KMC Controls STE-6010, STE-6012, STE-6011, STE-6013 STE-6015, STE-6016 Application Manual

...
Room Temperature Sensors
2.438
2.250
R 3.094
R .187
.450
STE-6012/6013/6019/6020
STE-6011
STE-6010/6014/6015/6016/6017/6018
Modular
RJ-45
Jack
Four-pin
EIA-485
PC Data
Port
Clamp
(Screw-type)
Terminals
Clamp
(Screw-type)
Terminals
.422 for
6019/6020
.149 for
6012/6013;
Applications Guide
STE-6000 Series
STE-6010/6011 STE-6013/6015
STE-6000 Series Overview .........................................................................................................................................2
Maintenance ..............................................................................................................................................................3
More Information ......................................................................................................................................................3
Wiring ........................................................................................................................................................................3
STE-6011 ............................................................................................................................................................. 3
STE-6013 ............................................................................................................................................................. 3
STE-6019/6020 ....................................................................................................................................................3
STE-6012 ............................................................................................................................................................. 3
STE-6010/6014/6015/6016/6017/6018 .............................................................................................................. 4
STE-6012/6016 Connection Configuration ................................................................................................................5
Overview .............................................................................................................................................................5
Controller Connection .........................................................................................................................................5
Fahrenheit/Celsius Display Selection ...................................................................................................................5
Temperature Calibration (Offset) Procedure ........................................................................................................5
Controller Configuration ............................................................................................................................................6
Overview .............................................................................................................................................................6
WinControl ..........................................................................................................................................................6
BACstage .............................................................................................................................................................9
STE-6000 Series Room Temperature Sensors 1 Applications Guide
STE-6012/6016
All dimensions are in inches
STE-6014 STE-6018/6020STE-6017/6019
STE-6000 Series Overview
These compact, stylish, and economical room temperature sensors are designed for use in KMC Digital controllers or other building automation systems. They incorporate a 10,000 ohm (@ 77° F) thermistor for the sensing element, providing
precise, stable temperature sensing. The low prole
and durable thermostat-style cover are visually appealing. These sensors may be surface mounted on a hollow wall or to a 2 x 4 in. electrical box.
The STE-6000 Series is specically designed to
complement the KMC Digital controllers.
An STE-6010/6011 contains a thermistor only.
An STE-6014/6017/6019/6018/6020 includes a rotary setpoint dial (available in degrees F or C).
An STE-6013/6015/6017/6019/6018/6020 allows selec­tion of an override condition by pushing the buon on the front. A green status LED (not on the STE-
6017/6019) illuminates according to the user-dened controller conguration (e.g., during setback/setup
or during normal/override modes).
An STE-6012/6016 includes an LCD display for the room temperature and setpoint. The temperature display can be toggled between Fahrenheit and Celsius scales. The setpoint is adjustable via the up and down arrow buons on the front panel. If the system is in normal/override mode, pressing a
buon will raise or lower the setpoint. When either buon is pushed, the display will toggle from room temperature to the setpoint. When the buon is
released, the number displayed is the new setpoint,
and the display will return to room temperature aer ten seconds. If the system is in setback/setup (for heating/cooling) mode, pressing either buon selects
override mode.
An STE-6010/6014/6015/6016/6017/6018 includes a four-pin EIA-485 (formerly RS-485) data port on the cover’s underside for easy temporary computer
connection to the network. (Access with a KMD-5624
cable.)
For more specications and mounting instructions,
see the Data Sheet and the Installation Guide for the STE-6000 series.
The following models are available:
Setpoint
Adjust
STE-
601x
Model
Number
Rotary Dial
6010-10 X X X
6011-10 X X
6013-10 X X X X
6015-10 X X X X X
6012-10 X X X X X
6016-10 X X X X X X
6014-10 ° F X X X
6014-11 ° C X X X
6017-10 ° F X X X X
6017-11 ° C X X X X
6019-10 ° F X X X
6019-11 ° C X X X
6018-10 ° F X X X X X
6018-11 ° C X X X X X
6020-10 ° F X X X X
6020-11 ° C X X X X
Other
Interface
Features
Up/Down Buttons
Override Button(s)
Connections
LCD Display
LED Status Indicator
Cable
RJ-45 Connector
Screw Clamp Terminals
EIA-485 Data Port
Temper-
ature
Output
10k Ohms Thermistor
The standard color is almond. To order in white
(minimum quantity of 250 required), add a “W” in the
place of the hyphen near the end of the model number (e.g., STE-6012W10).
Accessories available include:
HMO-6036: Universal Backplate
KMD-569x: STE-6010/6014/6015/6016 to Con-
troller Cable with RJ-45 to RJ-11 Connectors (­5693 = 25 ft.; -5694 = 50 ft.; -5695 = 75 ft.)
