Knightsbridge BATS4EM, BATS5EM, BATS6EM, BATS6EMH, BATS5EMH Installation Instructions

...
Page 1
INSTALLATION & MAINTENANCE MANUAL
BATS4EM / BATS5EM / BATS5EMH
BATS6EM / BATS6EMH / BATS5UHLEM
BATS6UHLEM
Page 2
GENERAL INSTRUCTIONS
These instructions should be read carefully and retained after installation by the end user for future reference and maintenance. These instructions should be used to aid installation of the following products: BATS4EM / BATS5EM / BATS5EMH / BATS6EM / BATS6EMH / BATS5UHLEM / BATS6UHLEM
SAFETY
• This product must be installed in accordance with the latest edition of the IEE Wiring Regulations (BS7671) and current Building Regulations. If in any doubt, consult a qualified electrician
• Please isolate mains prior to installation or maintenance
• Check the total load on the circuit (including when this luminaire is fitted) does not exceed the rating of the circuit cable, fuse or circuit breaker
• Please note the IP (Ingress Protection) rating of this luminaire when deciding the location for installation
• This product is for indoor use only
• This product is Class I and must be earthed
• This product series is IP20 rated
Page 3
Squeeze
INSTALLATION
Note - If this luminaire is being used in conjunction with an external PIR or sensor, please confirm with the manufacturer of the sensors that they are compatible with LED luminaires.
• Provide power to the required point of installation (refer to BS7671 for correct cabling methods)
• Squeeze the sides and hinge the diffuser away from the fitting (see Fig. 1)
• Mark the location of the fixing holes and drill the holes ensuring not to infringe with any gas/water pipes or electrical cables. The fitting can also be mounted over conduit boxes: for distance between fixing centres please see below:
Fig. 1
Part Code Distance (mm)
BATS4EM 600
BATS5EM / BATS5EMH / BATS5UHLEM 600
BATS6EM / BATS6EMH / BATS6UHLEM 600
Page 4
• Ensuring correct polarity is observed, carefully wire as shown in Fig. 2. Two cables can be
Distance (mm)
600
600
600
Squeeze
inserted into the push-fit terminal block in order to achieve loop-in / loop-out wiring
Fig. 2
• Connect the battery to the inverter
• Switch on and check for correct operation ensuring that the green LED indicator is illuminated
• We recommend, on commissioning the installation, a minimum charge period of 24 hours before carrying out an emergency duration test
Note - This fitting shuts off power to the Lithium Ion battery periodically to prevent overcharging. Therefore, the green LED indicator has been set up to indicate that the emergency inverter is in good condition, not to indicate that the battery is charging. The installer must ensure that the battery is connected.
Page 5
WARNING
This luminaire must be disconnected from the circuit if subjected to any high voltage or insulation resistance testing. Irreparable damage will occur if this instruction is not followed.
GENERAL
This product contains a light source of energy efficiency class E (BATSxEM, BATSxEMH) / D (BATSxUHLEM) to Regulation (EU) No. 2019/2015. This product contains a non-replaceable LED light source and a control gear which can be replaced by a professional.
Clean with a soft dry cloth only, do not use aggressive cleaning products or solvents which may damage the product. This product is non-dimmable This product should be dismantled for disposal when it reaches the end of its life. Please see website for dismantling instructions. This product should be recycled in the correct manner when it reaches the end of its life. Check local authorities for where facilities exist. The batteries in this luminaire are Lithium Ion and must be disposed of correctly. Please contact the local authorities for the disposal of this toxic waste.
Page 6
WARRANTY
This product has a warranty of 5 years (excluding battery) from date of purchase. Failure to install this product in accordance with the current edition of the IEE Wiring Regulations (BS7671), improper use, or removal of the batch code will invalidate the warranty. If this product should fail within its warranty period, it should be returned to the place of purchase for a free of charge replacement. ML Accessories does not accept responsibility for any installation costs associated with the replacement product. Your statutory rights are not affected. ML Accessories reserve the right to alter product specification without prior notice.
TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
• Daily check – check LED charge indicator is illuminated
• Monthly functional test - simulate a mains supply failure for approx. 30 seconds by operation of a key switch or switching off the circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
• Annual three-hour duration test - simulate a mains supply failure for three-hour continuous test by operation of a key switch or switching off the circuit breaker. Ensure normal supply is restored after test and ensure charge indicator is illuminated
• If the luminaire fails any of the above tests, please contact a qualified electrician. See below for test record sheet
Page 7
TEST RECORD SHEET
INITIAL COMMISSIONING
3 HOUR TEST
MONTH TEST
1 FUNCTIONAL
2 FUNCTIONAL
3 FUNCTIONAL
4 FUNCTIONAL
5 FUNCTIONAL
6 FUNCTIONAL
7 FUNCTIONAL
8 FUNCTIONAL
9 FUNCTIONAL
10 FUNCTIONAL
11 FUNCTIONAL
12 3 HOUR
FIRST YEAR SECOND YEAR THIRD YEAR FOURTH YEAR FIFTH YEAR
SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE SIGNED DATE
SIGNED DATE
Installed by: Installation date:
Contact number:
Page 8
INTERNATIONAL
INTERNATIONAL
CONTACT DETAILS
INTERNATIONAL
CONTACT DETAILS
CONTACT DETAILS
ML Accessories Limited LU5 4LT
www.mlaccessories.co.uk
52
-20~ 50°C
TA
DCAUG21_V3
Loading...