1. Clean the lines upstream from the valve. Remove any debris larger than 0.06" (0.015 mm).
2. Alignthevalve’sowindicatorwiththesystem ow.
3. Mount the valve so the actuator is positioned over valve.
CAUTION
Using mineral oil lubricants or other incompatible substances in system fluids may damage EPDM rubber seals in valves. Before using any lubricant or additive in a water or ethylene glycol base, consult the substance manufacturer for compatibility with EPDM (Ethylene Propylene Diene Monomer).

Wiring

NOTE: The installed actuator model is indicated
by the last two digits of the VEB valve model number (e.g., VEB-43xxxxCK has an MEP-4002V actuator) and the last three digits of the older VEP valve model number (e.g., VEP-45xxx745 has an MEP-4002 actuator). For wiring and other
information about tri-state and other actuators no longer sold mounted on these valves, see the respective actuator’s installation guide on the KMC web site.
CAUTION
To prevent condensation from dripping onto the actuator housing, mount the valve with the actuator in the upright position or, at most, at a 45° angle.
4. Seal valves with approved pipe sealant.
5. Using two wrenches, secure the valve to the pipe. Torque should not exceed 75 ft-lb. (102 N
6. Eliminate air from the system to keep the valves
fullofuidduringoperation.
NOTE: If the system experiences large amounts of
debris, steps should be taken to keep the system clean.
UP
Full CW = Valve Closed Full CCW = Valve Open
SYSTEM FLOW
VEB-43/VEP-45 Series 2-Way (1/2 to 3") NPT Control Ball Valves 1 Installation Guide
m).
ACTION:
Power
Supply
Control Signal
2–10 VDC
~
+
CK/745 Wiring (MEP-4002)
+
Feedback Output
1–5 or 2–10 VDC
NOTE: Before January 2014, MEP-40x2/48x2
models had 0–10 VDC inputs. They now have 2–10 VDC inputs. When replacing an older 0–10 VDC actuator with a 2–10 VDC
actuator,conguretheconnectedcontroller
or thermostat output to match.
Feedback Output 1–5 or 2–10 VDC
COM (Black)
T
OUT (Green)
2–10 IN (White)
~24 V (Red)
+ –
CL Wiring (MEP-4x52)
Power Supply
~/+
24 VAC/VDC
Control Signal
+
2–10 VDC

More Information

Formodels,specications,
and additional information, see the VEB-43/VFB-43
Series Data Sheet on the
KMC web site.
For additional instructions on wiring, feedback selec­tor, and actuator/signal range reset (auto-mapping), see the MEP-4000/4800 Series Installation Guide or (fail-safe) MEP-4200/4500/4900 Series Installation
Guide.

Operation

After the mechanical and electrical installations have been completed, cycle the actuator to verify the direction of rotation for normal operation and fail-safe if so equipped.

Maintenance

No routine maintenance is required. Each compo­nent is designed for dependable, long-term reliabil­ity, and performance. Careful installation will also ensure long-term reliability and performance.
For non-fail-safe wiring, auxiliary switches, feed­back/direction selectors, actuator/signal range reset (auto-mapping), and other information, see the MEP-
4000/4800 Series Installa­tion Guide.
For fail-safe wiring, auxiliary switches, feed­back/direction selectors, actuator/signal range reset (auto-mapping), and other information, see the
MEP-4200/4500/4900 Series Installation Guide.

Important Notices

For information on assem­bling a quick-mount “V”
The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice. KMC
actuator on a valve body, see the HPO-5074 Installation
Guide.
makes no representations or warranties with respect to this document. In no event shall KMC be liable for any damages, direct or incidental, arising out of or related to the use of this document.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
VEB-43/VEP-45 Series 2-Way (1/2 to 3") NPT Control Ball Valves 2 Installation Guide© 2013 KMC Controls, Inc. 050-019-53G
Loading...