NetSensor, WinControl, and the KMC logo are registered trademarks of KMC Controls, Inc.
AppStat, BACstage, FlexStat, FullBAC, KMC Connect, KMC Connect Lite, KMC Converge,
KMC Converge GFX, KMC Conquest, TotalControl, SimplyVAV, and the SimplyVAV logo are
trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may be reproduced, transmitted, transcribed,
stored in a retrieval system, or translated into any language in any form by any means
without the written permission of KMC Controls, Inc.
Printed in U.S.A.
The material in this manual is for information purposes only. The contents and the product it
describes are subject to change without notice. KMC Controls, Inc. makes no
representations or warranties with respect to this manual. In no event shall KMC Controls,
Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this
manual.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
U.S.A.
TEL: 1.574.831.5250
FAX: 1.574.831.5252
info@kmccontrols.com
2Revision H
SimplyVAVContents
C o n t e n t s
Contents3
Section 1: About the controllers5
Specifications6
Accessories and replacement parts9
Available models10
Safety considerations10
Section 2: Installing the controllers13
Setting the rotation limits13
Mounting on a VAV terminal box14
Connecting an airflow sensor15
Connecting inputs and outputs15
Connecting room temperature sensors15
Connecting a DAT sensor16
Connecting power17
Maintenance18
Section 3: Changing the room setpoint19
Section 4: Configuring the controllers21
Getting started with configuration21
Entering system temperature setpoints and limits23
Configuring the VAV Box options27
Set the airflow setpoints29
Advanced options33
Restore Application35
Section 5: Balancing airflow37
Section 6: Application drawings41
Cooling or heating without reheat42
Staged reheat43
Modulating reheat44
Time proportional reheat45
Floating reheat46
Dual-duct application47
Network bulbs64
Setting up network communications65
BACnet objects67
Input objects67
Output objects67
Value objects68
Loop objects70
Appendix A: K-factors71
Index73
4Revision H
SimplyVAV
Sec tion 1:About the cont roll er s
This section provides a description of the SimplyVAV series of controllers. It also
introduces safety information. Review this material before selecting, installing, or
operating the controllers.
The SimplyVAV series of controllers are an easy and unique approach to operating a wide
variety of VAV terminal units. The integrated actuators, internal airflow sensors, and wide
variety of application programs make these BACnet Application Specific controllers ideal for
either new or retrofit installations.
The controllers feature simple, menu driven setup choices when used with a SimplyVAV
digital sensor. No special programming skills or software tools are required to choose
applications, enter setpoints, set networkaddressing, and balance airflow. All options can
be set by using only an STE-8001 sensor which can be installed as the permanent room
sensor ortemporarily connected as a technician’s service tool.
All models are BACnet Application Specific Controllers that are ready to connect to a BACnet
MS/TP network. Device instance, MAC address, and baud rate are set from an STE-8001
sensor without special software.
BAC-8001Model BAC-8001 is supplied with inputs, outputs, and sequences of operation for
the following functions.
l Single duct heating and cooling VAV
l Automatic heating/cooling changeover including morning warmup
l Occupancy setback—requires STE-8201
l System diagnostic indicators
l Airflow balancing
BAC-8005 and BAC-8205 Models BAC-8005 and BAC-8205 are supplied with inputs,
outputs, and sequences of operation forthe following functions.
l Single duct heating and cooling VAV
l Modulating, floating, time proportional, and staged reheat
l Series and parallel fan control
l Automatic heating/cooling changeover including morning warmup
l Discharge air temperature limiting
l Occupancy setback—requires STE-8201
l Actuator position feedback fortrue damper positioning (BAC-8205 only)
l System diagnostic indicators
l Airflow balancing
Revision H5
Section 1: About the controllersKMC Controls, Inc.
BAC-8007Model BAC-8007 is supplied with inputs, outputs, and sequences of operation for
the following functions.
l Dual-duct VAV heating and cooling
l Occupancy setback—requires STE-8201
l System diagnostic indicators
l Airflow balancing
Additional topics in this section
Specifications6
Accessories and replacement parts9
Available models10
Safety considerations10
Specifications
SimplyVAV controller specifications are subject to change without notice.
Inputs and outputs
All inputs and outputs are factory programmed and application specific. No field
configuration is required. For details on input and output connections, see the topic
Application drawings on page 41. For a detailed listing of input and output objects, see the
topic BACnet objects on page 67.
Analog inputs
Analog inputs represent BACnet analog input. Not all input are applicable or required for all
models.
Key featuresStandard units of measure.
Overvoltage input protection
ConnectorsRJ-45 room sensor jack
Screw terminals for wire sizes 12-26 AWG
Conversion12–bit analog–to–digital conversion
Input rangePassive, 10 kΩ pull-up to 3.3 volts DC
Analog outputs
Analog outputs are configured to represent BACnet analog output objects. No field
configuration is required. For details on application specific outputconnections see the
section Application drawingson page 41.
