KMC Controls STE-1400 Series Application Manual

Applications Guide
Type III Temperature Sensors
STE-1400 and Other Series
Contents
Introduction ...................................................................1
Mounting Considerations ...............................................1
Troubleshooting .............................................................1
Controller Configuration ................................................2
Overview ....................................................................2
BAC-A1616BC BACnet Building Controller ................2
BACstage Software .....................................................2
TotalControl Software ................................................3
WinControl Software..................................................3
Important Notices ..........................................................3
Maintenance ..................................................................3
Introduction
This document gives conguration, troubleshoot­ing, and other related information for temperature sensors using Type III thermistors. For mounting,
wiring, and specications, see the respective product
installation guide and data sheet (STE-1400 Series
Data Sheet for STE-14xx sensors).
For information about Type II thermistor sensors, see:
STE-6010/6011/6013/6015 Application Guide for
room temperature sensors with optional override
buon and LED indicator.
STE-6014/6017/6018/6019/6020 Application
Guide for room temperature sensors with rotary
setpoint dials and optional override buon and LED indicator.
STE-6012/6016 Application Guide for room
temperature transmiers with LCD displays.
The latest support les are always available on the
KMC Controls web site (www.kmccontrols.com).
Mounting Considerations
Depending on the application, space temperature sensors generally should NOT be:
• Mounted on an exterior wall.
• Mounted on or near a large thermal mass (e.g., concrete block wall).
• Blocked from normal air circulation by obstruc­tions.
• Exposed to heat sources (e.g., lights, computers, copiers, or coee makers) or to sunlight (at any time of the day).
Exposed to drafts from windows, diusers, or returns.
Exposed to air ow through the conduit (from
leaks in plenum ducts)—put plumber’s puy, painter’s puy, caulk, or other sealant inside the conduit to block air ow.
Apply what is relevant to other applications (e.g., duct sensor).
Troubleshooting
• Check wiring. To prevent excessive voltage drop, use a conductor size that is adequate for the wiring length!
Check sensor conguration and tables in the controller.
• Check voltage from the controller.
• Check that the sensor is mounted correctly. (See the Mounting Considerations section above.)
Type III Temperature Sensors 1 Applications Guide, AN1013A Rev. B
Controller Configuration
Overview
Ensure that the corresponding 10,000 ohm pull-up resistors on the controller are selected (switched On). Consult the controller’s setup instructions for
information on switching on the pull-up resistors.
See the relevant software section for controller
conguration instructions.
BAC-A1616BC BACnet Building Controller
Select the 10K ohm pull-up resistor jumper posi­tion for the corresponding input. (See the Installa-
tion section of the BAC-A1616ABC Building Control­ler Installation and Operation Guide for the correct jumper position.)
Because the Building Controller has a 0–12 VDC
total input range, dierent tables are required than
in other (0–5 VDC) KMC controllers. If needed,
download the sensor tables (CSV) le from the
KMC Controls Partners web site and import the needed tables as described in the Tables section of the BAC-A1616ABC Building Controller Installa­tion and Operation Guide. (You must log into the
Partners site to see the zipped tables le on the
Building Controller product page downloads.)
1. In the desired Analog Input setup screen of the web page interface, select KMC Type III Degree Fahrenheit or KMC Type III Degree Celsius.
2. Select the Lookup Table for the Type III Thermistor. (Having it in Table 3 is good practice.)
BACstage Software
1. In the BACstage software main menu, select Objects > Inputs.
2. Click Edit.
3. Type in a name in the appropriate Description
eld (up to 32 characters) and/or Name eld (up
to 16 characters).
NOTE: No two labels or descriptions in a controller
can be identical.
4. Select Object Type: Analog if it is not the default.
5. Select Device Type: KMC10K Type III.
6. Select Units: °F or °C.
7. Optionally, change the Filter Weight (under More) to the desired number of thermistor readings averaged before displaying the result.
8. Click End Edit.
9. Click Yes for “Send Update Notication Now?”
10. In the BACstage software main menu, select Device > Device Tables > KMC10K Type III Table.
11. Click Edit.
12. Click Defaults (values will ll in).
13. Click End Edit.
14. Click Yes for “Send Update Notication Now?”
15. Click OK.
3. For the Fahrenheit scale, the multiplier is 1.8 and
the oset is 32. For Celsius, the multiplier is 1 and the oset is 0.
4. Click Save.
NOTE: See also TotalControl Software on page
3.
Type III Temperature Sensors 2 Applications Guide, AN1013A Rev. B
Loading...
+ 1 hidden pages