STE-6000 Series Overview .........................................................................................................................................2
More Information ......................................................................................................................................................3
STE-6000 Series Room Temperature Sensors 1 Applications Guide
STE-6012/6016
All dimensions are in inches
STE-6014STE-6018/6020STE-6017/6019
STE-6000 Series Overview
These compact, stylish, and economical room
temperature sensors are designed for use in KMC
Digital controllers or other building automation
systems. They incorporate a 10,000 ohm (@ 77°
F) thermistor for the sensing element, providing
precise, stable temperature sensing. The low prole
and durable thermostat-style cover are visually
appealing. These sensors may be surface mounted on
a hollow wall or to a 2 x 4 in. electrical box.
The STE-6000 Series is specically designed to
complement the KMC Digital controllers.
An STE-6010/6011 contains a thermistor only.
An STE-6014/6017/6019/6018/6020 includes a rotary setpoint dial (available in degrees F or C).
An STE-6013/6015/6017/6019/6018/6020 allows selection of an override condition by pushing the buon
on the front. A green status LED (not on the STE-
6017/6019) illuminates according to the user-dened
controller conguration (e.g., during setback/setup
or during normal/override modes).
An STE-6012/6016 includes an LCD display for the
room temperature and setpoint. The temperature
display can be toggled between Fahrenheit and
Celsius scales. The setpoint is adjustable via the
up and down arrow buons on the front panel. If
the system is in normal/override mode, pressing a
buon will raise or lower the setpoint. When either
buon is pushed, the display will toggle from room
temperature to the setpoint. When the buon is
released, the number displayed is the new setpoint,
and the display will return to room temperature aer
ten seconds. If the system is in setback/setup (for
heating/cooling) mode, pressing either buon selects
override mode.
An STE-6010/6014/6015/6016/6017/6018 includes a
four-pin EIA-485 (formerly RS-485) data port on
the cover’s underside for easy temporary computer
connection to the network. (Access with a KMD-5624
cable.)
For more specications and mounting instructions,
see the Data Sheet and the Installation Guide for
the STE-6000 series.
The following models are available:
Setpoint
Adjust
STE-
601x
Model
Number
Rotary Dial
6010-10XXX
6011-10XX
6013-10XXXX
6015-10XXXXX
6012-10XXXXX
6016-10XXXXXX
6014-10° FXXX
6014-11° CXXX
6017-10° FXXXX
6017-11° CXXXX
6019-10° FXXX
6019-11° CXXX
6018-10° FXXXXX
6018-11° CXXXXX
6020-10° FXXXX
6020-11° CXXXX
Other
Interface
Features
Up/Down Buttons
Override Button(s)
Connections
LCD Display
LED Status Indicator
Cable
RJ-45 Connector
Screw Clamp Terminals
EIA-485 Data Port
Temper-
ature
Output
10k Ohms Thermistor
The standard color is almond. To order in white
(minimum quantity of 250 required), add a “W” in the
place of the hyphen near the end of the model number
(e.g., STE-6012W10).
Accessories available include:
◆ HMO-6036: Universal Backplate
◆ KMD-569x: STE-6010/6014/6015/6016 to Con-
troller Cable with RJ-45 to RJ-11 Connectors (5693 = 25 ft.; -5694 = 50 ft.; -5695 = 75 ft.)
◆ KMD-5624: PC Data Port (EIA-485) Cable
◆ KMD-5576: EIA-485 to USB Communicator
0 to 5 VDC
STE-6000 Series Room Temperature Sensors 2 Applications Guide
Maintenance
Wiring
Careful installation will also ensure long-term reliability and performance. Remove dust as necessary
from holes in top and boom. Clean with a so,
damp cloth and mild soap.
More Information
For additional specications, see the STE-6000 Data
Sheet.
For mounting information, see the STE-6000 Installation Guide.
For an additional sample application of program-
ming override timers, adapt the information in the
Application Note AN0504F Programming Override
Timers section of the the Digital Designer’s Guide
(SP-022).
For applications requiring humidity sensing, the
THE-1002/1102/1105 humidity transmiers also
include the same type of thermistor as in the STE6000 series.
