KMC Controls SimplyVAV BAC-8001, SimplyVAV BAC-8205, SimplyVAV BAC-8005, SimplyVAV BAC-8007 Application And Installation Manual

SimplyVAV
Application and Installation Guide
Revision H
KMC Controls, Inc.
©2018, KMCControls, Inc.
NetSensor, WinControl, and the KMC logo are registered trademarks of KMC Controls, Inc.
AppStat, BACstage, FlexStat, FullBAC, KMC Connect, KMC Connect Lite, KMC Converge, KMC Converge GFX, KMC Conquest, TotalControl, SimplyVAV, and the SimplyVAV logo are trademarks of KMC Controls, Inc.
Printed in U.S.A.
The material in this manual is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this manual. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this manual.
KMC Controls, Inc.
19476 Industrial Drive New Paris, IN 46553 U.S.A. TEL: 1.574.831.5250 FAX: 1.574.831.5252
info@kmccontrols.com
2 Revision H
SimplyVAV Contents

C o n t e n t s

Contents 3
Section 1: About the controllers 5
Specifications 6 Accessories and replacement parts 9 Available models 10 Safety considerations 10
Section 2: Installing the controllers 13
Setting the rotation limits 13 Mounting on a VAV terminal box 14 Connecting an airflow sensor 15 Connecting inputs and outputs 15 Connecting room temperature sensors 15 Connecting a DAT sensor 16 Connecting power 17 Maintenance 18
Section 3: Changing the room setpoint 19
Section 4: Configuring the controllers 21
Getting started with configuration 21 Entering system temperature setpoints and limits 23 Configuring the VAV Box options 27 Set the airflow setpoints 29 Advanced options 33 Restore Application 35
Section 5: Balancing airflow 37
Section 6: Application drawings 41
Cooling or heating without reheat 42 Staged reheat 43 Modulating reheat 44 Time proportional reheat 45 Floating reheat 46 Dual-duct application 47
Section 7: Sequences of operation 49
Input sources 49 Occupancy sequence 50
Automatic occupancy 50 Occupied 50 Unoccupied 51 Standby 51
Space setpoints 51
Types of setpoints 51
Setpoint limits 52 PID control loops 52 Airflow setpoints sequence 53 Changeover 53 Discharge Air Temperature (DAT) limiting 53
Revision H 3
Contents KMC Controls, Inc.
System diagnostic indicators 54
NEED AHU (BV1) 55 NEED COLDER SUPPLY (BV2) 55 NEED MORE STATIC (BV3) 55
NEED HOTTER SUPPLY (BV7) 55 Damper operation 55 Fan operation 56
Series Fan 56
Parallel Fan 56 Reheat sequence 57
Modulating reheat 58
Staged reheat 58
Time proportioned reheat 59
Floating reheat 59 Balancing airflow sequence 60 Dual duct 61
Section 8: System integration and networking 63
Connecting to an MS/TP network 63
Connections and wiring 64
End of line termination switches 64
Network bulbs 64 Setting up network communications 65 BACnet objects 67
Input objects 67
Output objects 67
Value objects 68
Loop objects 70
Appendix A: K-factors 71
Index 73
4 Revision H
SimplyVAV