Key featuresOutput short protection
Standard units of measure
ConnectorScrew terminals for wire size 12-26AWG
Conversion12–bit digital-to-analog conversion
Output voltage0–10 VDC
Output current30 mA per output, 30 mA total for all analog outputs
6Revision H
SimplyVAVSection 1: About the controllers
Binary outputs
Binary outputs are configured to represent BACnet binary output objects. No field
configuration is required. For details on application specific outputconnections see the
section Application drawingson page 41.
Key featuresOptically isolated triac output
ConnectorScrew terminals for wire size 12-26AWG
Output rangeMaximum switching 24 Volts AC
1 ampere per external output, 3 amperes total
Communications—BACnet MS/TP
l EIA–485 operating at rates up to 76.8 kilobaud.
l Removable screw terminal block.
l Wire size 12-26AWG
l Switch selected end of line termination
Memory
l Programs and program parameters are stored in nonvolatile memory.
l Auto restart on power failure
Air flow sensor features
l Configured as BACnet analog inputobject.
l CMOS differential pressure 0-2 inches of water (0-500 Pa) measurement range.
Internally linearized and temperature compensated.
l Span accuracy 4.5% of reading.
l Zero point accuracy 0.0008 in. H2O/0.2 Pa at 25° C
l Barbed connections for 1/4 inch FR tubing.
Actuator specifications
Torque40 in-lb. (4.5 N•m)
Angular rotation0 to 95°
Adjustable end stops at 45° and 60° rotation
Motor timing
BAC-8001, BAC-8005,
BAC-8007
Motor timing
BAC-8205
Shaft sizeDirectly mounts on 3/8 to 5/8inch (9.5to16mm) round or 3/8
90 sec./90° at 60 Hz
108 sec./90° at 50 Hz
60 sec./90° at 60 Hz
to 7/16 inch (9.5to11 mm) square damper shafts.
Revision H7
Section 1: About the controllersKMC Controls, Inc.
Regulatory
l UL 916 Energy Management Equipment
l BACnet Testing Laboratory listed as an application specific controller (ASC).
l CE compliant
l FCC Class B, Part 15, Subpart B and complies with Canadian ICES-003 Class B
This device complies with part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may
cause undesired operation.
Installation
Supply voltage24 volts AC, -15%, +20% 5 VA,
Weight13.2ounces (376 grams)
Case materialFlame retardant plastic
Environmental limits
Operating32 to 120° F (0 to 49° C)
Shipping–40 to 140° F (–40 to 60° C)
Humidity5–93% relative humidity (non-condensing)
50/60 Hz
8Revision H
ON CTS
1 2
1.92 in.
49 mm
6.53 in.
166 mm
4.89 in.
124 mm
4.25 in.
108 mm
0.77 in.
19 mm
6.00 in.
152 mm
2.14 in.
54 mm
SimplyVAVSection 1: About the controllers
Dimensions
Accessories and replacement parts
The following accessories and replacement parts are available from KMC Controls, Inc.
Power transformer
XEE-6111-50Transformer, 120-to-24VAC, 50 VA, single-hub
XEE-6112-50Transformer, 120-to-24VAC, 50 VA, dual-hub
XEE-6311-100Transformer, 120, 277 -to-24 VAC, 50/60 Hz, 96 VA, dual-hub
Sensors
STE-8001W80SimplyVAV sensor and digital display
STE-8201W80SimplyVAV sensor and digital display with motion sensor
STE-6010W80Discrete temperature sensor with RJ-45 connector
STE-6014W80Discrete temperature sensor with rotary setpoint dial, RJ-45
STE-6017W80Discrete temperature sensor with rotary setpoint dial, override
HPO-9005Room Sensor Adapter
connector
button, RJ-45 connector
Revision H9
Section 1: About the controllersKMC Controls, Inc.
Sensor cables
HSO-9001Cable: Ethernet, 50 foot
HSO-9011Cable: Ethernet, 50 foot, Plenum Rated
Surge suppressors
KMD-5567EIA-485 surge suppressor for MS/TPnetworks
Replacement parts
HPO-0054Replacement bulbs
HPO-0063Replacement two-pin jumper
Dual duct actuator
TSP-8001VAV actuator with airflow inputs (required for dual duct)
Airflow sensors
For VAV terminal units withoutairflow pickup tubes, order one of the following sensors.
SSS-10123-5/32 in. length (80 mm)
SSS-10135-13/32 in. length (137 mm)
SSS-10147-21-32 in. length (195 mm)
SSS-10159-29/32 in. length (252 mm)
KIT-8001A 3-5/32 inch sensor and 3 feet of FR tubing
Available models
The following is a list of SimplyVAV available models.
