Mounting

3-Way, Mixing or Diverting, Flanged, Control Ball Valves
VEB-56 Series
Installation Guide
1. Clean the lines upstream from the valve. Remove any debris (welding slag, pipe scale, or other contaminants) larger than 1/16 inch (1.6 mm).
NOTE: If the system experiences large amounts
of debris, steps should be taken to keep the system clean, such as 20 mesh strainer installed upstream of the valve.
2. Align the valve assembly according to the system
ow requirements (see the illustration below).
3. The valve may be mounted on either vertical or horizontal pipe lines. On horizontal lines, mount the valve so the actuator is positioned upright
Diverting Flow Action:
Port 'AB' to Port 'A'—full CW; Port 'AB' to 'B'—full CCW
Full CW
AB
A
and over the valve. (Leave sucient room on all
sides to service the actuator and valve.)
CAUTION
To prevent condensation from dripping onto the actuator housing on horizontal lines, mount the valve with the actuator in the upright position or, at most, at a 45° angle.
4. Install approved ange gaskets (not supplied by
KMC Controls) and bolt the valve to the pipes.
5. Eliminate air from the system to keep the valves
full of uid during operation.
Mixing Flow Action:
Port 'A' to Port 'AB'—full CW; Port 'B' to 'AB'—full CCW
Full CCW
AB
D
A
B
B
UP (on
horizontal
lines)
E
B
Size
Dimensions (Inches):
A B
11.875 9 14.5 10.375 18 80
13.875 10 15.5 12 18.875 95
15.875 11 16.5 13.375 20 110
C
D
E
Weight
(lb.)
CAUTION
Using mineral oil lubricants or other incompatible substances in system fluids may damage EPDM rubber seals in valves. Before using any lubricant or additive in a water or ethylene glycol base, consult the substance manufacturer for compatibility with EPDM (Ethylene Propylene Diene Monomer).
VEB-56 Series Valves 1 Installation Guide
A
C

Wiring

Wiring is dependent on the type of actuator and the desired options that are available. Consult the actuator model label and then the relevant sections in the MEP-7500/7800 Series Actuators Installation
Guide for detailed instructions on the applicable
wiring, feedback selector, and actuator/signal range reset (auto-mapping) of the valve’s actuator. (See the More Information section.)

More Information

For models, specications, and additional information, see the VEB-56 Series Data
Sheet on the KMC web site
(www.kmccontrols.com).

Operation

After the mechanical and electrical installations have been completed, cycle the actuator to verify the direction of rotation for normal operation and
fail-safe if so equipped.

Maintenance

No routine maintenance is required. The motors are
permanently lubricated. Careful installation will also ensure long term reliability and performance.

Accessories/Repair Parts

CME-7001 Single auxiliary switch, 1 SPDT
CME-7002 Dual auxiliary switch, 2 SPDT
HMO-4536 Adjustable stop kit
MEP-7xxx Replacement actuator (see label
on actuator or data sheet)
For wiring, feedback/
direction selectors, ac­tuator/signal range reset (auto-mapping), and other
information, see the MEP-
7500/7800 Series Installa­tion Guide.
For actuator specications and other information, see the MEP-7500/7800 Series
Data Sheet.
For accessories, trouble­shooting, and other
information, see the MEP-
7500/7800 Series Applica­tion Guide.