Knightsbridge EMPOWER4ST, EMPOWER4WST Installation Instructions

Page 1
INSTALLATION & MAINTENANCE MANUAL
EMPOWER4ST/ EMPOWER4WST
Page 2
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by the end user for future reference and maintenance. These instructions should be used to aid installation of the following products: EMPOWER4ST / EMPOWER4WST 
SAFETY
• This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
• Please isolate mains prior to installation or maintenance
• Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the circuit cable, fuse or circuit breaker
• Please note the IP (Ingress Protection) rating of this product when deciding the location for installation
• Allow 50mm above and around the fitting for air dissipation (do not cover the fitting with insulation)
• This product is for indoor use only
• This product is Class II double insulated
• This product is IP20 rated
INSTALLATION
• Provide power to the required point of installation
• Cut a suitable hole in the mounting surface as per the cut-out details (see Fig. 1) ensuring not to infringe with any joists, gas / water pipes or electrical cables
Page 3
INSTALLATION & MAINTENANCE MANUAL
Fig. 1
• Connect the luminaire to the mains supply via a suitable junction box (not included) ensuring the correct polarity is observed: LS – Switched Live (brown), L - Live, N - Neutral (blue) (see Fig. 2)
Fig. 2
• Connect the battery via the plug and socket to the inverter
• Choose the required bezel and lens according to the light output pattern required (see Fig. 3)
Page 4
• Remove the bezel and lens by inserting a small flat screwdriver into the edge of the bezel and lift out
• Fit the required lens and bezel, ensuring the two clips on the rear of the bezel are aligned with the slots on the fitting
• Place the battery and inverter into the ceiling void ensuring that there is at least 50mm of clearance above and around them
• Lift both spring clips on the sides of the luminaire and push into the ceiling
• Switch on and check for correct operation, ensuring the green indicator LED is illuminated
SELF TEST FUNCTION
• This product is programmed to carry out its own self-test function according to the following programme:
24 hours after first power-on 3-hour duration test Then every 28 days 30 second monthly function test And every 52 weeks 3-hour duration test
The downlight has an integrated LED indicator which is illuminated green when charging and red to indicate faults. Following self-tests, the unit will go back into charging mode, and any faults will be indicated by the LED indicator as follows:
LED indicator Status
Solid green Normal conditions / charging / test successful
1 red flash Battery fault
2 red flashes Lamp fault
3 red flashes Duration test failure
NB: disconnect and restore power to the unit to clear a fault indication once the condition is rectified. This product has no facility for initiating tests manually.
Page 5
WARNING
This product must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire should be replaced. Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the product. This product is non-dimmable. This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities for where facilities exist. The batteries in this luminaire are Lithium Ion and must be disposed of correctly. Please contact the local authorities for the disposal of this toxic waste.
WARRANTY
This product has a warranty of 5 years from date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specification without prior notice.
Page 6
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
• Daily check – check LED charge indicator is illuminated
• Monthly functional test - simulate a mains supply failure for approx. 30 seconds by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
• Annual 3-hour duration test - simulate a mains supply failure for 3-hour continuous test by operation of key switch or switching off circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
• If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record sheet
Page 7
230V 50Hz
(UK) MANUFACTURER
ML ACCESSORIES LTD,
UNIT E CHILTERN PARK,
BOSCOMBE ROAD, DUNSTABLE
LU5 4LT,
WWW.MLACCESSORIES.CO.UK
IP20
SUPPLIED BY:
(EU) AUTHORISED REPRESENTATIVE
52531 ÜBACH-PALENBERG, GERMANY
0 ~
25°C
TA
54
SLV LIGHTING GROUP,
DAIMLERSTRASSE 21-23,
EMAIL: EPREL@GROUP.SLV.COM
MADE IN CHINA
AKDEC22_V1
Page 8