16.0]
DPT_String_ASCII
14 Bytes
No Name Function Flags Data Point Type Size
Page 24
22 Transfer protocol
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
239 Display_Return approval Input -WC- [1.1]
DPT_Switch
1 Bit
240 Pushbutton 1 long-term Output R-CT [1.8]
DPT_UpDown
1 Bit
241 Pushbutton 1 short-term Output R-CT [1.10]
DPT_Start
1 Bit
242 Pushbutton 1 switching Input/
Output
R-CT [1.1]
DPT_Switch
1 Bit
243 Pushbutton 1 Relative dimming Input/
Output
RWCT[3.7]
DPT_Control_Dim­ming
4 Bit
244 Pushbutton 1 encoder 8 bit Output R-CT [5]
5.xxx
1 Byte
245 Pushbutton 1 encoder 16 bit Output R-CT [9]
9.xxx
2 Bytes
246 Pushbutton 1 Scenario Output R-CT [5]
5.xxx
1 Byte
247 Pushbutton 2 long-term Output R-CT [1.8]
DPT_UpDown
1 Bit
248 Pushbutton 2 short-term Output R-CT [1.10]
DPT_Start
1 Bit
249 Pushbutton 2 switching Input/
Output
R-CT [1.1]
DPT_Switch
1 Bit
250 Pushbutton 2 Relative dimming Input/
Output
RWCT[3.7]
DPT_Control_Dim­ming
4 Bit
251 Pushbutton 2 encoder 8 bit Output R-CT [5]
5.xxx
1 Byte
252 Pushbutton 2 encoder 16 bit Output R-CT [9]
9.xxx
2 Bytes
253 Pushbutton 2 Scenario Output R-CT [5]
5.xxx
1 Byte
221 Display lighting (1 = on | 0 = off) Input -WC- [1.1]
DPT_Switch
1 Bit
222 Display lighting brightness Input RWCT[5.1]
DPT_Scaling
1 Byte
223 Display lighting switch-off delay Input RWCT[7.5]
DPT_TimePeriodSec
2 Bytes
No Name Function Flags Data Point Type Size
Page 25
23 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
5. Parameter setting
5.1. Behaviour on power failure/ restoration of
power
Behaviour following a failure of the bus power supply:
The device sends nothing.
Behaviour on bus restoration of power and following programming or reset:
The device sends all outputs according to their send behaviour set in the parameters with the delays established in the "General settings" parameter block.
5.2. General settings
Set the basic data transfer characteristics and select whether or not malfunction ob­jects should be sent.
5.3. Temperature value
Use Offsets to adjust the readings to be sent.
The unit can calculate a mixed value from its own reading and an external value. Set the mixed value calculation if desired. If an external value is used, all of the following settings are referred to the total value.
Send delay after power-up and programming for: Measured values 5 s • ... • 2 h Threshold values and switching outputs 5 s • ... • 2 h Controller objects 5 s • 10 s • ... • 2 h Logic outputs 5 s • 10 s • ... • 2 h Maximum telegram quota • 1 message per second
• ...
• 5 messages per second
• ...
• 20 messages per second Use temp./humidity malfunction object Yes • No Use CO2 malfunction object Yes • No
Offset in 0,1°C -50…50; 0
Use external reading Yes • No Ext. Reading proportion of the total reading 5% • 10% • ... • 50% • ... • 100% All of the following settings are referred to the total value.
Page 26
24 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
The minimum and maximum readings can be saved and sent to the bus. Use the „Reset temperature min/max. value“ objects to reset the values to the current rea­dings. The values are not retained after a reset.
5.4. Temperature threshold values
Activate the required temperature threshold values. The menus for setting the thresh­old values are displayed.
5.4.1. Threshold value 1, 2, 3
Threshold value
Set, in which cases threshold values received via object are to be retained. The pa­rameter is only taken into consideration if the setting via object is activated below. Please note that the setting "After power supply restoration and programming" should not be used for the initial start-up, as the factory settings are always used until the first communication (setting via objects is ignored).
Set the threshold value directly in the application program using parameters, or define them via the bus using a communication object.
Threshold value setting via parameter:
Set the threshold values and hysteresis directly.
Threshold value setting via a communication object:
Define, how the threshold value is to be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
During initial commissioning, a threshold value must be defined, which will be valid until the first communication with a new threshold value. For units which have already been taken into service, the last communicated threshold value can be used. Basically,
Send internal and total reading • never
• periodically
• on change
• on change and periodically From change of
(if sent on change)
0,1°C • 0,2°C • 0,5°C • ... • 5,0°C
Send cycle
(if sent periodically)
5 s • 10 s • ... • 2 h
Use minimum/maximum value Yes • No
Use threshold value 1/2/3 Yes • No
Threshold value setting via Parameter • Communication objects Threshold value in 0.1°C -300 … 800; 200
Page 27
25 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
a temperature range is given, in which the threshold value can be changed (object val­ue limit).
A set threshold value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Set the hysteresis independent of the type of threshold value specification.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under­cut. The output switching delay can be set using objects or directly as a parameter.
Threshold value setting via Parameter • Communication objects The value communicated last shall be
maintained
• never
• after power supply restoration
• after power supply restoration and
programming
Start threshold value in 0.1°C valid until first communication
-300 … 800; 200
Object value limit (min) in 0.1°C -300…800 Object value limit (max) in 0.1°C -300…800 Type of threshold value change Absolute value • Increase/decrease Increment
(upon increase/decrease change)
0,1 °C • ... • 5°C, 1°C
Hysteresis in % of the threshold value 0 … 50; 20
When the following conditions apply, the output is (TV = Threshold value)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1 Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(If delay can be set via objects: valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(If delay can be set via objects: valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically Cycle
(only if sending periodically is selected)
5 s • 10 s • 30 s… • 2 h
Page 28
26 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Block
The switching output can be blocked using an object.
If the block is activated, define specifications here for the behaviour of the output when blocked.
The behaviour of the switching output on release is dependent on the value of the pa­rameter "Switching output sends" (see "Switching output")
5.5. Temperature PI control
Activate the control if you want to use it.
General control
Set, in which cases setpoint values and extension time received via object are to be retained. The parameter is only taken into consideration if the setting via object is activated below. Please note that the setting "After power supply restoration and pro­gramming" should not be used for the initial start-up, as the factory settings are always used until the 1st communication (setting via objects is ignored). .
Use switching output block No • Yes
Analysis of the blocking object • At value 1: block | At value 0: release
• At value 0: block | At value 1: release Blocking object value before
1st communication
0 • 1
Behaviour of the switching output On block • Do not send message
• send 0
• send 1 On release
(with 2 seconds release delay)
[Dependent on the "Switching output sends" setting]
Switching output sends on change • Do not send message
• Send switching output status Switching output sends on change to 1 • Do not send message
• if switching output = 1 send 1 Switching output sends on change to 0 • Do not send message
• if switching output = 0 send 0 Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and periodically
if switching output = 1 send 1
Switching output sends on change to 0 and periodically
if switching output = 0 send 0
Use control No • Yes
Page 29
27 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
For an adequate regulation of the indoor temperature, comfort, standby, eco and building protection modes may be used.