Sec tion 1: About the cont roll er s

This section provides a description of the SimplyVAV series of controllers. It also introduces safety information. Review this material before selecting, installing, or operating the controllers.
The SimplyVAV series of controllers are an easy and unique approach to operating a wide variety of VAV terminal units. The integrated actuators, internal airflow sensors, and wide variety of application programs make these BACnet Application Specific controllers ideal for either new or retrofit installations.
The controllers feature simple, menu driven setup choices when used with a SimplyVAV digital sensor. No special programming skills or software tools are required to choose applications, enter setpoints, set networkaddressing, and balance airflow. All options can be set by using only an STE-8001 sensor which can be installed as the permanent room sensor ortemporarily connected as a technician’s service tool.
All models are BACnet Application Specific Controllers that are ready to connect to a BACnet MS/TP network. Device instance, MAC address, and baud rate are set from an STE-8001 sensor without special software.
BAC-8001Model BAC-8001 is supplied with inputs, outputs, and sequences of operation for
the following functions.
l Single duct heating and cooling VAV
l Automatic heating/cooling changeover including morning warmup
l Occupancy setback—requires STE-8201
l System diagnostic indicators
l Airflow balancing
BAC-8005 and BAC-8205 Models BAC-8005 and BAC-8205 are supplied with inputs,
outputs, and sequences of operation forthe following functions.
l Single duct heating and cooling VAV
l Modulating, floating, time proportional, and staged reheat
l Series and parallel fan control
l Automatic heating/cooling changeover including morning warmup
l Discharge air temperature limiting
l Occupancy setback—requires STE-8201
l Actuator position feedback fortrue damper positioning (BAC-8205 only)
l System diagnostic indicators
l Airflow balancing
Revision H 5
Section 1: About the controllers KMC Controls, Inc.
BAC-8007Model BAC-8007 is supplied with inputs, outputs, and sequences of operation for
the following functions.
l Dual-duct VAV heating and cooling
l Occupancy setback—requires STE-8201
l System diagnostic indicators
l Airflow balancing
Additional topics in this section
Specifications 6 Accessories and replacement parts 9 Available models 10 Safety considerations 10

Specifications

SimplyVAV controller specifications are subject to change without notice.
Inputs and outputs
All inputs and outputs are factory programmed and application specific. No field configuration is required. For details on input and output connections, see the topic
Application drawings on page 41. For a detailed listing of input and output objects, see the
topic BACnet objects on page 67.
Analog inputs
Analog inputs represent BACnet analog input. Not all input are applicable or required for all models.
Key features Standard units of measure.
Overvoltage input protection
Connectors RJ-45 room sensor jack
Screw terminals for wire sizes 12-26 AWG
Conversion 12–bit analog–to–digital conversion
Input range Passive, 10 kΩ pull-up to 3.3 volts DC
Analog outputs
Analog outputs are configured to represent BACnet analog output objects. No field configuration is required. For details on application specific outputconnections see the section Application drawingson page 41.
Key features Output short protection
Standard units of measure
Connector Screw terminals for wire size 12-26AWG
Conversion 12–bit digital-to-analog conversion
Output voltage 0–10 VDC
Output current 30 mA per output, 30 mA total for all analog outputs
6 Revision H
SimplyVAV Section 1: About the controllers
Binary outputs
Binary outputs are configured to represent BACnet binary output objects. No field configuration is required. For details on application specific outputconnections see the section Application drawingson page 41.
Key features Optically isolated triac output
Connector Screw terminals for wire size 12-26AWG
Output range Maximum switching 24 Volts AC
1 ampere per external output, 3 amperes total
Communications—BACnet MS/TP
l EIA–485 operating at rates up to 76.8 kilobaud.
l Removable screw terminal block.
l Wire size 12-26AWG
l Switch selected end of line termination
Memory
l Programs and program parameters are stored in nonvolatile memory.
l Auto restart on power failure
Air flow sensor features
l Configured as BACnet analog inputobject.
l CMOS differential pressure 0-2 inches of water (0-500 Pa) measurement range.
Internally linearized and temperature compensated.
l Span accuracy 4.5% of reading.
l Zero point accuracy 0.0008 in. H2O/0.2 Pa at 25° C
l Barbed connections for 1/4 inch FR tubing.
Actuator specifications
Torque 40 in-lb. (4.5 N•m)
Angular rotation 0 to 95°
Adjustable end stops at 45° and 60° rotation
Motor timing BAC-8001, BAC-8005, BAC-8007
Motor timing BAC-8205
Shaft size Directly mounts on 3/8 to 5/8inch (9.5to16mm) round or 3/8
90 sec./90° at 60 Hz 108 sec./90° at 50 Hz
60 sec./90° at 60 Hz
to 7/16 inch (9.5to11 mm) square damper shafts.
Revision H 7
Section 1: About the controllers KMC Controls, Inc.
Regulatory
l UL 916 Energy Management Equipment
l BACnet Testing Laboratory listed as an application specific controller (ASC).
l CE compliant
l FCC Class B, Part 15, Subpart B and complies with Canadian ICES-003 Class B
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Installation
Supply voltage 24 volts AC, -15%, +20% 5 VA,
Weight 13.2ounces (376 grams)
Case material Flame retardant plastic
Environmental limits
Operating 32 to 120° F (0 to 49° C)
Shipping –40 to 140° F (–40 to 60° C)
Humidity 5–93% relative humidity (non-condensing)
50/60 Hz
8 Revision H
ON CTS
1 2
1.92 in. 49 mm
6.53 in.
166 mm
4.89 in.
124 mm
4.25 in.
108 mm
0.77 in. 19 mm
6.00 in.
152 mm
2.14 in. 54 mm
SimplyVAV Section 1: About the controllers
Dimensions

