These instructions should be read carefully and retained after installation by the end user for
future reference and maintenance.
These instructions should be used to aid installation of the following products:
TRLED14EM / TRLED15EM / TRLED15EMD / TRLED16EM / TRLED16EMD / TRLED24EM
TRLED25EM / TRLED25EMD / TRLED26EM / TRLED26EMD
SAFETY
• This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671)
and current Building Regulations. If in any doubt, consult a qualified electrician
• Please isolate mains prior to installation or maintenance
• Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the
circuit cable, fuse or circuit breaker
• Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
• This product is Class I and must be earthed
• This product is IP65 rated
INSTALLATION
Note - If this product is being used in conjunction with an external PIR or sensor, please confirm with the
manufacturer of the sensors that they are compatible with LED luminaires.
• Provide power to the required point of installation (refer to BS7671 for correct cabling methods). Suitable IP
rated junction boxes should be used where required
• Using the mounting brackets as a template, mark the location for, and drill the fixing holes ensuring not to
infringe with any gas/water pipes or electrical cables. Fixing centres are shown in Fig. 1
SAFETY
•Thisproductmust be installed in accordance with the latest edition ofthe IEE Wiring Regulations(BS7671)and current Building Regulations.If in any doubt,consult a qualified electrician
•Please isolate mains prior to installation or maintenance
•Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of
the circuitcable, fuse orcircuit breaker
•Please note the IP (Ingress Protection)rating of this productwhen decidingthe location for installation
•This product isClassI and mustbeearthed
•This product is IP65 rated
INSTALLATION
Note - Ifthis product is being used in conjunction with an external PIRor sensor, please confirm with the manufacturerof the sensors that they are compatible with LED luminaires.
•Provide power to the required point of installation (refer to BS7671 for correct cablingmethods).Suitable IP rated junction boxes should be used where required
•Using the mounting brackets as a template, mark the location for, and drillthe fixing holesensuring not
to infringe with any gas/waterpipes orelectrical cables. Fixing centres are shown inFig. 1
Fig. 1
•Secure the mounting bracketsto the surface using suitable fixings (not included)
•Unfasten the clips on eitherside of the fitting(see Fig. 2)
(BS7671) and currentBuilding Regulations.If in any doubt,consult a qualified electrician
the circuit cable,fuse orcircuit breaker
Suitable IP rated junction boxes should be used where required
to infringe with any gas/waterpipes orelectrical cables. Fixing centres are shown inFig. 1
Fig. 1
• Secure the mounting brackets to the surface using suitable fixings (not included)
• Unfasten the clips on either side of the fitting (see Fig. 2)
Fig. 2
Live, 2 - Switched Live (brown), E - Earth (green/yellow), N- Neutral (blue)(see Fig. 4)
• Remove the gear tray from the baseplate by pinching the clips at two locations (see Fig. 3)
Fig. 3
• Feed the mains cable through the compression gland provided at the end of the fitting
• Connect the luminaire to the mains supply ensuring the correct polarity is observed: 1 - Permanent Live,
Emergency (Brown), 2 - Switched Live (brown), E - Earth (green/yellow), N - Neutral (blue) (see Fig. 4)
Permanent Live, Emergency
(brown)
Fig. 4
• Connect the battery pack to the emergency inverter via the plug and socket
• Align the fitting with the mounting brackets and clip into place
• Tighten the compression gland ensuring a tight seal is made
• Replace the gear tray and diffuser ensuring all clips are fastened securely
• Switch on and check for correct operation, ensuring the green indicator LED is illuminated
• We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying
out an emergency duration test
• If the batteries have been left in a discharged state for an extended period, we recommend that one or more
charge and discharge cycles are completed which should help to restore the battery capacity
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
This product contains a light source of energy efficiency class C (TRLED14EM, TRLED25EMD, TRLED26EMD)
/ D (TRLED15EM, TRLED15EMD, TRLED16EM, TRLED16EMD, TRLED24EM, TRLED25EM, TRLED26EM) to
Regulation (EU) No. 2019/2015.
This product contains a non-replaceable LED light source and a control gear which can be replaced by a
professional.
Clean the external surfaces with a damp cloth using a mild solution of detergent and warm water only, do not
use aggressive cleaning products or solvents which may damage the product.
Do not use any source of high-pressure washers to maintain or clean this luminaire.
This product is non-dimmable.
This product should be dismantled for disposal when it reaches the end of its life. Please see website for
dismantling instructions.
This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities
for where facilities exist.
The batteries in this luminaire are Nickel Cadmium and must be disposed of correctly. Please contact the local
authorities for the disposal of this toxic waste.
WARRANTY
This product has a warranty of 5 years (excluding battery) from date of purchase. Failure to install this product
in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal
of the batch code will invalidate the warranty. If this product should fail within its warranty period, it should
be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept
responsibility for any installation costs associated with the replacement product. Your statutory rights are not
affected. ML Accessories reserve the right to alter product specification without prior notice.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
• Daily check – check LED charge indicator is illuminated
• Monthly functional test - simulate a mains supply failure for approx. 30 seconds by operation of key switch
or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is
illuminated
• Annual 3-hour duration test - simulate a mains supply failure for three hour continuous test by operation
of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge
indicator is illuminated
• If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record
sheet
TEST RECORD SHEET
INITIAL COMMISSIONING
3 HOUR TEST
MONTHTEST
1FUNCTIONAL
2FUNCTIONAL
3FUNCTIONAL
4FUNCTIONAL
5FUNCTIONAL
6FUNCTIONAL
7FUNCTIONAL
8FUNCTIONAL
9FUNCTIONAL
10FUNCTIONAL
11FUNCTIONAL
123 HOUR
FIRST YEARSECOND YEARTHIRD YEARFOURTH YEARFIFTH YEAR
SIGNEDDATE SIGNED DATE SIGNED DATE SIGNEDDATE SIGNEDDATE
Installed by: Installation date:
Contact number:
SIGNEDDATE
INTERNATIONAL
INTERNATIONAL
CONTACTDETAILS
INTERNATIONAL
CONTACTDETAILS
CONTACT DETAILS
ML Accessories Limited LU5 4LT
www.mlaccessories.co.uk
-20~
35°C
TA
52
DCSEP21_V2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.