Comfort when present, Standby during short absences, Eco as a night-time mode and Frost/heat protection (building protection) during longer absences.
The settings for the temperature control include the set point temperatures for the individual modes. Objects are used to determine which mode is to be selected. A change of mode may be triggered manually or automatically (e.g. by a timer, window contact).
The mode may be switched with two 8 bit objects of different priority. Objects „... HVAC mode (Prio 2)“ for switching in everyday operation and „... HVAC mode (Prio 1)“ for central switching with higher priority. The objects are coded as follows: 0 = Auto 1 = Comfort 2 = Standby 3 = Eco 4 = Building Protection
Alternatively, you can use three objects, with one object switching between eco and standby mode and the two others activating comfort mode and frost/heat protection mode respectively. The comfort object blocks the eco/standby object, and the frost/ heat protection object has the highest priority. Objects „... Mode (1: Eco, 0: Standby)“, „... comfort activation mode" and „... frost/heat protection activation mode"
Select the mode to be activated after reset (e.g. power failure, reset of the line via the bus) (Default). Then configure a temperature control block via the blocking object.
Switch mode via • two 8 Bit objects (HVAC Modes)
• three 1 bit objects
Mode after reset • Comfort
• Standby
• Eco
• Building protection Behaviour of the blocking object with value • 1 = Block | 0 = release
• 0 = block | 1 = release Blocking object value
before 1st communication
0 • 1
Page 30
28 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Specify when the current control variables of the controller are to be sent to the bus. Periodic sending is safer, in case a message does not reach a recipient. You may also set up periodical monitoring by the actuator with this setting.
The status object reports the current status of the control variables (0% = OFF, >0% = ON) and may for example be used for visualisation, or to switch off the heating pump as soon as the heating is switched off.
Then define the type of control. Heating and/or cooling may be controlled in two lev­els.
General set point values
You may enter separate set point values for each mode or use the comfort set point as a basic value. If you are using the controls for both heating and cooling, you may also select the setting "separately with switching object". Systems used for cooling in the summer and for heating in the winter can thus be switched from one to the other. If you are using the basic value, only the deviation from the comfort set point value is listed for the other modes (e. g., 2°C less for standby mode).
Send control variable • on change
• on change and periodically from change (in % absolute) 1...10; 2 Cycle
(if sent periodically)
5 s • ... • 5 min • … • 2 h
Send status objects • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically Cycle
(if sent periodically)
5 s • ... • 5 min • … • 2 h
Type of control • Single level heating
• Dual-level heating
• Single-level cooling
• Dual-level cooling
• Single-level heating + single-level cooling
• Dual-level heating + single-level cooling
• Dual-level heating + dual-level cooling
Preserve modified set points after mode change
No • Yes
Setting the nominal values • separate with switching object
• separate without switching object
• with comfort set point as a basis
Page 31
29 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
The grades for the set point changes is predefined. Modifications may only remain ac­tive temporarily (do not save) or remain saved even after voltage recovery (and pro­gramming). This also applies to a comfort extension.
The control may be manually reset to comfort mode from eco, or night mode. This allows the user to maintain the daily nominal value for a longer time, e.g. when having guests. The duration of this comfort extension period is set. After the comfort extension period is terminated, the system returns to eco mode.
Set point Comfort
Comfort mode is usually used for daytime mode when people are present. A starting value is defined for the comfort set point as well as a temperature range in which the nominal value may be modified.
If set point values are entered separately:
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is set.
Grading for set point changes (in 0.1 °C)
1… 50; 10
Saving set point value(s) not
• after voltage recovery
• after voltage recovery and programming
Comfort extension time in seconds (can only be activated from eco mode)
1…36000; 3600
Initial heating/cooling set point (in 0.1 °C) valid till 1st communication
not upon saving the set point value after programming
-300…800; 210
Min. object value heating/cooling (in 0.1 °C)
-300…800; 160
Max. object value heating/cooling (in 0.1 °C)
-300…800; 280
Starting heating/cooling setpoint (in 0.1 °C) valid until 1st communication
-300…800; 210
Minimum base setpoint (in 0.1°C) -300…800; 160 Maximum base setpoint (in 0.1°C) -300…800; 280 Reduction by up to (in 0.1°C) 0…100; 50 Increase by up to (in 0.1°C) 0…100; 50
Page 32
30 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
If the comfort setpoint is used as the basis without a switching object, a dead zone is specified for the control mode "heating and cooling" to avoid direct switching from heating to cooling.
Standby setpoint
Standby mode is usually used for daytime mode when people are absent.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint value may be changed.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is set.
Eco setpoint
Eco mode is usually used for night mode.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint value may be changed.
Dead zone between heating and cooling in 0,1°C
(only if both heating AND cooling are used)
1…100; 50
Starting heating setpoint (in 0.1 °C) valid until 1st communication
-300…800; 180
Starting heating setpoint (in 0.1 °C) valid until 1st communication
-300…800; 240
Min. object value heating/cooling (in 0.1 °C)
-300…800; 160
-300…800; 280 Max. object value heating/cooling (in 0.1 °C)
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 30
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 30
Starting heating setpoint (in 0.1 °C) valid until 1st communication
-300…800; 160
Starting cooling setpoint (in 0.1 °C) valid until 1st communication
-300…800; 280
Min. object value heating/cooling (in 0.1 °C)
-300…800; 160
-300…800; 280 Max. object value heating/cooling (in 0.1 °C)
Page 33
31 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is set.
Setpoint values for frost/heat protection (building protection)
The building protection mode is for example used as long as windows are opened for ventilation. Setpoints for frost protection (heating) and heat protection (cooling) are determined which may not be modified from outside (no access via operating devices etc.). The building protection mode may be activated with delay, which allows you to leave the building before the controls switch to frost/heat protection mode.
General control variables
This setting appears for the control types "Heating and Cooling" only. Here, you can decide whether to use a common control variable for heating and cooling. If the 2nd level has a common control variable, you also determine the control mode of the 2nd level here.
When using the control variable for a 4/6 way valve, the following applies: 0%...100% heating = 66%...100% control variable OFF = 50% control variable 0%...100% cooling = 33%...0% control variable
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 50
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 60
Setpoint frost protection (in 0.1°C) -300…800; 70 Activation delay less than • 5 s • ... • 5 min • … • 2 h Setpoint heat protection (in 0.1°C) -300…800; 350 Activation delay none • 5 s • ... • 5 min • … • 2 h
For heating and cooling • separate control variables are used
• common control variables are used for
Level 1
• common control variables are used for
Level 2
• common control variable are used for
Level 1+2
Use control variable for 4/6-way valve
(only for common control variables in level 1)
No • Yes
Control type
(for level 2 only)
• 2-point-control
• PI control Control variable of the 2nd Level is on
(only for level 2 with 2 point controlling)
• 1 bit object
• 8 bit object
Page 34
32 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
5.5.1. Heating control level 1/2
If a heating control mode is configured, one or two setting sections for the heating lev­els are displayed.
In the 1st level, heating is controlled by a PI control, which allows to either enter control parameters or select predetermined applications.
In the 2nd level (therefore only in case of 2-level heating), heating is controlled via a PI or a 2-point-control. In level 2, the setpoint difference between the two levels must also be specified, i.e. be­low which setpoint deviation the second level is added.