Accessories and replacement parts

The following accessories and replacement parts are available from KMC Controls, Inc.
Power transformer
XEE-6111-50 Transformer, 120-to-24VAC, 50 VA, single-hub
XEE-6112-50 Transformer, 120-to-24VAC, 50 VA, dual-hub
XEE-6311-100 Transformer, 120, 277 -to-24 VAC, 50/60 Hz, 96 VA, dual-hub
Sensors
STE-8001W80 SimplyVAV sensor and digital display
STE-8201W80 SimplyVAV sensor and digital display with motion sensor
STE-6010W80 Discrete temperature sensor with RJ-45 connector
STE-6014W80 Discrete temperature sensor with rotary setpoint dial, RJ-45
STE-6017W80 Discrete temperature sensor with rotary setpoint dial, override
HPO-9005 Room Sensor Adapter
connector
button, RJ-45 connector
Revision H 9
Section 1: About the controllers KMC Controls, Inc.
Sensor cables
HSO-9001 Cable: Ethernet, 50 foot
HSO-9011 Cable: Ethernet, 50 foot, Plenum Rated
Surge suppressors
KMD-5567 EIA-485 surge suppressor for MS/TPnetworks
Replacement parts
HPO-0054 Replacement bulbs
HPO-0063 Replacement two-pin jumper
Dual duct actuator
TSP-8001 VAV actuator with airflow inputs (required for dual duct)
Airflow sensors
For VAV terminal units withoutairflow pickup tubes, order one of the following sensors.
SSS-1012 3-5/32 in. length (80 mm)
SSS-1013 5-13/32 in. length (137 mm)
SSS-1014 7-21-32 in. length (195 mm)
SSS-1015 9-29/32 in. length (252 mm)
KIT-8001 A 3-5/32 inch sensor and 3 feet of FR tubing

Available models

The following is a list of SimplyVAV available models.
Description Models
BACnet ASC: VAV Cooling/Heating only, 40 in-lbs, 90second actuator BAC-8001
BACnet ASC: VAV Fan and Reheat, 40 in-lbs, 90second actuator BAC-8005
BACnet ASC: VAV Dual Duct, 40 in-lbs, 90second actuator BAC-8007
BACnet ASC: VAV Fan and Reheat, True damper position, 40 in-lbs, 60 second actuator
BAC-8205

Safety considerations

KMC Controls assumes the responsibility for providing you a safe product and safety guidelines during its use. Safety means protection to all individuals who install, operate, and service the equipment as well as protection of the equipment itself. To promote safety, we use hazard alert labeling in this manual. Follow the associated guidelines to avoid hazards.
10 Revision H
Danger
Warning
Caution
SimplyVAV Section 1: About the controllers
Danger represents the most severe hazard alert. Bodily harm or death will occur if danger guidelines are not followed.
Warning represents hazards that could result in severe injury or death.
Caution indicates potential personal injury or equipment or property damage if instructions are not followed.
Note: Notes provide additional information that is important.
Tip: Provides programing tips and shortcuts that may save time.
Revision H 11
Section 1: About the controllers KMC Controls, Inc.
12 Revision H
Caution
45
60
Position notch as shown
Stop position holes
Stop screw in storage
Rotate CW
SimplyVAV