Connect wires as shown for the relevant model.
STE-6011
(Wires are
interchangeable)
Thermistor (10k Ohms)
STE-6013
10 VDC LED Supply (from Controller)
Common (Ground)
Thermistor (10k Ohms)
(Override
Button)
D
B
C
STE-6019/6020
Potentiometer
Common (Ground)
Thermistor (10k Ohms)
10 VDC LED Supply (from Controller;
for STE-6020 Only)
(Override
Button)
A
B
C
D
STE-6012
7.5 VDC (Setback/Setup) or
D
B
C
A
{
12 VDC (Normal/Override) Supply (from Controller)
{
Common (Ground)
0–5 VDC Temperature Signal and (Momentary)
{
SENSOR-ON (0 VDC) or SENSOR-OFF (> 5 VDC)
{
0–5 VDC Setpoint Signal
NOTE: In the STE-6012/6016, pressing the Down buon
momentarily sends 0 VDC to the controller for
a SENSOR-ON signal; pressing the Up buon
sends greater than 5 VDC for a SENSOR-OFF
signal. When in normal/override mode, pressing
the Down or Up buon raises or lowers the
setpoint voltage. When in setback/setup mode,
pressing either buon selects override mode.)
(For the STE-6010/6014/6015/6016/6017/6018, see the
next page. )
STE-6000 Series Room Temperature Sensors 3 Applications Guide
Orange/White Wire = Setpoint Signal Input to Controller
(for STE-6014/6016/6017/6018 only; clip or tape when not used)
12 inches
52
RJ-11 and
Wire Leads
to Controller
RJ-45
to STE
Sensor
Green Wire = Aux. Supply Voltage to STE-6015/6018
(10 VDC) or STE-6016 (7.5/12 VDC) (clip or tape when not used)
RJ-11 RJ-45 Color
(Lead) 8 Orange
7 N.C.
(Lead) 6 Green
3 5 Blue
4 4 Blue/White
5 3 Green
2 N.C.
(Lead) 1 Orange/White
(Cables crossed, 20 AWG)
Controller Connection
Connecting any of these models to a controller
requires a special cable with (on the sensor end) an
RJ-45 connector and (on the controller end) an RJ-11
connector with an additional three wires (as relevant
to the model) for controller inputs. Purchasing
preassembled cables from KMC is more cost-eective and reliable than creating custom cables in
the eld. Use one of the following cables:
KMD-5693 = 25 .
•
KMD-5694 = 50 .
•
KMD-5695 = 75 .
•
The additional orange wire is for the thermistor
input to the controller. The additional orange/white
wire is for the STE-6014/6016/6017/6018 setpoint
signal input to the controller. The additional green
wire is for the auxiliary supply voltage of 10 VDC
to the STE-6015/6018 or 7.5/12 VDC to the STE-6016.
The STE-6016 is the only model that uses all the
wires. For the other models, clip or tape the unused
wire(s).
PC Port Connection
At the boom of an STE-
6010/6014/6015/6016/601
7/6018 case is an EIA-485
(formerly RS-485) computer port. This port provides
a temporary connection
to the digital network for
network setup or troubleshooting.
To use the port to connect to a computer, a means of
converting the EIA-485 signal to a USB or EIA-232
(formerly RS-232) signal will be needed. The exact
connection depends on the computer and the opera-
tor workstation soware. (See also the instructions
included with those devices and soware.)
For USB (to WinControl or BACstage), use a KMD-
5576 USB Communicator.
For EIA-232 to BACstage, use a third-party interface.
For EIA-232 to WinControl, use the following (or
equivalent) items:
KMD-5624 NetSensor to PC cable
•
KMD-5559 CommTalk
•
KMD-5625 adapter cable
•
To access the network through the STE’s port:
1. Connect the keyed, at end of the EIA-485 cable
to the port on the boom of the STE.
2. Connect the other end of the cable to the interface
device that converts the EIA-485 signal into an
EIA-232 or USB signal.
3. Connect the suitable cable from the interface
device to the computer’s serial or USB port. Install
any required soware and congure the port as
necessary.
STE-6000 Series Room Temperature Sensors 4 Applications Guide
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.