PI control with control parameters:
This setting allows individual input of the parameters for PI control.
Specify the deviation from the setpoint value at which the maximum control variable value is reached, i.e. the point at which maximum heating power is activated. The reset time shows how quickly the controller responds to deviations from the set­point value. In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less urgently and needs longer until the necessary control variable for the setpoint value deviation is reached. You should set the time appropriate to the heating system at this point (observe man­ufacturer's instructions).
Now specify what should be sent when the control is blocked. Set a value greater 0 (=OFF) to receive a basic heating level, e.g. for floor heating. On release, the control variable follows the rule again.
Setpoint difference between 1st and 2nd level (in 0.1°C)
(for level 2)
0...100; 40
Control type
(for level 2, no common control variables)
• 2-point-control
• PI control Control variable is a
(for level 2 with 2-point controlling, no common control variables)
• 1 bit object
• 8 bit object
Control type PI control Setting of the controller by Controller parameter
• specified applications
Maximum control variable is reached at setpoint/actual difference of (in °C)
1...5
Reset time (in min.) 1...255; 30
When blocked, the control variable shall • not be sent
• send a specific value Value (in %)
(if a value is sent)
0...100
Page 35
33 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
In case of a common control variable for heating and cooling, 0 is always transmitted as a fixed value.
PI control with predetermined application:
This setting provides fixed parameters for frequent applications.
Now specify what should be sent when the control is blocked. Set a value greater 0 (=OFF) to receive a basic heating level, e.g. for floor heating. On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted as a fixed value.
2-point-control (only level 2):
2-point-control is used for systems which are only set to ON or OFF.
Enter the hysteresis that prevents frequent on/off switching of temperatures in the threshold range.
If separate control variables are used, select whether the control variable of the 2nd level is a 1 bit object (on/off) or an 8 bit object (on with percentage/off).
Control type PI control Setting of the controller by • Controller parameter
specified applications Application • Warm water heating
• Floor heating
• Convection unit
• Electric heating Maximum control variable is reached
at setpoint/actual difference of (in °C)
Warm water heating: 5 Floor heating: 5 Convection unit: 4 Electric heating: 4
Reset time (in min.) Warm water heating: 150
Floor heating: 240 Convection unit: 90 Electric heating: 100
When blocked, the control variable shall • not be sent
• send a specific value Value (in %)
(if a value is sent)
0...100
Control type
(is determined at a higher level for com­mon control variables)
2-point-control
Hysteresis (in 0.1°C) 0...100; 20
Control variable is a • 1 bit object
• 8 bit object Value (in %)
(for 8 bit object)
0...100
Page 36
34 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Now specify what should be sent when the control is blocked. Set a value greater 0 (=OFF) to receive a basic heating level, e.g. for floor heating. On release, the control variable follows the rule again.
5.5.2. Cooling control level 1/2
If a cooling control mode is configured, one or two setting sections for the cooling lev­els are displayed.
In the 1st level, cooling is controlled by a PI control in which either control parameters can be entered or predetermined applications can be selected.
In the 2nd level (therefore only for 2-level cooling), cooling is controlled via a PI or a 2­point-control. In level 2, the setpoint deviation between the two levels must also be specified, i.e. above which setpoint value deviation the second level is added.
PI control with control parameters:
This setting allows individual input of the parameters for PI control.
Specify the deviation from the setpoint value which reaches maximum variable value, i.e. the point at which maximum cooling power is activated. The reset time shows how quickly the controller responds to deviations from the set­point value. In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less urgently and needs longer until the necessary control variable for the setpoint value deviation is reached. You should set the time appropriate to the cooling system at this point (observe manufacturer's instructions).
When blocked, the control variable shall • not be sent
• send a specific value Value (in %)
only if a value is sent
0...100
Setpoint difference between 1st and 2nd level (in 0.1°C)
(for level 2)
0...100; 40
Control type
(for level 2, no common control variables)
• 2-point-control
• PI control Control variable is a
(for level 2 with 2-point controlling, no common control variables)
• 1 bit object
• 8 bit object
Control type PI control Setting of the controller by Controller parameter
• specified applications
Maximum control variable is reached at setpoint/actual difference of (in °C)
1...5
Reset time (in min.) 1...255; 30
Page 37
35 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Now specify what should be sent when the control is blocked. On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted as a fixed value.
PI control with predetermined application:
This setting provides fixed parameters for a cooling ceiling
Now specify what should be sent when the control is blocked. On release, the control variable follows the rule again.
2-point-control (only level 2):
2-point-control is used for systems which are only set to ON or OFF.
Enter the hysteresis that prevents frequent on/off switching of temperatures in the threshold range.
If separate control variables are used, select whether the control variable of the 2nd level is a 1 bit object (on/off) or an 8 bit object (on with percentage/off).
When blocked, the control variable shall • not be sent
• send a specific value Value (in %)
(if a value is sent)
0...100
Control type PI control Setting of the controller by • Controller parameter
specified applications Application • Cooling ceiling Maximum control variable is reached
at setpoint/actual difference of (in °C)
Cooling ceiling: 5
Reset time (in min.) Cooling ceiling: 30
When blocked, the control variable shall • not be sent
• send a specific value Value (in %)
(if a value is sent)
0...100
Control type
is determined at a higher level for common variables
2-point-control
Hysteresis (in 0.1°C) 0...100; 20
Control variable is a • 1 bit object
• 8 bit object Value (in %)
(for 8 bit object)
0...100
Page 38
36 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Now specify what should be sent when the control is blocked. On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted as a fixed value.
5.6. Humidity measurement
Select (see 5.2.General settings), whether a malfunction object is to be sent if the sensor is faulty.
Use Offsets to adjust the readings to be sent.
The unit can calculate a mixed value from its own reading and an external value. Set the mixed value calculation if desired. If an external portion is used, all of the following settings (threshold values, etc.) are related to the overall reading.
The minimum and maximum readings can be saved and sent to the bus. Use the „Reset humidity min/max value“ object to reset the values to the current readings. The values are not retained after a reset.
5.7. Humidity threshold values
Activate the required air humidity threshold values. The menus for setting the thresh­old values are displayed.
When blocked, the control variable shall • not be sent
• send a specific value Value (in %)
(if a value is sent)
0...100
Use malfunction object No • Yes
Offset in 0,1°C -10…10; 0
Use external measured value No • Yes Ext. Reading proportion of the total reading 5% • 10% • ... • 50% • ... • 100% All of the following settings are referred to the total value. Send internal and total reading • never
• periodically
• on change
• on change and periodically At and above change of
(if sent on change)
0.1% RH • 0.2% RH • 0.5% RH • 1.0% RH • ...
• 25% RH Send cycle
(if sent periodically)
5 s • 10 s • ... • 2 h
Use minimum and maximum value No • Yes
Use threshold value 1/2 Yes • No
Page 39
37 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
5.7.1. Threshold value 1, 2
Threshold value
Set, in which cases threshold values and delay times received via objects are to be retained. The parameter is only taken into consideration if the setting via object is ac­tivated below. Please note that the setting "After power supply restoration and pro­gramming" should not be used for the initial start-up, as the factory settings are always used until the first communication (setting via objects is ignored). Set the threshold value directly in the application program using parameters, or define them via the bus using a communication object.