Sec tion 2: Instal l ing the controllers

This section provides important instructions and guidelines for installing the SimplyVAV controllers. Carefully review this information before installing the controller.
Installing SimplyVAV includes the following topics that are covered in this section.
Installation topics in this section
Setting the rotation limits 13 Mounting on a VAV terminal box 14 Connecting an airflow sensor 15 Connecting inputs and outputs 15 Connecting room temperature sensors 15 Connecting a DAT sensor 16 Connecting power 17 Maintenance 18

Setting the rotation limits

SimplyVAV controllers are manufactured for a damper that rotates 90 degrees from open to close. If the VAV damper is not a 90 degree damper, set the rotation limits to 45 or 60 degrees before mounting the controller.
Illustration 2–1 Controller rotation limit selections
Before setting the rotation limits on the controller, refer to the damper position specifications in the VAV control box to which the controller will be attached. Setting rotation limits that do not match the VAV damper may result in improper operation or equipment damage.
Revision H 13
ON CTS
1 2
COMM READY
AI1
AI5
GND
AO4
AO3
SC
BO8
BO5
BO6
SC
BO7
24VAC
AI6
GND
AI7
T-STAT/
SENSOR
-A
+B
S
EOL
BACnet MS/TP
Status LEDs
Mounting
tab
Mounting bushing
Gear clutch button
Drive hub and V-bolt
Section 2: Installing the controllers KMC Controls, Inc.
To set the rotational limits, do the following
1 Turn the controller over so you have access to the back.
2 Manually rotate the actuator fully clockwise as viewed from the back.
3 Remove the stop screw from its storage location and clean any debris from the
threads.
4 Insert the screw into the correct stop position hole.
5 Tighten the screw only until the head touches the plastic in the bottom of the recess.

Mounting on a VAV terminal box

Mount the controller inside of a metal enclosure. To maintain RF emissions specifications, use either shielded connecting cables or enclose all cables in conduit.
Mount the controller directly over the damper shaft. A minimum shaft length of 2.0 inch (51mm) is required.
Note: SimplyVAV controllers are designed to directly mount to 3/8 to 5/8inch (9.5to16mm)
round or 3/8 to 7/16 inch (9.5to11 mm) square damper shafts.
Illustration 2–2 Controls and indicators
Mount the controller as follows:
1 Manually rotate the damper on the VAV box to the fully open position.
2 On the controller, press the gear clutch button and rotate the drive hub in the same
direction that opened the damper. Turn the hub until it reaches a rotation limit.
3 Loosen the nuts on the V-bolt until the damper shaft can fit through the collar.
4 Place the controller over the damper shaft.
5 Finger tighten the nuts on the V-bolt to position the shaft in the drive hub.
6 Center the mounting bushing in the mounting tab and fasten it with a #8 sheet metal
screw.
14 Revision H
7 Evenly tighten the V-bolt nuts on the drive hub to 30-35 in-lbs.
ON CTS
1 2
COMM READY
24VAC
T-STAT/
SENSOR
-A
+B
S
EOL
BACnet MS/TP
Total airflow (high) Static airflow (low)
SimplyVAV Section 2: Installing the controllers

Connecting an airflow sensor

An airflow sensor is incorporated as one of the inputs to the controller. Remove the plugs and connect the tubing from the pitot assembly to the airflow sensor inputs next to the drive hub.
Illustration 2–3 Airflow sensor inputs
Typically, airflow sensors are supplied by the manufacturer as part of the VAV terminal unit. If a sensor is needed, choose a sensor listed in the topic Accessories and replacement
parts on page 9.

Connecting inputs and outputs

SimplyVAV series controllers have preconfigured inputs and outputs to support only the supplied programs and applications.
l For input and output connection information, see the topic Application drawingson
page 41.
l To connect room temperature sensors, see the topic Connecting room
temperature sensors on page 15
l To connect a DAT sensor, see the topic Connecting a DAT sensor on page 16.
l For the BACnet object descriptions of the inputs and outputs, see the topic BACnet
objects on page 67.