BACnet ASC: VAV Fan and Reheat, True damper position, 40 in-lbs, 60
second actuator
BAC-8205
Safety considerations
KMC Controls assumes the responsibility for providing you a safe product and safety
guidelines during its use. Safety means protection to all individuals who install, operate, and
service the equipment as well as protection of the equipment itself. To promote safety, we
use hazard alert labeling in this manual. Follow the associated guidelines to avoid hazards.
10Revision H
Danger
Warning
Caution
SimplyVAVSection 1: About the controllers
Danger represents the most severe hazard alert.
Bodily harm or death will occur if danger guidelines
are not followed.
Warning represents hazards that could result in
severe injury or death.
Caution indicates potential personal injury or
equipment or property damage if instructions are not
followed.
Note:Notes provide additional information that is important.
Tip:Provides programing tips and shortcuts that may save time.
Revision H11
Section 1: About the controllersKMC Controls, Inc.
12Revision H
Caution
45
60
Position notch
as shown
Stop position
holes
Stop screw in
storage
Rotate CW
SimplyVAV
Sec tion 2:Instal l ing the controllers
This section provides important instructions and guidelines for installing the SimplyVAV
controllers. Carefully review this information before installing the controller.
Installing SimplyVAV includes the following topics that are covered in this section.
Installation topics in this section
Setting the rotation limits13
Mounting on a VAV terminal box14
Connecting an airflow sensor15
Connecting inputs and outputs15
Connecting room temperature sensors15
Connecting a DAT sensor16
Connecting power17
Maintenance18
Setting the rotation limits
SimplyVAV controllers are manufactured for a damper that rotates 90 degrees from open to
close. If the VAV damper is not a 90 degree damper, set the rotation limits to 45 or 60
degrees before mounting the controller.
Before setting the rotation limits on the controller, refer to the
damper position specifications in the VAV control box to which
the controller will be attached. Setting rotation limits that do not
match the VAV damper may result in improper operation or
equipment damage.
Revision H13
ON CTS
1 2
COMM
READY
AI1
AI5
GND
AO4
AO3
SC
BO8
BO5
BO6
SC
BO7
24VAC
AI6
GND
AI7
T-STAT/
SENSOR
-A
+B
S
EOL
BACnet MS/TP
Status LEDs
Mounting
tab
Mounting
bushing
Gear clutch button
Drive hub
and V-bolt
Section 2: Installing the controllersKMC Controls, Inc.
To set the rotational limits, do the following
1Turn the controller over so you have access to the back.
2Manually rotate the actuator fully clockwise as viewed from the back.
3Remove the stop screw from its storage location and clean any debris from the
threads.
4Insert the screw into the correct stop position hole.
5Tighten the screw only until the head touches the plastic in the bottom of the recess.
Mounting on a VAV terminal box
Mount the controller inside of a metal enclosure. To maintain RF emissions specifications,
use either shielded connecting cables or enclose all cables in conduit.
Mount the controller directly over the damper shaft. A minimum shaft length of 2.0 inch
(51mm) is required.
Note:SimplyVAV controllers are designed to directly mount to 3/8 to 5/8inch (9.5to16mm)
round or 3/8 to 7/16 inch (9.5to11 mm) square damper shafts.
Illustration 2–2 Controls and indicators
Mount the controller as follows:
1Manually rotate the damper on the VAV box to the fully open position.
2On the controller, press the gear clutch button and rotate the drive hub in the same
direction that opened the damper. Turn the hub until it reaches a rotation limit.
3Loosen the nuts on the V-bolt until the damper shaft can fit through the collar.
4Place the controller over the damper shaft.
5Finger tighten the nuts on the V-bolt to position the shaft in the drive hub.
6Center the mounting bushing in the mounting tab and fasten it with a #8 sheet metal
screw.
14Revision H
7Evenly tighten the V-bolt nuts on the drive hub to 30-35 in-lbs.
ON CTS
1 2
COMM
READY
24VAC
T-STAT/
SENSOR
-A
+B
S
EOL
BACnet MS/TP
Total airflow (high) Static airflow (low)
SimplyVAVSection 2: Installing the controllers
Connecting an airflow sensor
An airflow sensor is incorporated as one of the inputs to the controller. Remove the plugs
and connect the tubing from the pitot assembly to the airflow sensor inputs next to the drive
hub.
Illustration 2–3 Airflow sensor inputs
Typically, airflow sensors are supplied by the manufacturer as part of the VAV terminal unit.
If a sensor is needed, choose a sensor listed in the topic Accessories and replacement
parts on page 9.