Threshold value setting using parameter:
Set the threshold values and hysteresis directly.
Threshold value setting using a communication object:
Define, how the threshold value is to be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
During initial commissioning, a threshold value must be defined, which will be valid until the first communication with a new threshold value. For units which have already been taken into service, the last communicated threshold value can be used. Basically, a humidity range is specified in which the threshold value can be changed (object value limit).
A set threshold value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Threshold value setting using Parameter • Communication objects Threshold value in 0.1% RH
(valid until 1st communication)
0 … 100; 70
Threshold value setting using Parameter • Communication objects The value communicated last shall be
maintained
• never
• after power supply restoration
• after power supply restoration and
programming
Starting threshold value in 0.1% RH valid until first communication
0 … 100; 70
Object value limit (min.) in 0.1%RH 0…100 Object value limit (max.) in 0.1%RH 0…100 Type of threshold value change Absolute value • Increase/Decrease Increment
(upon increase/decrease change)
1,00% • 2,00% • 5,00% • 10,00%
Page 40
38 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Set the hysteresis independent of the type of threshold value specification.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under­cut. The output switching delay can be set using objects or directly as a parameter.
Block
The switching output can be blocked using an object.
If the block is activated, define specifications here for the behaviour of the output when blocked.
Hysteresis of the threshold value in % (relative to the threshold value)
0 … 50; 20
When the following conditions apply, the output is (TV = Threshold value)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1 Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(If delay can be set via objects: valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(If delay can be set via objects: valid until 1st communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically Cycle
(is only sent if periodically is selected)
5 s • 10 s • 30 s… • 2 h
Use switching output block No • Yes
Analysis of the blocking object • At value 1: block | At value 0: release
• At value 0: block | At value 1: release Blocking object value before first communi-
cation
0 • 1
Behaviour of the switching output On block • Do not send message
• send 0
• send 1 On release
(with 2 seconds release delay)
[Dependent on the "Switching output sends" setting]
Page 41
39 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
The behaviour of the switching output on release is dependent on the value of the pa­rameter "Switching output sends" (see "Switching output")
5.8. Humidity PI control
If you activate humidity control, you can use the following settings to define control type, setpoint values, and humidification and dehumidification.
General control
Sensor KNX AQS/TH-UP Touch can be used to control one- or two-level dehumidi-
fication or combined humidification/dehumidification.
Configure a block for the humidity control using the blocking object.
Specify when the current control variables are to be sent to the bus. Periodic sending is safer, in case a message does not reach a recipient. You may also set up periodic monitoring using an actuator with this setting.
Switching output sends on change • Do not send message
• Send switching output status Switching output sends on change to 1 • Do not send message
• if switching output = 1 send 1 Switching output sends on change to 0 • Do not send message
• if switching output = 0 send 0 Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and periodically
if switching output = 1 send 1
Switching output sends on change to 0 and periodically
if switching output = 0 send 0
Use humidity control No • Yes
Type of control • One-level dehumidification
• Two-level dehumidification
• Humidification and dehumidification
Behaviour of the blocking object with value • 1 = block control | 0 = release control
• 0 = block control | 1 = release control Blocking object value
before first communication
0 • 1
Send control variable • on change
• on change and periodically from change (in % absolute) 1 ... 20, 2 Send cycle
(is only sent if "periodically" is selected)
5 s • ... • 5 min • … • 2 h
Page 42
40 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
The status object shows the current status of the output variable (0 = OFF, >0 = ON) and can for example be used for visualisation.
Controller setpoint
Set, in which cases setpoint values received via object are to be retained. Please note that the setting "After power supply restoration and programming" should not be used for the initial start-up, as the factory settings are always used until the first communi­cation (setting via objects is ignored).
During initial commissioning, a setpoint value must be defined which is valid until the first communication of a new setpoint value. For units which have already been tak­en into service, the last communicated setpoint value can be used. Basically, an air hu­midity range is specified in which the setpoint value can be changed (object value limit).
Enter, how the setpoint value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
A set setpoint value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Setpoint value setting using parameter:
Set the threshold values and hysteresis directly.
Setpoint value setting using communication object:
Send status object(s) • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically Send cycle
(is only sent if "periodically" is selected)
5 s • ... • 5 min • … • 2 h
Setpoint value setting using Parameter • Communication objects Setpoint value in 0.1% RH
(valid until 1st communication)
0 … 100; 70
Setpoint value setting using Parameter • Communication objects The value communicated last shall be
maintained
• never
• after power supply restoration
• after power supply restoration and
programming
Start setpoint in % valid until first communication
(not upon saving the setpoint value after programming)
0 … 100; 50 0…100; 40
Object value limit (min.) in % 0…100; 60
Page 43
41 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
In "Humidification and dehumidification" control mode, a dead zone is specified so that a direct changeover switching between humidification and dehumidification can be avoided.
Humidification starts, when the relative air humidity is lower or equal to the setpoint value - dead zone value.
Dehumidification and/or humidification
Depending on the control mode, settings sections for humidification and dehumidifi­cation appear (level 1/2).
For dual-level dehumidification, the setpoint value difference between the two levels must be defined, i.e. the setpoint value which, when exceeded, triggers the switch to the 2nd level.
Determine the deviation from the setpoint value at which the maximum variable value is reached, i.e. the point at which maximum output is used. The reset time shows how quickly the controller responds to deviations from the set­point value. In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less urgently and needs longer until the necessary control variable for the setpoint value deviation is reached. You should set the time appropriate for the humidification/dehumidification system at this point (note manufacturer instructions).
Now specify, what should be sent when the control is blocked. On release, the control variable follows the rule again.
Object value limit (max.) in % Absolutwert • Anhebung / Absenkung
1,00% • 2,00% • 5,00% • 10,00%
Dead zone between humidification and dehumidification in %
(only if both humidification and dehumidifi­cation are used)
0…50; 15
Target value difference between level 1 and 2 in %
(for level 2 only)
0...50; 15
Maximum control variable is reached at target/actual difference of %
1...50; 5
Reset time in minutes 1...255; 3
When blocked, the control variable shall • not be sent
• send a specific value Value in %
(if a value is sent)
0...100
Page 44
42 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
5.9. Dewpoint measurement
The Sensor KNX AQS/TH-UP Touch calculates the dewpoint temperature and can output the value to the bus.
Activate the monitoring of the coolant temperature if required. The menus for setting the monitoring are displayed.
5.9.1. Cooling medium temp. monitoring
A threshold value can be set for the temperature of the coolant, which is based on the current dewpoint temperature (offset/deviation). The switching output of the coolant temperature monitoring system can provide a warning prior to any build-up of conden­sation in the system, and/or activate appropriate countermeasures.
Threshold value
Threshold value = dewpoint temperature + offset
Set, in which cases offset received via object is to be retained. Please note that the set­ting "After power supply restoration and programming" should not be used for the in­itial start-up, as the factory settings are always used until the first communication (set­ting via objects is ignored).
