INSTALLATION & MAINTENANCE MANUAL
TRLEDxxEM
52
1

GENERAL INSTRUCTIONS
TRLEDxx
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by the end user for future reference and
maintenance.
These instructions should be used to aid installation of the following products:
TRLED12 / TRLED14 / T RLED15 / TRLED16 / TRLED22 / TR LED24 / TRLED25 / TRLED26
SAFETY
• Installation of this luminaire should only be carried out by a qualified electrician or competent person to the
latest Building and current IEE Wiring Regulations (BS7671)
• Please isolate mains prior to installation/maintenance
• Check the total load on the circuit (including when this luminaire and LED load is fitted) does not exceed the
rating of the circuit cable, fuse or circuit breaker
• Please note the IP (Ingress of Protection) rating of this product when deciding the location for installation
• This product is Class I and must be earthed
• This product is IP65 rated
• This product is non-dimmable
Note: Outdoor electrical installations should be protected by an earth leakage circuit breaker such as a residua l current
device (RCD)
INSTALLATION
Note: If this luminaire is being used in conjunction with external PIR or sensors, please confirm with the manufacturer of
the sensors that they are compatible with LED luminaires
• Provide power to the required point of installation
• Important: Subject to the sur face foundation material, ensure the correct fixings are used if installed outside, the
mains cable should be connected into a suitable IP rated junction box
• Referring to Fig 1, using the mounting brackets as a template, mark the location of the fixing holes. Drill the fixing
holes ensuring not to infringe with any joists, gas/water pipes, or electrical cables that may be hidden behind the
surface
• Unfasten clips on either side of the fitting (see Fig 2)
These instructions should be read carefully and retained after installation by the end user for future reference
and maintenance.
These instructions should be used to aid installation of the following products:
TRLED14EM / TRLED15EM / TRLED15EMD / TRLED16EM / TRLED16EMD / TRLED24EM / TRLED25EM /
TRLED25EMD / TRLED26EM / TRLED26EMD
SAFETY
• Installation of this luminaire should only be carried out by a qualified electrician or competent person to the
latest Building and current IEE Wiring Regulations (BS7671)
• Please isolate mains prior to installation/maintenance
• Check the total load on the circuit (including when this luminaire and LED load is fitted) does not exceed the
rating of the circuit cable, fuse or circuit breaker
• Please note the IP (Ingress of Protection) rating of this product when deciding the location for installation
• We recommend a minimum charge period of 24 hours before completing an initial emergency duration test
• This product is Class I and must be earthed
• Installing in areas where the temperature consistently drops below 0°C may shorten the battery life
• This product is IP65 rated
• This product is non-dimmable
Note: Outdoor electrical installations should be protected by an earth leakage circuit breaker such as a
residual current device (RCD)
INSTALLATION
Note: If this luminaire is being used in conjunction with external PIR or sensors, please confirm with the
manufacturer of the sensors that they are compatible with LED luminaires
• Provide power to the required point of installation
• Important: Subject to the surface foundation material, ensure the correct fixings are used if installed outside, the
mains cable should be connected into a suitable IP rated junction box
• Referring to Fig 1, using the mounting brackets as a template mark the location of the fixing holes. Drill the fixing
holes ensuring not to infringe with any joists, gas/water pipes, or electrical cables that may be hidden behind the
surface
Fig 1
• Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
2
TRLED14EM
TRLED15EM/EMD
TRLED16EM/EMD
TRLED24EM
TRLED25EM/EMD
TRLED26EM/EMD
L (mm) L (ft) A1 (mm)
1263 4 900
1563 5 1000
1828 6 1000
1263 4 900
1563 5 1000
1828 6 1000

• Remove the diffuser
• Unfasten clips on either side of the fitting (see Fig 2)
Fig 2
• Remove the diffuser
• Remove the gear tray by pinching the clips at the two locations (see Fig 3)
• Remove the gear tray by pinching the clips at the two locations (see Fig 3)
Fig 3
• When using as a singular fitting, feed cable through compression gland (supplied) at the end of the fitting
• Connect the battery pack to the emergency inverter via the plug and socket
Connect the Neutral (blue), Earth (yellow and green), Live (1) and Switched Live (2) (see Fig 4)
Fig 4
• Replace the gear tray and diffuser ensuring all clips are fastened correctly
• Align the fitting with the mounting brackets and fix into place
• Switch on power supply and check for correct operation
Note: This fitting can be linked to another fitting by using the terminal connector (see Fig 4) at the opposite end
to the incoming power supply. There are knock-outs at both ends of the fitting which can be drilled using a 20mm
holesaw. The IP65 rating will be maintained when a 20mm compression gland (supplied) is used in the drilled hole.
WARNING
This product must be disconnected from the circuit if it subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
The product should be recycled in the correct manner when it reaches the end of its life. Check local authorities for
where facilities exist. If the batteries have been left in a discharged state for an extended period, we recommend
that one or more charge and discharge cycles are performed, which should restore the battery to its full capacity
The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact the local
authorities for the disposal of this toxic waste. Clean with a soft dry cloth only, do not use aggressive cleaning
products or solvents which may damage the product.
3

WARRANTY
This product has a warranty of 5 years (excluding battery) from date of purchase. Failure to install this product
in accordance with the current edition of the IEE Wiring Regulations, improper use, or removal of the batch
codes will invalidate the warranty. If this product should fail within its warranty period it should be returned to
the place of purchase for a free of charge replacement. Warranty only valid if test procedure BS5266 has been
complied with. ML Accessories does not accept responsibility for any installation costs associated with the
replacement product. Your statutory rights are not affected.
ML Accessories reserve the right to alter product specification without prior notice.
TESTING FOR EMERGENCY LUMINARES
RECOMMENDED ROUTINE TEST PROCEDURE IN ACCORDANCE WITH BS5266
We recommend a minimum charge period of 24 hours before completing an initial commissioning emergency
duration test
Daily check – check that the status GREEN LED indicator is illuminated.
Monthly functional test – simulate a mains supply failure for approx. 30 secs by operation of key switch or switching
off a circuit breaker. Ensure normal supply is restored after test and the indicator status LED is illuminated.
Annual full three hour duration test - conduct a three hour continuous duration test. Simulate a mains supply
failure for three hour continuous test by operation of key switch or switching off circuit breaker. Ensure normal
supply is restored after test and the indicator status LED is illuminated.
If the luminaire fails any of the above tests, please consult a qualified electrician
TEST RECORD SHEET
INITIAL COMMISSIONING
3 HOUR TEST
MONTH TEST
1 FUNCTIONAL
2 FUNCTIONAL
3 FUNCTIONAL
4 FUNCTIONAL
5 FUNCTIONAL
6 FUNCTIONAL
7 FUNCTIONAL
8 FUNCTIONAL
9 FUNCTIONAL
10 FUNCTIONAL
11 FUNCTIONAL
12 3 HOUR
FIRST YEAR SECOND YEAR THIRD YEAR FOURTH YEAR FIFTH YEAR
SIGNED DATE SIGNED DATE SIGNED DATE SIGNED D ATE SIGNED DAT E
SIGNED DATE
Installed by: Installation date:
Contact number: