Mounting
Temperature Sensor, Strap-On
STE-1454/1455
Installation Guide
These models are designed for monitoring uid temperatures in situations where an immersion sensor
cannot be used. Mount the probe in direct physical
contact with the pipe and under pipe insulation.
1. For the STE-1454 (only), mount the included
case (see the diagram) in a suitable location close
to where the probe will be aached to the pipe.
Aach conduit to it as needed.
NOTE: The STE-1455 does not include an
enclosure.
2. From the probe area, remove any pipe insulation
and clean the exterior of the pipe to ensure good
contact and heat transfer.
NOTE: For best results, apply thermal conductive
compound to the pipe underneath the
sensor.
3. Place the sensor probe in direct contact with the
pipe and strap the probe to the pipe using metal
pipe straps or cable ties.
4. Any extra lead length can be wound around the
pipe for extra security.
5. Wrap, or replace, insulation around the sensor to
reduce the eect of ambient air temperature.
3.320“
84.3 mm
53.6 mm
2.10”
53.3 mm
2.110”
Plastic Enclosure
Mounting Holes (X2) Ø 0.200”
4.56”
115.8 mm
2X Ø 0.850”
Metal Enclosure
8X Ø 0.875”
4.24”
107.7 mm
5.0 feet
1.524 m
2”
50 mm
0.25“
6.35 mm
304 Series
S/S Probe
4.0”
101.6 mm
2.04 ”
51.8 mm
5.0 feet
1.524 m
2”
50 mm
0.25“
6.35 mm
304 Series
S/S Probe
Connections and Wiring
1. For the STE-1454, feed the wire leads through
the hole in the enclosure and secure with the
included grommet.
2. Make connections to the two wire leads with
either bu-splices or solder. Using wire nuts is
not recommended.
STE-1454/1455 1 Installation Guide
NOTE: The two-wire sensor is not polarity
sensitive.
Configuration
More Information
For controller conguration, see the Type III Sensors
Applications Guide on the KMC web site.
Maintenance
No routine maintenance is required. Each component is designed for dependable, long-term reliability
and performance. Careful installation will also
ensure long term reliability and performance.
Specifications
Sensor Type III thermistor, 10K ohm @
77° F (25° C)
Temperature Limits –4 to 221° F (–20 to 105° C)
Wiring 5 foot (1.52 m) PVC insulated,
parallel bonded, 2 wire pigtail,
22 AWG
Probe Material 304 series stainless steel
Probe Dimensions 2" (50 mm) length by 0.25"
(6.35 mm) diameter
Enclosure (STE-1454 Only)
Standard: ame-retardant
plastic
Metal: Galvanized steel
For additional information,
see the STE-1400 Series
Data Sheet on the KMC
web site.
For troubleshooting, con-
troller conguration, and
other information, see the
Type III Sensors Applications Guide on the KMC
web site.
Important Notices
The KMC logo and KMC Controls are registered
trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may
be reproduced, transmied, transcribed, stored in a
retrieval system, or translated into any language in
any form by any means without the wrien permission of KMC Controls, Inc.
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
STE-1454/1455 2 Installation Guide