Mounting
Duct Temperature Sensor, Averaging (Flexible)
STE-1415/1416/1417
Installation Guide
The averaging temperature sensor incorporates several discrete sensors encapsulated at equal distances
across the length of the probe. The complete assembly acts as a single sensor to monitor the average
temperature in a duct. Averaging elements are not
recommended for high humidity applications.
53.6 mm
2.110"
2X Ø 0.850”
Foam Gasket
115.8 mm
4.56"
FT6 Plenum rated cable
The sensors can be installed onto hangers in the
duct using tube clamps or wire ties. They should
be located in a straight section of duct away from
heating, cooling, or humidier elements.
Temperature sensors can be aected by air stratica-
tion in the duct, air leakage through the conduit
or other duct holes, and nearness to exterior walls,
a large thermal mass (e.g., concrete blocks), heat
sources, or wires with power.
Because of air stratication, the coldest air tends to
be toward the boom of the duct. Hence, one of the
sensors should be near the boom of the duct.
The exible cable can be easily shaped to t any duct
size but observe a minimum bend radius of two
inches to prevent damage to wires or sensors.
1. Cut a hole in the duct large enough to feed the
sensor cable through the back of the sensor
enclosure.
2. Fasten the enclosure to the duct by drilling holes
in the duct and threading screws through the
mounting holes in the case.
3. Insert the sensor cable into the duct, stringing the
cable to cover the air path, and secure as needed.
4. For the cable leading to the building automation
system controller, aach conduit to a hole in one
of the sides.
Various Cable Lengths
Mounting Holes (X2) Ø 0.200"
84.3 mm
3.320"
STE-1415/1416/1417 1 Installation Guide
Use
Tie Wraps
to Secure
Cable
2"
Min.
Bend
Radius
Connections and Wiring
More Information
1. Feed wires from the controller through the
conduit opening.
2. Make connections to the two sensor wire leads
with either bu-splices or solder. (Using wire
nuts is not recommended.) The two-wire sensor is
not polarity sensitive.
3. Plug the conduit with plumber’s puy, painter’s
puy, caulk, or other sealant to prevent air
inltration.
Configuration
For controller conguration, see the Type III Sensors
Applications Guide on the KMC web site.
Maintenance
No routine maintenance is required. Each component is designed for dependable, long-term reliability
and performance. Careful installation will also
ensure long term reliability and performance.
Specifications
Sensor Type III thermistor, 10K ohm @
77° F (25° C)
Temperature Limits –4 to 221° F (–20 to 105° C)
Wiring FT6 plenum-rated, 22 AWG
wire leads
Enclosure Flame-retardant ABS plastic
Cable Lengths and Number of Discrete Sensors
For additional information,
see the STE-1400 Series
Data Sheet on the KMC
web site.
For troubleshooting, con-
troller conguration, and
other information, see the
Type III Sensors Applications Guide on the KMC
web site.
Important Notices
The KMC logo and KMC Controls are registered
trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may
be reproduced, transmied, transcribed, stored in a
retrieval system, or translated into any language in
any form by any means without the wrien permission of KMC Controls, Inc.
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
STE-1415 6 feet (1.8 m), 4 sensors
STE-1416 12 feet (3.6 m), 4 sensors
STE-1417 24 feet (7.3 m), 9 sensors
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
STE-1415/1416/1417 2 Installation Guide
© 2014 KMC Controls, Inc. 717-019-16D