These instructions should be read carefully and retained after installation by the end user for
future reference and maintenance.
These instructions should be used to aid installation of the following product:
EMXSTL
SAFETY
• This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671)
and current Building Regulations. If in any doubt, consult a qualified electrician
• Please isolate mains prior to installation or maintenance
• Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the
circuit cable, fuse or circuit breaker
• Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
• This product is for indoor use only
• This product is Class II double insulated
• This product is IP20 rated
INSTALLATION
• Provide power to the required point of installation
• Remove the top plate by inserting a screwdriver into the slots on the side (see Fig. 1)
Page 3
INSTRUCTIONS EMXST
Insert screwdriv er to release top plate
Test button
LED indicator
Cable entry
Test button
LEDindicator
Fig. 1
• Mark the location of the fixing holes and drill the holes ensuring not to infringe with any gas/water pipes or
electrical cables
• Feed the mains cable through the cable entry hole on the top plate (see Fig. 2)
• Fix the luminaire to the surface using appropriate fixings
Fig. 2
• Connect the mains cable into the push-fit terminal block ensuring correct polarity is observed: Live (brown),
Neutral (blue)
• For non-maintained operation, remove the 2-pin connector from the circuit board (see Fig. 3).
For maintained operation keep it in place. This fitting cannot be connected for switched-maintained
operation
Page 4
maintained operationkeep it in place. This fitting cannot be connected for switched-maintained operation
Fig. 3
• Ensure the battery is connected via the plug and socket to the PCB
• Refit the luminaire to the top cover ensuring all 4 lugs lock into place
• Switch on and check for correct operation, ensuring the green indicator LED is illuminated
See below for operation of the self-test function
We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying
out an emergency duration test
SELF-TEST FUNCTION
This product is programmed to carry out its own self-test function according to the following
programme:
24 hours after first power-on3-hour duration test
then every 28 days30 second monthly function test
and every 52 weeks3-hour duration test
Following self-tests, the unit will go back into charging mode, and any faults will be indicated by the bi-colour
LED indicator as follows:
Page 5
LED INDICATORSTATUS
Solid greenNormal conditions / charging / test successful
1 Red flashBattery fault
2 Red flashesLamp fault
3 Red flashesDuration test failure
NB: power should be cut off and restored to the unit to clear a fault indication once the condition is rectified
Tests can also be initiated manually as follows:
TEST BUTTONGREEN LEDSTATUS
Short press
Press for approx.
5 seconds
Press for approx.
7 seconds
Press for approx.
10 seconds
Off
Slow flash
Fast flash
Emergency mode while test button held in
Emergency mode for 30 seconds
(monthly function test)
Emergency mode for 3 hours (duration test)
End the duration test
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance
testing. Irreparable damage will occur if this instruction is not followed
Page 6
WARRANTY
This product has a warranty of 3 years from date of purchase. Failure to install this product in accordance with
the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the batch codes will
invalidate the warranty. If this product should fail within its warranty period it should be returned to the place
of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation
costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve
the right to alter product specification without prior notice.
TESTING FOR EMERGENCY LUMINARIES
Recommended routine test procedure in accordance with BS5266:
• Daily check – check status of bi-colour LED indicator
• Monthly functional test – the luminaire will perform this function without any action from the user.
Alternatively, simulate a mains supply failure for approx. 30 seconds by operation of key switch, switching off
circuit breaker or using test button. Ensure normal supply is restored after test and check status of bi-colour
LED indicator
• Annual three-hour duration test – the luminaire will perform this function without any action from the user.
Alternatively, simulate a mains supply failure for three-hour continuous test by operation of key switch,
switching off circuit breaker or using test button. Ensure normal supply is restored after test and check status
of bi-colour LED indicator
• If the luminaire fails any of the above tests, please contact a qualified electrician. Results should be recorded,
even when obtained via the self-test function. See below for test record sheet
Page 7
GENERAL
The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole
luminaire should be replaced.
Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the
product.
This product is non-dimmable.
This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities
for where facilities exist.
The batteries in this luminaire are Lithium Ion and must be disposed of correctly. Please contact the local
authorities for the disposal of this toxic waste.
SUPPLIED BY:
(UK) MANUFACTURER
ML ACCESSORIES LTD, UNIT E CHIL-
TERN PARK,
BOSCOMBE ROAD, DUNSTABLE
LU5 4LT,
WWW.MLACCESSORIES.CO.UK
(EU) AUTHORISED REPRESENTATIVE
SLV LIGHTING GROUP,
DAIMLERSTRASSE 21-23,
52531 ÜBACH-PALENBERG, GERMANY
EMAIL: EPREL@GROUP.SLV.COM
MADE IN CHINA
0~45°C
TA
54
DCJUN23_V1
Page 8
TEST RECORD SHEET
INITIAL COMMISSIONING
3 HOUR TEST
SIGNEDDATE
MONTHTEST
FIRST YEARSECOND YEARTHIRD YEARFOURTH YEARFIFTH YEAR
SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE
1FUNCTIONAL
2FUNCTIONAL
3FUNCTIONAL
4FUNCTIONAL
5FUNCTIONAL
6FUNCTIONAL
7FUNCTIONAL
8FUNCTIONAL
9FUNCTIONAL
10FUNCTIONAL
11FUNCTIONAL
123 HOUR
Installed by: Installation date:
Contact number:
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.