During initial commissioning, an offset must be defined which is valid until the first communication of a new offset. For units which have already been taken into service, the last communicated offset can be used.
Use dewpoint temperature No • Yes Sending pattern • never
• periodically
• on change
• on change and periodically At and above change of
(if sent on change)
0,1°C • 0,2°C • 0,5°C • 1,0°C • 2,0°C • 5,0°C
Send cycle
(if sent periodically)
5 s • 10 s • 30 s • 1 min • … • 2 h
Use monitoring of the coolant temperature No • Yes
The offset communicated last shall be maintained
• never
• after power supply restoration
• after power supply restoration and
programming
Page 45
43 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
A set offset will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Switching output
The output switching delay can be set using objects or directly as a parameter.
Blocking
The switching output can be blocked using an object. Define specifications here for the behaviour of the output when blocked.
Start offset in °C valid until first communication
0...20; 3
Increment for offset change via communi­cation object
0,1°C • 0,2°C • 0,3°C • 0,4°C • 0,5°C • 1°C • 2°C • 3°C • 4°C • 5°C
Hysteresis of the threshold value in %
(for setting in %)
0 ... 50; 20
Threshold value sends • never
• periodically
• on change
• on change and periodically At and above change of
(if sent on change)
0.1°C • 0.2°C • 0.5°C • 1.0°C • 2.0°C • 5.0°C
Send cycle
(if sent periodically)
5 s • 10 s • 30 s • 1 min • … • 2 h
When the following conditions apply, the output is (TV = Threshold value)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1 Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
for setting via objects: valid until 1st communication
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
for setting via objects: valid until 1st communication
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching output sends • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically Send cycle
(is only sent if periodically is selected)
5 s • 10 s • 30 s… • 2 h
Page 46
44 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
The behaviour of the switching output on release is dependent on the value of the pa­rameter "Switching output sends" (see "Switching output")
5.10. Absolute humidity
The absolute air humidity value is detected by the KNX AQS/TH-UP Touch and can be output to the bus.
Use switching output block No • Yes Analysis of the blocking object • At value 1: block | At value 0: release
• At value 0: block | At value 1: release Blocking object value before first communi-
cation
0 • 1
Behaviour of the switching output On block • Do not send message
• send 0
• send 1 On release
(with 2 seconds release delay)
[Dependent on the "Switching output sends" setting]
Switching output sends on change • Do not send message
• Send switching output status Switching output sends on change to 1 • Do not send message
• if switching output = 1 send 1 Switching output sends on change to 0 • Do not send message
• if switching output = 0 send 0 Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and periodically
if switching output = 1 send 1
Switching output sends on change to 0 and periodically
if switching output = 0 send 0
Use absolute humidity No • Yes
Sending pattern • never
• periodically
• on change
• on change and periodically At and above change of
(if sent on change)
0,1 g • 0,2 g • 0,5 g • 1,0 g • 2,0 g • 5,0 g
Send cycle
(if sent periodically)
5 s • 10 s • 30 s… • 2 h
Page 47
45 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
5.11. Comfort field
The Sensor KNX AQS/TH-UP Touch can send a message to the bus if the limits of the comfort field are exceeded. In this way, it is for example possible to monitor com­pliance with DIN 1946 (standard values) or even to define your own comfort field.
Define the comfort field by specifying the minimum and maximum values for temper­ature and humidity. The specified standard values comply with DIN 1946
Temperature hysteresis: 1°C Relative humidity hysteresis: 2% RH Absolute humidity hysteresis: 2 g/kg
5.12. CO
2
parameter settings
Select (see General settings, Seite 23), whether a malfunction object is to be sent if the sensor is faulty.
Use Offsets to adjust the readings to be sent.
The unit can calculate a mixed value from its own reading and an external value. Set the mixed value calculation if desired. If an external portion is used, all of the following settings (threshold values, etc.) are related to the overall reading.
Use comfort field No • Yes Sending pattern • never
• periodically
• on change
• on change and periodically Send cycle (if sent periodically) 5 s • 10 s • 30 s… • 2 h
Maximum temperature in °C (Standard 26°C)
25 ... 40; 26
Minimum temperature in °C (Standard 20°C)
10 ... 21; 20
Maximum relative humidity in % (Standard 65%)
52 ... 90; 65
Minimum relative humidity in % (Standard 30%)
10 ... 43; 30
Maximum absolute humidity in 0.1 g/kg (Standard 115 g/kg)
50 ... 200; 115
Use malfunction object No • Yes
Offset in ppm -100…100; 0
Use external measured value No • Yes Ext. Reading proportion of the total reading 5% • 10% • ... • 50% • ... • 100% All of the following settings are referred to the total value.
Page 48
46 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
The maximum reading can be saved and sent to the bus. Using the "Reset CO2 max- imum value" objects, the value can be reset to the current reading. The value is not re­tained after a reset.
5.13. CO2 threshold values
Activate the required CO2 threshold value. The menus for setting the threshold values are displayed.
300 ppm ... 1000 ppm: fresh air 1000 ppm ... 2000 ppm: used air
1000 ppm = 0.1 %
5.13.1. Threshold value 1, 2, 3, 4
Threshold value
Set, in which cases threshold values and delay times received via object are to be retained. The parameter is only taken into consideration if the setting via object is ac­tivated below. Please note that the setting "After power supply restoration and pro­gramming" should not be used for the initial start-up, as the factory settings are always used until the first communication (setting via objects is ignored).
Set the threshold value directly in the application program using parameters, or define them via the bus using a communication object.
Threshold value setting using parameters:
Set the threshold values and hysteresis directly.
Threshold value setting using a communication object:
Define, how the threshold value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
Sending pattern for internal and total measured value
• never
• periodically
• on change
• on change and periodically At and above change of
(relative to the last measured value)
(if sent on change)
2% • 5% • ... • 50%
Send cycle (if sent periodically) 5 s • 10 s • ... • 2 h
Use maximum value No • Yes
Use threshold value 1/2/3/4 Yes • No
Threshold value setting using Parameter • Communication objects Threshold value in ppm 0 … 5000; 1200
Page 49
47 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
During initial commissioning, a threshold value must be defined, which will be valid until the first communication of a new threshold value. For units which have already been taken into service, the last communicated threshold value can be used. Basically, a range is specified in which the threshold value can be changed (object value limit).
A set threshold value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Set the hysteresis independent of the type of threshold value specification.
Switching output
Set the behaviour of the switching output when a threshold value is exceeded/under­cut. The output switching delay can be set using objects or directly as a parameter.
Threshold value setting using Parameter • Communication objects The value communicated last shall be
maintained
• never
• after power supply restoration
• after power supply restoration and
programming
Start threshold value in 0.1°C valid until first communication
0 … 5000; 1200
Limitation of object value (min) in ppm 0…5000 Limitation of object value (max) in ppm 0…5000; 2000 Type of threshold value change Absolute value • Increase/Decrease Increment in ppm
(upon increase/decrease change)
1 • 2 • 5 • 10 • 20 • ... • 200
Hysteresis in % of the threshold value 0 … 50; 20
When the following conditions apply, the output is (TV = Threshold value)
• TV above = 1 | TV - hyst. below = 0
• TV above = 0 | TV - hyst. below = 1
• TV below = 1 |TV + hyst. above = 0
• TV below = 0 |TV + hyst. above = 1 Delays can be set via objects
(in seconds)
No • Yes
Switching delay from 0 to 1
(If delay can be set via objects: valid until first communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Switching delay from 1 to 0
(If delay can be set via objects: valid until first communication)
None • 1 s • 2 s • 5 s • 10 s • … • 2 h
Page 50
48 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Block
The switching output can be blocked using an object.