Connecting room temperature sensors

Connect any of the following sensors to the RJ-45 thermostat and sensor jack. The controller automatically detects the type of sensor. No programming or configuration is required.
Revision H 15
l STE-6010W80
l STE-6014W80
l STE-6017W80
l STE-8001W80
l STE-8201W80
Ethernet cable
Maximum 75 feet
DAT sensor Prefered location
DAT sensor Changeover only
Section 2: Installing the controllers KMC Controls, Inc.
Connect the controller to sensors with standard Ethernet cables up to 75 feet long. See the installation guide supplied with the sensors for sensor installation instructions.
Illustration 2–4 Connecting to a sensor

Connecting a DAT sensor

The Discharge Air Temperature sensor is required forautomatic changeover and for VAV terminal units with reheat.
Illustration 2–5 Discharge air temperature sensor location
16 Revision H
T
COMM READY
AI1
GND
AO4
AO3
Blue
Brown
24 VAC Class 2
ON CTS
1 2
COMM READY
AI1
AI5
GND
AO4
AO3
SC
BO8
BO5
BO6
SC
BO7
24VAC
AI6
GND
AI7
T-STAT/
SENSOR
-A
+B
S
EOL
BACnet MS/TP
SimplyVAV Section 2: Installing the controllers
Connect a 10 kΩ, Type 3 thermistor temperature probe to the discharge air temperature input. The input includes the internal pull-up resistor. An STE-1401 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation.
l For DAT limiting and reheat, install the sensor in the airflow after the reheat unit. See
the topic, Advanced options on page 33 to enable discharge air temperature control.
l When the DAT sensor is used only to detect primary air temperature, the sensor can be
placed in either location shown in the illustration Discharge air temperature
sensor location.
Illustration 2–6 Discharge air temperature input details

Connecting power

The controllers require a 24 volt, AC power source. Use the following guidelines when choosing and wiring transformers to the controller.
l Use a Class–2 transformer of the appropriate size to supply power to the controller.
l KMC Controls recommends powering only one controller from each transformer.
l Do not run 24 volt, AC power from within an enclosure to external controllers.
Connect the 24 volt AC power supply to the power terminal block on the lower right side of the controller. Connect the ground side of the transformer to the ground terminal and the AC phase to the phase terminal. Power is applied to the controller when the transformer is connected to power.
Illustration 2–7 Controller power terminals
Revision H 17
Section 2: Installing the controllers KMC Controls, Inc.

Maintenance

SimplyVAV controllers require no routine maintenance. If necessary, clean with a damp cloth and mild soap.
18 Revision H
Set
Point
72
12S1
Set
Point
PSW1
OOOO
SimplyVAV

Sec tion 3: Chan g i n g t h e r oom s et p oi nt

This section covers topics for the end user in a facility.
Changing the SimplyVAV user functions with an STE-8001 or STE-8201 are limited to changing the active setpoints in a room. The setpoints are entered or changed using the buttons and display on the front of the sensor.
Quick start to changing setpoints
1. Press any button to begin changing setpoints.
2. If required, enter Password 1.
Press the up or down buttons to change a
3. setpoint value.
Press the
4.
button to save the value or
advance to the next function.
To enter or change the active setpoints you may need Password 1.
Tip: Once the following procedure is started, all steps must be completed in order.
Changing room setpoints
Procedure Steps Sensor display
1 Starting display
2 Enter Password 1.
Start from the temperature display.
1. Press any button. The display changes to PSW1.
Revision H 19
Press the or buttons to change the first digit.
2.
Press the
3.
button to select the next digit. Repeat
for all four digits.
Note: If Password 1 has not previously been entered, the display will change to the occupied cooling setpoint display after Step 1.
Set
Point
745
COOLING
Set Point
685
HEATING
Section 3: Changing the room setpoint KMC Controls, Inc.
Changing room setpoints (continued)
Procedure Steps Sensor display
3 Set the active cooling setpoint.
4 Set the active heating setpoint.
Press the or buttons to change the cooling
1. setpoint temperature. The setpoint changes in increments of 0.5 degrees.
Press the
2.
button to save the value.
The display advances to set the heating setpoint.
Press the or buttons to change the heating
1. setpoint temperature. The setpoint changes in increments of 0.5 degrees.
Press the
2.
button to save the value.
The display returns to the temperature display.
20 Revision H
SimplyVAV

