These instructions should be read carefully and retained after installation by the
end user for future reference and maintenance.
These instructions should be used to aid installation of the following product:
EMPOWER3
SAFETY
• This product must be installed in accordance with the latest edition of the IEE Wiring
Regulations (BS7671) and current Building Regulations. If in any doubt, consult a
qualified electrician
• Please isolate mains prior to installation or maintenance
• Check the total load on the circuit (including when this luminaire is fitted) does not exceed
the rating of the circuit cable, fuse or circuit breaker
• Please note the IP (Ingress Protection) rating of this luminaire when deciding the location
for installation
• Allow 50mm above and around the fitting for air dissipation (do not cover the fitting with
insulation)
• This product is for indoor use only
• This product is Class II double insulated
• This product is IP20 rated
Page 3
INSTALLATION
• Provide power to the required point of installation
• Cut a suitable hole in the mounting surface as per the cut-out details (see Fig. 1) ensuring
not to infringe with any joists, gas/water pipes or electrical cables
Fig. 1
• Connect the luminaire to the mains supply via a suitable junction box ensuring that
correct polarity is observed: Live (brown) and Neutral (blue) (see Fig. 2)
Page 4
Fig. 2
• Connect the battery to the inverter via the plug and socket provided, ensuring correct
polarity is observed
• Connect the downlight to the inverter via the plug and socket provided
• Change the bezel, if required, by unscrewing from the downlight and replacing with the
required bezel
• Place the inverter and battery into the ceiling via the cut-out
• Lift both spring clips on the sides of the fitting and push into the ceiling
• Switch on and check for correct operation, ensuring the green indicator LED is illuminated
• We recommend, on commissioning the installation, a minimum charge period of 24 hours
before carrying out an emergency duration test
Page 5
WARNING
This luminaire must be disconnected from the circuit if subjected to any high voltage or
insulation resistance testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
The LED lamps fitted in this product are non-replaceable. The product should be recycled
in the correct manner when it reaches the end of its life. Check local authorities for where
facilities exist.
The batteries in this luminaire are Lithium Ion and must be disposed of correctly. Please
contact the local authorities for the disposal of this toxic waste.
Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which
may damage the product.
This product is non-dimmable.
WARRANTY
This product has a warranty of 3 years (excluding battery) from date of purchase. Failure
to install this product in accordance with the current edition of the IEE Wiring Regulations
(BS7671), improper use, or removal of the batch code will invalidate the warranty. If this
product should fail within its warranty period, it should be returned to the place of purchase
for a free of charge replacement. ML Accessories does not accept responsibility for any
installation costs associated with the replacement product. Your statutory rights are not
affected. ML Accessories reserve the right to alter product specification without prior notice.
Page 6
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
• Daily check – check LED charge indicator is illuminated
• Monthly functional test - simulate a mains supply failure for approx. 30 seconds by
operation of key switch or switching off circuit breaker. Ensure normal supply is restored
after test and ensure charge indicator is illuminated
• Annual 3-hour duration test - simulate a mains supply failure for 3-hour
continuous test by operation of key switch or switching off circuit breaker. Ensure normal
supply is restored after test and ensure charge indicator is illuminated
• If the luminaire fails any of the above tests, please contact a qualified electrician. See
below/overleaf for test record sheet
Page 7
INITIAL COMMISSIONING
3 HOUR TEST
MONTHTEST
1FUNCTIONAL
2FUNCTIONAL
3FUNCTIONAL
4FUNCTIONAL
5FUNCTIONAL
6FUNCTIONAL
7FUNCTIONAL
8FUNCTIONAL
9FUNCTIONAL
10FUNCTIONAL
11FUNCTIONAL
123 HOUR
FIRST YEARSECOND YEARTHIRD YEARFOURTH YEARFIFTH YEAR
SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE
SIGNEDDATE
Installed by: Installation date:
Contact number:
TEST RECORD SHEET
Page 8
INTERNATIONAL
INTERNATIONAL
CONTACTDETAILS
INTERNATIONAL
CONTACTDETAILS
CONTACT DETAILS
ML Accessories Limited LU5 4LT
www.mlaccessories.co.uk
54
5~
60°C
TA
AVSEP21_V2
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.