KMD-5624: PC Data Port (EIA-485) Cable
KMD-5576: EIA-485 to USB Communicator
0 to 5 VDC
STE-6000 Series Room Temperature Sensors 2 Applications Guide
Maintenance
Wiring
Careful installation will also ensure long-term reli­ability and performance. Remove dust as necessary
from holes in top and boom. Clean with a so,
damp cloth and mild soap.
More Information
For additional specications, see the STE-6000 Data
Sheet.
For mounting information, see the STE-6000 Installa­tion Guide.
For an additional sample application of program-
ming override timers, adapt the information in the
Application Note AN0504F Programming Override Timers section of the the Digital Designer’s Guide (SP-022).
For applications requiring humidity sensing, the
THE-1002/1102/1105 humidity transmiers also
include the same type of thermistor as in the STE­6000 series.
Connect wires as shown for the relevant model.
STE-6011
(Wires are
interchangeable)
Thermistor (10k Ohms)
STE-6013
10 VDC LED Supply (from Controller)
Common (Ground)
Thermistor (10k Ohms)
(Override
Button)
D
B
C
STE-6019/6020
Potentiometer
Common (Ground)
Thermistor (10k Ohms)
10 VDC LED Supply (from Controller; for STE-6020 Only)
(Override
Button)
A
B
C
D
STE-6012
7.5 VDC (Setback/Setup) or
D
B
C
A
{
12 VDC (Normal/Override) Supply (from Controller)
{
Common (Ground)
0–5 VDC Temperature Signal and (Momentary)
{
SENSOR-ON (0 VDC) or SENSOR-OFF (> 5 VDC)
{
0–5 VDC Setpoint Signal
NOTE: In the STE-6012/6016, pressing the Down buon
momentarily sends 0 VDC to the controller for
a SENSOR-ON signal; pressing the Up buon
sends greater than 5 VDC for a SENSOR-OFF
signal. When in normal/override mode, pressing the Down or Up buon raises or lowers the setpoint voltage. When in setback/setup mode, pressing either buon selects override mode.)
(For the STE-6010/6014/6015/6016/6017/6018, see the next page. )
STE-6000 Series Room Temperature Sensors 3 Applications Guide
STE-6010/6014/6015/6016/6017/6018
KMD–5693 = 25 feet; KMD–5694 = 50 feet; KMD–5695 = 75 feet
1 8
Orange Wire = Thermistor Input to Controller
Orange/White Wire = Setpoint Signal Input to Controller (for STE-6014/6016/6017/6018 only; clip or tape when not used)
12 inches
52
RJ-11 and
Wire Leads
to Controller
RJ-45 to STE Sensor
Green Wire = Aux. Supply Voltage to STE-6015/6018 (10 VDC) or STE-6016 (7.5/12 VDC) (clip or tape when not used)
RJ-11 RJ-45 Color
(Lead) 8 Orange 7 N.C. (Lead) 6 Green 3 5 Blue 4 4 Blue/White 5 3 Green 2 N.C. (Lead) 1 Orange/White
(Cables crossed, 20 AWG)
Controller Connection
Connecting any of these models to a controller requires a special cable with (on the sensor end) an RJ-45 connector and (on the controller end) an RJ-11 connector with an additional three wires (as relevant to the model) for controller inputs. Purchasing preassembled cables from KMC is more cost- eective and reliable than creating custom cables in
the eld. Use one of the following cables:
KMD-5693 = 25 .
KMD-5694 = 50 .
KMD-5695 = 75 .
The additional orange wire is for the thermistor input to the controller. The additional orange/white wire is for the STE-6014/6016/6017/6018 setpoint signal input to the controller. The additional green wire is for the auxiliary supply voltage of 10 VDC to the STE-6015/6018 or 7.5/12 VDC to the STE-6016. The STE-6016 is the only model that uses all the wires. For the other models, clip or tape the unused wire(s).
PC Port Connection
At the boom of an STE-
6010/6014/6015/6016/601 7/6018 case is an EIA-485 (formerly RS-485) comput­er port. This port provides a temporary connection
to the digital network for network setup or troubleshooting.
To use the port to connect to a computer, a means of converting the EIA-485 signal to a USB or EIA-232 (formerly RS-232) signal will be needed. The exact connection depends on the computer and the opera-
tor workstation soware. (See also the instructions included with those devices and soware.)
For USB (to WinControl or BACstage), use a KMD-
5576 USB Communicator.
For EIA-232 to BACstage, use a third-party interface.
For EIA-232 to WinControl, use the following (or
equivalent) items:
KMD-5624 NetSensor to PC cable
KMD-5559 CommTalk
KMD-5625 adapter cable
To access the network through the STE’s port:
1. Connect the keyed, at end of the EIA-485 cable to the port on the boom of the STE.
2. Connect the other end of the cable to the interface device that converts the EIA-485 signal into an EIA-232 or USB signal.
3. Connect the suitable cable from the interface device to the computer’s serial or USB port. Install
any required soware and congure the port as
necessary.
STE-6000 Series Room Temperature Sensors 4 Applications Guide
Loading...
+ 8 hidden pages