Knightsbridge T8BLED15, T8BLED25, T8BLED14, T8BLED16, T8BLED24 Installation Instructions

...
INSTALLATION & MAINTENANCE MANUAL
T8BLED12 / T8BLED14 / T8BLED15 / T8BLED16 T8BLED22 / T8BLED24 / T8BLED25 / T8BLED26
These instructions should be read carefully and retained after installation by the end user for future reference and maintenance. These instructions should be used to aid installation of the following products: T8BLED12 / T8BLED14 / T8BLED15 / T8BLED16 / T8BLED22 / T8BLED24 / T8BLED25 / T8BLED26
SAFETY
• This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
• Please isolate mains prior to installation or maintenance
• Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the circuit cable, fuse or circuit breaker
• Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
• This product is for indoor use only
• This product is Class I and must be earthed
• This product is IP20 rated
INSTALLATION
Note - If this product is being used in conjunction with an external PIR or sensor, please confirm with the manufacturer of the sensors that they are compatible with LED luminaires.
• Provide power to the required point of installation
• Remove the two end caps with the aid of a flat-head screwdriver
• Single luminaire: squeeze the sides of the fitting together to separate the LED plate from the housing
• Twin luminaire: remove the two screws (see Fig. 1) and slide the LED plate away from the housing
INSTALLATION & MAINTENANCE MANUAL
Fig. 1
• Mark the location of the fixing holes and drill the holes ensuring not to infringe with any gas / water pipes or electrical cables. The fitting can also be mounted over conduit boxes, the distance between fixing centres is 60cm
• Feed the mains cable into the luminaire either through the rear, or by drilling the end cap and using a 20mm compression gland (not included)
• Secure the luminaire to the surface
• Ensuring correct polarity is observed, carefully wire as shown in Fig. 2
Fig. 2
• Check the earth tab connection is in place and reconnect if required
Check the earth tab connection is in place and reconnect if required
Ensure the battery is connected via the plug and socket
Refasten the cover
Switch on and check for correct operation, ensuring the green indicator LED is illuminated
We recommend, on commissioning the installation, a minimum charge period of 24 hours before
carrying out an emergency duration test
• Refasten the cover
• Switch on and check for correct operation
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
This product contains a light source of energy efficiency class D (T8BLED12, T8BLED14, T8BLED15, T8BLED22, T8BLED24, T8BLED25, T8BLED26) / E (T8BLED16) to Regulation (EU) No. 2019/2015 This product contains a non-replaceable LED light source and a control gear which can be replaced by a professional.
Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the product. This product is non-dimmable. This product should be dismantled for disposal when it reaches the end of its life. Please see website for dismantling instructions. This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities for where facilities exist.
WARRANTY
This product has a warranty of 5 years from date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specification without prior notice.