Sec tion 4: Configuring the cont roll er s

This topics in this section are advanced topics for control technicians and engineers.
The configuration functions that are accessible through an STE-8000 series digital sensor are all of the values and settings that are entered during the installation and commissioning of a VAV terminal unit. Typically, these functions do not change after the installation and commissioning process.
To set up the configuration functions, you will need the following items and information.
l Details about the VAV terminal unit including the configuration for fans and reheat.
l An STE-8001 orSTE-8201 digital sensor to use as a configuration tool.
l The building automation system plans for controllers connected to a network.
Users may change the active heating and cooling setpoints without accessing the configuration functions. This procedure is covered in the topic Changing the room
setpoint on page 19.
Note: The instructions for the configuration functions cover all of the functions that a digital
sensor can set up in the SimplyVAV series of controllers. Not all functions are available on every model of controller.
Configuration topics
Getting started with configuration 21 Entering system temperature setpoints and limits 23 Configuring the VAV Box options 27 Set the airflow setpoints 29 Advanced options 33 Restore Application 35

Getting started with configuration

For access to the configuration functions you will need the Password 2.
l If the controller has not been previously set up, no password is required.
l A new Password 2 can be entered or changed in the advance functions. See the topic
Advanced options on page 33.
Revision H 21
72
12S1
Set
Point
PSW2
OOOO
CNFG
Section 4: Configuring the controllers KMC Controls, Inc.
Enter the configuration mode
Procedure Detailed steps Sensor display
1 Starting display
2 Enter Password 2.
1. Start at the temperature display.
Press the and buttons together.
2.
l If Password 2 is not required, the display
changes to CNFG.
l If required, enter Password 2. The display
changes to CNFG when Password 2 is correct.
Press the and buttons together and hold them
1.
down until the display changes to PSW2.
Press the or button to change the first digit.
2.
Press the
3.
for all four digits.
4. When the button is pushed for the fourth correct digit,
the display changes to COMM.
button to select the next digit. Repeat
3 Select a configuration
function.
Note: If Password 2 has not previously been entered the display will change to the CNFG display after Step 1.
Access to the configuration functions always start at the
CNFG display.
22 Revision H
72
12S1
PSW2
OOOO
Set
Point
Set
Point
CNFG
STPT
MIN
68O
SimplyVAV Section 4: Configuring the controllers

Entering system temperature setpoints and limits

The system temperature setpoints set the operational parameters and limits for the VAV terminal unit.
The temperature setpoints include the following items.
l Minimum cooling and maximum heating setpoints
l Occupied and unoccupied cooling setpoints
l Occupied and unoccupied heating setpoints
l Changeover differential setpoint
l Standby differential setpoint
Setting the temperature setpoints requires entering Password 2 which is described in detail in the topic Getting started with configuration on page 21.
Tip: Once the following procedure is started, all steps must be completed in order.
Procedure to set the temperature setpoints
Procedure Detailed steps Sensor display
1 Start at the temperature
display.
1. Start at the temperature display.
Press the and buttons together.
2.
l If Password 2 is not required, the display
changes to CNFG.
l If required, enter Password 2. The display
changes to CNFG when Password 2 is correct.
2 Select the setpoint display.
From the CNFG display, press the or buttons to
1.
show STPT.
Press the
2.
button to select the CNFG options. The
display changes to STPT.
Press the
3.
button to select STPT. The display
changes to MIN.
3 Set the minimum cooling
Revision H 23
setpoint.
This setpoint limits the lowest temperature that a user can enter as the active setpoint.
Loading...
+ 52 hidden pages