If the block is activated, define specifications here for the behaviour of the output when blocked.
The behaviour of the switching output on release is dependent on the value of the pa­rameter "Switching output sends" (see "Switching output")
Switching output sends • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically Cycle
(is only sent if periodically is selected)
5 s • 10 s • 30 s… • 2 h
Use switching output block No • Yes
Analysis of the blocking object • At value 1: block | At value 0: release
• At value 0: block | At value 1: release Blocking object value before first communi-
cation
0 • 1
Behaviour of the switching output On block • Do not send message
• send 0
• send 1 On release
(with 2 seconds release delay)
[Dependent on the "Switching output sends" setting]
Switching output sends on change • Do not send message
• Send switching output status Switching output sends on change to 1 • Do not send message
• if switching output = 1 send 1 Switching output sends on change to 0 • Do not send message
• if switching output = 0 send 0 Switching output sends on change and
periodically
Send switching output status
Switching output sends on change to 1 and periodically
if switching output = 1 send 1
Switching output sends on change to 0 and periodically
if switching output = 0 send 0
Page 51
49 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
5.14. CO2 PI-control
If you activate air quality control, you can use the following settings to define control type, setpoint values, and ventilation.
General control
The Sensor KNX AQS/TH-UP Touch can be used to control one or two-stage venti­lation.
Configure a block for the ventilation control using the blocking object.
Specify when the current control variables are to be sent to the bus. Periodic sending is safer, in case a message does not reach a recipient. You may also set up periodic monitoring using an actuator with this setting.
The status object shows the current status of the output variable (0 = OFF, >0 = ON) and can for example be used for visualisation.
Controller setpoint
The setpoint values can be set directly in the application program using parameters, or be defined via the bus using a communication object.
Use control Yes • No
Type of control • One-stage ventilation
• Two-stage ventilation
Behaviour of the blocking object with value • 1 = block control | 0 = release control
• 0 = block control | 1 = release control Blocking object value
before first communication
0 • 1
Send control variable • on change
• on change and periodically at and above change of (in ppm) 1...20; 2 Cycle
(if sent periodically)
5 s • ... • 5 min • … • 2 h
Send status object(s) • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically Cycle
(if sent periodically)
5 s • 10 s • … • 2 h
Page 52
50 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Setpoint value setting using parameters:
Set the setpoint value directly.
Setpoint value setting via communication object:
Enter, how the setpoint value will be received from the bus. Basically, a new value can be received, or simply a command to increase or decrease.
During initial commissioning, a setpoint value must be defined which is valid until the first communication of a new setpoint value. For units which have already been taken into service, the last communicated setpoint value can be used. Basically, an air humid­ity range is given in which the setpoint value can be changed (object value limit).
A set setpoint value will be retained until a new value or a change is transferred. The current value is saved, so that it is retained in the event of a power supply failure and will be available once the power supply is restored.
Ventilation control
Depending on the control mode, one and/or two setting sections for the ventilation stages are displayed.
For two-stage ventilation, the setpoint value difference between the two stages must be defined, i.e. the setpoint value which, when exceeded, triggers the switch to the 2nd level.
Specified setpoint using Parameter • Communication objects Target value in ppm 300…5000; 800
Threshold value setting using Parameter • Communication objects The last communicated value should be
retained
• never
• after power supply restoration
• after power supply restoration and
programming
Start setpoint value in ppm valid until first communication
(not upon saving the setpoint value after programming)
300… 5000; 800
Object value limit (min) in 0.1°C 300…5000; 400 Object value limit (max) in 0.1°C 300…5000; 1500 Type of threshold value change Absolute value • Increase/decrease Increment in ppm
(upon increase/decrease change)
1 • 2 • 5 • ... • 20 • ... • 100 • 200
Target value difference between 1st and 2nd level in ppm
(for level 2 only)
100...2000; 400
Page 53
51 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Determine the deviation from the setpoint value at which the maximum variable value is reached, i.e. the point at which maximum output is used. The reset time shows how quickly the controller responds to deviations from the set­point value. In case of a short reset time, the control responds with a fast increase of the control variable. In case of a long reset time, the control responds somewhat less urgently and needs longer until the necessary control variable for the setpoint value deviation is reached. You should set the time appropriate to the ventilation system at this point (follow the manufacturer's instructions).
Now specify what should be sent when the control is blocked. On release, the control variable follows the rule again.
5.15. Variable comparator
The two integrated control variable comparators can output maximum, minimum and median values.
5.15.1. Control variable comparator 1/2
Determine what the control variable comparator should output, and activate the input objects to be used. Send behaviour and blocks can also be set.
Maximum control variable is reached at setpoint value/actual difference of (in ppm)
100...2000
Reset time in minutes 1st level Reset time in minutes 2nd level
1...255; 30
1...255; 10
When blocked, the control variable shall • not send anything
• send a value Value in %
(if a value is sent)
0...100
Use comparator 1/2 No • Yes
Output delivered • Maximum value
• Minimum value
• Average value Use input 1/2/3/4/5 No • Yes Output sends • on change of output
• on change of output and periodically
• when receiving an input object
• when receiving an input object and peri-
odically
From change of
(is only sent if "on change" is selected)
1% • 2% • 5% • 10% • 20% • 25%
Send cycle
(is only sent if "periodically" is selected)
5 s • 10 s • 30 s • ... • 5 min • … • 2 h
Page 54
52 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
5.16. Logic
The device has 16 logic inputs, four AND- and four OR-logic gates.
Activate the logic inputs and assign object values up to 1st communication. Then, ac­tivate the required logic outputs.
Activate the required logic outputs.
AND logic
OR logic
5.16.1. AND logic 1-4 and OR logic outputs 1-4
The same setting options are available for AND and OR logic.
Each logic output may transmit one 1 bit or two 8 bit objects. Determine what the out put should send if logic = 1 and = 0.
Analysis of the blocking object • at value 1: block | at value 0: release
• at value 0: block | at value 1: release Blocking object value
before 1st communication
0 • 1
Behaviour of the switching output With blocking • do not send message
• Send value Sent value in % 0 ... 100
Use logic inputs Yes • No Object value before 1st communication for
- Logic input 1 0 • 1
- Logic input ... 0 • 1
- Logic input 16 0 • 1
AND logic 1 not active • active AND logic ... not active • active AND logic 4 not active • active
OR logic 1 not active • active OR logic ... not active • active OR logic 4 not active • active
Page 55
53 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
If the output type is a 1-bit object, set the output values for the various conditions.
If the output type is two 8-bit objects, set the type of object and the output values for the various conditions.
Set the output send pattern.
