KMC Controls VEF-56 User Manual

Installation Guide
E/I–P Transducer
XEC-3001/3002/3004

(Snap Track) Mounting

The transducers may be mounted in any position.
1. Carefully remove the circuit board from the Snap Track.
3. Replace board in the track. Do not slide or ex the circuit board while replacing.

Connections

A clean, dry, oil-free main air supply is required for proper operation. An internal, non-replaceable lter is used. If air supply contamination is suspected, use an external HFO-0006 in-line lter.
The gauge port will accept a 1/8" male NPT pressure gauge. This allows direct reading of the pressure output. This port must be plugged if a pressure gauge is not required.
1. Connect the 20 psi main air to the “M” port.
2. Connect the “B” port to the controlled device (damper or valve actuator).

Wiring

1. Connect the power.
a. 24 VAC (+20%/–15%, Class 2 Only, 1 VA):
Transformer phase lead to “~” (phase).
Neutral lead to “GND” (common).
b. 24 VDC (+66%/–8%, 50 mA):
Positive to “~” (phase).
Negative to “GND.”
NOTE: Any other device connected to this
(Class 2 only) transformer must use the same common. If you are not sure of the other device’s polarity, use a separate transformer. If the shared device is a coil, use a spike-snubbing device across the coil to prevent possible malfunctions.
2. Position Input Program Jumper to 1–5 VDC, 2–10 VDC, or 4–20 mA.
3. Connect the input signal wiring, positive to “IN” and negative to “GND.”
4. Connect the output feedback signal (if required) positive to “OUT 1–5” and negative to “GND.”
XEC-3001/3002/3004 1 Installation Guide

Adjustments

Maintenance

Manual Override (XEC-3004 Only)

1. Move the “MAN/AUTO” jumper from “AUTO” to “MAN.” (See the illustration on page 1.)
2. Adjust the potentiometer for desired output by observing gauge or the 1–5 VDC output signal.

Span and Zero

The “Span and “Zero” adjustments are factory-set and should never need adjusting. On boards manu­factured before Nov. 2009 (only), this calibration may be adjusted slightly as follows:
1. Disconnect the main air.
2. Adjust the “ZERO” potentiometer to 0.1 VDC feedback output.
3. Reconnect the main air.
4. Apply an input voltage of 5.1 or 10.2 VDC or input current of 20.4 mA.
5. Adjust the “SPAN” potentiometer for 15 psi branch output pressure.
No routine maintenance is required. Each compo­nent is designed for dependable, long-term reliabil­ity, and performance. Careful installation will also ensure long-term reliability and performance.
CAUTION
Pneumatic devices must be supplied with clean, dry control air. Any other medium (e.g., oil or moisture contamination) will cause the device to fail.

Models

XEC-3001 Module only
XEC-3002 Module mounted in an HCO-
1008 enclosure (not shown)
XEC-3004 Module only with manual over-
ride

Accessories

6. Apply an input voltage of 3 or 6 VDC or input current of 12 mA.
7. Readjust the “ZERO” potentiometer for 9 psi.
HCO-1008 Enclosure (for XEC-3001/3004)
HFO-0006 In-line air lter
ICI-1005 2", 0–30 psi gauge
For other pneumatic accessories, such as connectors, tubing, ings, lters, and gauges, see the Com­pressed Air Accessories section in the KMC Controls Catalog (SP-071).
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
XEC-3001/3002/3004 2 Installation Guide
© 2013 KMC Controls, Inc. 871-019-01J
Loading...