Room Temperature Sensor (Flat Plate)
Installation Guide
Mounting and Wiring
The STE-1430 is a blank, stainless-steel wall plate
that incorporates a precision sensor used to monitor
room temperatures where additional security is
required (e.g., against vandalism).
It is designed to be mounted directly to a single-gang
electrical box. Insulating foam is adhered to the back
of the wall plate to provide a thermal barrier from
internal wall temperatures. The STE-1430 should
be installed where it can sense the average room
temperature and be unaected by direct sunlight
and drafts.
STE-1430
1. Feed the cable wires through the conduit or hole
opening.
2. Make connections to the two sensor wire leads
with either bu-splices or solder. (Using wire
nuts is not recommended.) The two-wire sensor
is not polarity sensitive.
3. Plug the conduit with plumber’s puy, painter’s
puy, caulk, or other sealant to prevent air
inltration.
4. Aach the sensor panel to the electrical box using
the two supplied #6 screws.
Configuration
For controller conguration, see the Type III Sensors
Applications Guide on the KMC web site.
Specifications
0.1875"
4.75 mm
3.375"
85.73 mm
4.5"
114.3 mm
2.75"
69.85 mm
Sensor Type III thermistor, 10K ohm
@ 77° F (25° C)
Temperature Limits –4 to 221° F (–20 to 105° C)
Wiring 22 AWG wire leads
Dimensions 2-3/4 x 4-1/2 inches (70 x 114
mm)
Finish Brushed stainless steel
STE-1430 1 Installation Guide
Maintenance
No routine maintenance is required. Each component is designed for dependable, long-term reliability
and performance. Careful installation will also
ensure long term reliability and performance.
![](/html/d8/d825/d8258975a1c529b5dcdea2094cf3555c4cc3b9e938f30f01c06a154f67cfb731/bg2.png)
More Information
Important Notices
For additional information,
see the STE-1400 Series
Data Sheet on the KMC
web site.
For troubleshooting, con-
troller conguration, and
other information, see the
Type III Sensors Applications Guide on the KMC
web site.
The KMC logo and KMC Controls are registered
trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may
be reproduced, transmied, transcribed, stored in a
retrieval system, or translated into any language in
any form by any means without the wrien permission of KMC Controls, Inc.
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
STE-1430 2 Installation Guide© 2014 KMC Controls, Inc. 717-019-20B