1. / 2. / 3. / 4. Input • do not use
- Logic inputs 1...16
- Logic inputs 1...16 inverted
• all switching events that the device
provides (see Connection inputs of the AND/OR logic)
Output type • a 1-Bit-object
• two 8-bit objects
Output value if logic = 1
1 • 0
Output value if logic = 0
1 • 0
Object type • Value (0…255)
• Percent (0…100%)
• Angle (0…360°)
• Scene call-up (0…127) Output value object A
if logic = 1
0 … 255 / 100% / 360° / 127; 1
Output value object B if logic = 1
0 … 255 / 100% / 360° / 127; 1
Output value object A if logic = 0
0 … 255 / 100% / 360° / 127; 0
Output value object B if logic = 0
0 … 255 / 100% / 360° / 127; 0
Send pattern • on change of logic
• on change of logic to 1
• on change of logic to 0
• on change of logic and periodically
• on change of logic to 1 and periodically
• on change of logic to 0 and periodically
• on change of logic+object receipt
• on change of logic+object receipt
and periodically
Send cycle
(if sent periodically)
5 s • 10 s • ... • 2 h
Page 56
54 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Block
If necessary, activate the block for the logic output and set what a 1 or 0 at the block input means and what happens in the event of a block.
5.16.2.Connection inputs of the AND logic
do not use Logic input 1 Logic input 1 inverted Logic input 2 Logic input 2 inverted Logic input 3 Logic input 3 inverted Logic input 4 Logic input 4 inverted Logic input 5 Logic input 5 inverted Logic input 6 Logic input 6 inverted Logic input 7 Logic input 7 inverted Logic input 8 Logic input 8 inverted Logic input 9 Logic input 9 inverted Logic input 10 Logic input 10 inverted Logic input 11 Logic input 11 inverted Logic input 12 Logic input 12 inverted Logic input 13 Logic input 13 inverted Logic input 14 Logic input 14 inverted Logic input 15 Logic input 15 inverted
Analysis of the blocking object • At value 1: block | At value 0: release
• At value 0: block | At value 1: release Blocking object value before first call 0 • 1 Behaviour of switching output On block • Do not send message
• Transmit block value [see above,
Output value if blocking active]
On release (with 2 seconds release delay)
[send value for current logic status]
Page 57
55 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Logic input 16 Logic input 16 inverted Temperature/Humidity sensor malfunction = ON Temperature/Humidity sensor malfunction = OFF CO2 sensor malfunction ON CO2 sensor malfunction OFF Switching output temperature 1 Switching output temperature 1 inverted Switching output temperature 2 Switching output temperature 2 inverted Switching output temperature 3 Switching output temperature 3 inverted Comfort temperature controller active Comfort temperature controller inactive Eco temperature controller active Eco temperature controller inactive Standby temperature controller active Standby temperature controller inactive Temperatur controller frost/heat active Temperatur controller frost/heat inactive Temp. control status heating 1 Temp. control status heating 1 inverted Temp. control status heating 2 Temp. control status heating 2 inverted Temp. control status cooling 1 Temp. control status cooling 1 inverted Temp. control status cooling 2 Temp. control status cooling 2 inverted Switching output humidity 1 Switching output humidity 1 inverted Switching output humidity 2 Switching output humidity 2 inverted Humidity control status dehumidification 1 Humidity control status dehumidification 1 inv. Humidity control status dehumidification 2 Humidity control status dehumidification 2 inv. Humidity control status humidification Humidity control status humidification inverted Switching output coolant temperature Switching output coolant temperature inverted Switching output cooling medium temperature Switching output cooling medium temperature inv. Switching output room climate status Switching output room climate status inverted Switching output CO2 1 Switching output CO2 1 inverted Switching output CO2 2 Switching output CO2 2 inverted
Page 58
56 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Switching output CO2 3 Switching output CO2 3 inverted Switching output CO2 4 Switching output CO2 4 inverted CO2 controller status ventilation 1 CO2 controller status ventilation 1 inverted CO2 controller status ventilation 2 CO2 controller status ventilation 2 inverted
5.16.3. Connection inputs of the OR logic
The OR logic connection inputs correspond to those of the AND logic. In addition the following inputs are available for the OR logic:
AND logic 1 AND logic output 1 inverted AND logic output 2 AND logic output 2 inverted AND logic output 3 AND logic output 3 inverted AND logic output 4 AND logic output 4 inverted
5.17. Display
Adjust the display settings here.
Set contrast and number of lines, as well as the type of temperature target value display.
Use display lighting No • Yes Brightness in % up to 1. Communication 0 ... 255; 100 Lighting always on • only when operating Switch off delay after operation until 1st
communication (in seconds)
1 ... 600; 10
Saving brightness and switch off delay • never
• after power restoration
• after power restoration and
programming
Use object "display contrast" No • Yes Display mode • two lines
(with optional thermostat display)
• three lines
(with optional thermostat display)
• Permanent thermostat Temperature controller display when using
pushbutton
No • Yes
only possible if the pushbuttons are also set to "For temperature control")
Page 59
57 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Choose if you would like to use the return release.
Choose if input objects should be used.
Set what should appear on the display.
The following table contains a list of other selection options.
Type of temperature target value display
(only for active thermostat display)
• Current target value
• Basic setpoint
• Basic setpoint as bar chart
• Basic setpoint as bar chart with count
• Basic setpoint as bar chart with range
Basic setpoint as bar chart with range and count
Display duration in seconds for Temperature controller display
2...240; 5
Use object "Return approval" No • Yes Object evaluation • 1= Allow return | 0=Return not allowed
• 1= Allow return | 0=Return not allowed Object value prior to initial communication 0 • 1
Use input objects No • Yes
Content line 1 (small font size) • display nothing
• internal temperature
• other selection options
Content line 2 (large font size) • display nothing
• CO2 internal reading
• other selection options
Content line 3 (small font size) • display nothing
• relative humidity internal
• other selection options
Page 60
58 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
List with other selection options:
5.18. Pushbutton
Adjust the pushbutton settings here.
External temperature Total temperature Current thermostat target value Dew point temperature relative humidity external relative humidity total absolute humidity g/kg
absolute humidity g/m
3
CO2 external reading CO2 total reading Date (Not for line 2!)
Time 8-bit object value 1
8-bit object value 2 8-bit object value 3
• without [0 ... 255]
• percentage [0% ... 100%]
• degree [0° ... 360°] 16-bit object value 1
16-bit object value 2 (Not for line 2!)
• without
• °C (degree Celsius)
• lux
• m/s (metres per second)
• Pa (Pascal)
• bar
• mbar (millibar)
• % R.H. (% relative humidity)
• ppm (parts per million)
• s (second)
• ms (millisecond)
• v (volt)
• mV (millivolt)
• A (ampere)
• mA (milliampere)
• W (watt)
• mW (milliwatt)
• W/m
2
(watt per square meter)
• W/h (watt per hour)
• ltr (litre)
• ltr/h (litre per hour)
• m (meter)
• mm (millimetre) Text message 1
Text message 2 (Not for line 2!)
Display duration of the message:
• until new notification available
• max. 1 minute
• ...
• max. 60 minutes
Page 61
59 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
5.18.1. Pushbutton for temperature control
5.18.2. Pushbutton interface
Choose if you would like to use the button as a button interface, and set the function.
Define which values are sent when the button is pressed/released, and when these are sent.
Use pushbutton • as button interface
• for temperature control Pushbutton functions Left button (short) --> target temperature down
Right button (short) --> target temperature up
Left button (longer than 2 sec) --> mode switch Right button (longer than 2 sec) --> mode switch
If both buttons are pressed in eco mode for more than 2 seconds, comfort mode is acti-
vated for the set duration. The following modes can be selected by pushbutton: Comfort No • Yes Standby No • Yes Eco No • Yes Building protection No • Yes
Use pushbutton interface No • Yes Function • Switch
• Changeover switch
• Shutter
• Roller blind
• Awning
• Window
• Dimmer
• 8-bit encoder
• 16-bit encoder
• Scenario recall
Command when pressing the pushbutton • send 0
• send 1
• do not send message
Command when releasing the pushbutton • send 0
• send 1
• do not send message
Page 62
60 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Changeover switching
Blind
Standard:
Standard inverted:
Comfort mode:
Send value • on change
• on change to 1
• on change to 0
• on change and periodically
• on change to 1 and periodically
• on change to 0 and periodically
Cycle (if sent periodically) 5 s • ... • 1 min • ... • 2 h
Command when pressing the pushbutton • Changeover switching
• do not send message
Command when releasing the pushbutton • Changeover switching
• do not send message
Pushbutton function • Up
• Down
Control mode • Standard
• Standard inverted
• Comfort mode
• Dead man’s switch
Behaviour for button actuation (up): short = Stop/Step | long = Up Behaviour for button actuation (down): short = Stop/Step | long = Down
Time between short and long in 0.1 seconds
0 ... 50; 10
Behaviour for button actuation (up): long = Stop/Step | short = Up Behaviour for button actuation (down): short = Stop/Step | long = Down
Time between short and long in 0.1 seconds
0 ... 50; 10
Repeat the step command for a long button press
every 0.1 s • every 2 sec; every 0.5 sec
Button is pushed and released before time 1 expired
held longer than time 1 released between time 1 and 1-2 released after time 1 +2
stop/step
Up or Down
Stop
no more stop Time 1 (in 0,1 s) 0 ... 50; 4 Time 2 (in 0,1 s) 0 ... 50; 20
Page 63
61 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Dead man‘s switch:
Shutter
Standard:
Standard inverted
Comfort mode:
Dead man‘s switch:
Push button down command Release button up command
Pushbutton function • Up
• Down
• Up/Down
Control mode • Standard
• Standard inverted
• Comfort mode
• Dead man‘s switch
Behaviour for button actuation (up): short = Stop | long = Up Behaviour for button actuation (down): short = Stop | long = Down Behaviour in case of button actuation (up/down): short = Stop | long = Up/Down
Time between short and long in 0.1 seconds
0 ... 50; 10
Behaviour for button actuation (up): long = Stop | short = Up Behaviour for button actuation (down): short = Stop | long = Down Behaviour in case of button actuation (up/down): short = Stop | long = Up/Down
Time between short and long in 0.1 seconds
0 ... 50; 10
Repeat the step command for a long button press (only Up)
no • every 0,1 s • ... • every 0,5 s • ... • every
2 s
Button is pushed and released before time 1 expired
held longer than time 1 released between time 1 and 1-2 released after time 1 +2
Stopp
Up | Down | Up/Down
Stop
no more stop Time 1 (in 0,1 s) 0 ... 50; 4 Time 2 (in 0,1 s) 0 ... 50; 20
Push button Up- | Down- | Up/Down command Release button Stop command
Page 64
62 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Awning
Standard:
Standard inverted:
Comfort mode:
Dead man‘s switch:
Pushbutton function • On
• Off
• On/Off
Control mode • Standard
• Standard inverted
• Comfort mode
• Dead man‘s switch
Behaviour in case of button actuation (retract): short = Stop | long = Retract Behaviour in case of button actuation (extend): short = Stop | long = Extend Behaviour in case of button actuation (retract/extend): short = Stop | long = Retract/Extend
Time between short and long in 0.1 seconds
0 ... 50; 10
Behaviour in case of button actuation (retract): long = Stop | short = Retract Behaviour in case of button actuation (extend): long = Stop | short = Extend Behaviour in case of button actuation (retract/extend): long = Stop | short = Retract/Extend
Time between short and long in 0.1 seconds
0 ... 50; 10
Repeat the step command for a long button press (only Up)
no • every 0,1 s • ... • every 0,5 s • ... • every
2 s
Button is pushed and released before time 1 expired
held longer than time 1 released between time 1 and 1-2 released after time 1 +2
Stop
On | Off | On/Off
Stop
no more stop Time 1 (in 0,1 s) 0 ... 50; 4 Time 2 (in 0,1 s) 0 ... 50; 20
Push button On- | Off- | On/Off command Release button Stop command
Page 65
63 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Window
Standard:
Standard inverted:
Comfort mode:
Dead man‘s switch:
Pushbutton function • Close
• Open
• Open/Close
Control mode • Standard
• Standard inverted
• Comfort mode
• Dead man‘s switch
Behaviour in case of button actuation (close): short = Stop | long = Close Behaviour for button actuation (up): short = Stop | long = Up Behaviour in case of button actuation (open/close): short = Stop | long = Open/Close
Time between short and long in 0.1 seconds
0 ... 50; 10
Behaviour in case of button actuation (close): long = Stop | short = Close Behaviour for button actuation (up): long = Stop | short = Up Behaviour in case of button actuation (open/close) long = Stop | short = Open/Close
Time between short and long in 0.1 seconds
0 ... 50; 10
Repeat the step command for a long button press (only Up)
no • every 0,1 s • ... • every 0,5 s • ... • every
2 s
Button is pushed and released before time 1 expired
held longer than time 1 released between time 1 and 1-2 released after time 1 +2
stop/step
Up or Down
Stop
no more stop Time 1 (in 0,1 s) 0 ... 50; 4 Time 2 (in 0,1 s) 0 ... 50; 20
Push button Close- | Up- | Open/Close command Release button Stop command
Page 66
64 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Dimmer
8 bit encoder
16 bit encoder:
Scenario control:
Pushbutton function • Brighter • darker • Brighter/darker Time between switching and dimming
in 0.1 seconds
0 ... 50; 5
Repetition of the dimming command No • Yes Repetition of the dimming command
upon extended button actuation
every 0,1 s • ... • every 0,5 s • ... • every 2 s
Dimming by 100% • ... • 6% • ... • 1,5%
Value range • 0 ... 255
• 0% ... 100%
• 0° ... 360°
Value • 0... 255
• 0
... 100
• 0°... 360°
Value in 0.1 -6707600 ... 6707600; 0
Scenario no. 0 ... 127
Page 67
65 Parameter setting
Sensor KNX AQS/TH-UP Touch • Version: 23.10.2018 • Technical changes and errors excepted.
Page 68
Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16
75395 Ostelsheim Phone +49 (0) 70 33 / 30 945-0 info@elsner-elektronik.de Germany Fax +49 (0) 70 33 / 30 945-20 www.elsner-elektronik.de
Technical support: +49 (0) 70 33 / 30 945-250
Loading...