Connecting inputs and outputs
SimplyVAV series controllers have preconfigured inputs and outputs to support only the
supplied programs and applications.
l For input and output connection information, see the topic Application drawingson
page 41.
l To connect room temperature sensors, see the topic Connecting room
temperature sensors on page 15
l To connect a DAT sensor, see the topic Connecting a DAT sensor on page 16.
l For the BACnet object descriptions of the inputs and outputs, see the topic BACnet
objects on page 67.
Connecting room temperature sensors
Connect any of the following sensors to the RJ-45 thermostat and sensor jack. The
controller automatically detects the type of sensor. No programming or configuration is
required.
Revision H15
l STE-6010W80
l STE-6014W80
l STE-6017W80
l STE-8001W80
l STE-8201W80
Ethernet cable
Maximum 75 feet
DAT sensor
Prefered location
DAT sensor
Changeover only
Section 2: Installing the controllersKMC Controls, Inc.
Connect the controller to sensors with standard Ethernet cables up to 75 feet long. See the
installation guide supplied with the sensors for sensor installation instructions.
Illustration 2–4 Connecting to a sensor
Connecting a DAT sensor
The Discharge Air Temperature sensor is required forautomatic changeover and for VAV
terminal units with reheat.
Illustration 2–5 Discharge air temperature sensor location
16Revision H
T
COMM
READY
AI1
GND
AO4
AO3
Blue
Brown
24 VAC
Class 2
ON CTS
1 2
COMM
READY
AI1
AI5
GND
AO4
AO3
SC
BO8
BO5
BO6
SC
BO7
24VAC
AI6
GND
AI7
T-STAT/
SENSOR
-A
+B
S
EOL
BACnet MS/TP
SimplyVAVSection 2: Installing the controllers
Connect a 10 kΩ, Type 3 thermistor temperature probe to the discharge air temperature
input. The input includes the internal pull-up resistor. An STE-1401 sensor is suitable for this
application. Follow the instructions supplied with the sensor for installation.
l For DAT limiting and reheat, install the sensor in the airflow after the reheat unit. See
the topic, Advanced options on page 33 to enable discharge air temperature control.
l When the DAT sensor is used only to detect primary air temperature, the sensor can be
placed in either location shown in the illustration Discharge air temperature
sensor location.
Illustration 2–6 Discharge air temperature input details
Connecting power
The controllers require a 24 volt, AC power source. Use the following guidelines when
choosing and wiring transformers to the controller.
l Use a Class–2 transformer of the appropriate size to supply power to the controller.
l KMC Controls recommends powering only one controller from each transformer.
l Do not run 24 volt, AC power from within an enclosure to external controllers.
Connect the 24 volt AC power supply to the power terminal block on the lower right side of
the controller. Connect the ground side of the transformer to the ground terminaland the
AC phase to the phaseterminal. Power is applied to the controller when the transformer is
connected to power.
Illustration 2–7 Controller power terminals
Revision H17
Section 2: Installing the controllersKMC Controls, Inc.
Maintenance
SimplyVAV controllers require no routine maintenance. If necessary, clean with a damp cloth
and mild soap.
18Revision H
Set
Point
72
12S1
Set
Point
PSW1
OOOO
SimplyVAV
Sec tion 3:Chan g i n g t h e r oom s et p oi nt
This section covers topics for the end user in a facility.
Changing the SimplyVAV user functions with an STE-8001 or STE-8201 are limited to
changing the active setpoints in a room. The setpoints are entered or changed using the
buttons and display on the front of the sensor.
Quick start to changing setpoints
1. Press any button to begin changing setpoints.
2. If required, enter Password 1.
Press the upor downbuttons to change a
3.
setpoint value.
Press the
4.
button to save the value or
advance to the next function.
To enter or change the active setpoints you may need Password 1.
Tip:Once the following procedure is started, all steps must be completed in order.
Changing room setpoints
ProcedureStepsSensor display
1 Starting display
2 Enter Password 1.
Start from the temperature display.
1. Press any button. The display changes to PSW1.
Revision H19
Press theorbuttons to change the first digit.
2.
Press the
3.
button to select the next digit. Repeat
for all four digits.
Note: If Password 1 has not previously been entered,
the display will change to the occupied cooling
setpoint display after Step 1.
Set
Point
745
COOLING
Set
Point
685
HEATING
Section 3: Changing the room setpointKMC Controls, Inc.
Changing room setpoints (continued)
ProcedureStepsSensor display
3 Set the active cooling setpoint.
4 Set the active heating setpoint.
Press theorbuttons to change the cooling
1.
setpoint temperature. The setpoint changes in
increments of 0.5 degrees.
Press the
2.
button to save the value.
The display advances to set the heating setpoint.
Press theorbuttons to change the heating
1.
setpoint temperature. The setpoint changes in
increments of 0.5 degrees.
Press the
2.
button to save the value.
The display returns to the temperature display.
20Revision H
SimplyVAV
Sec tion 4:Configuring the cont roll er s
This topics in this section are advanced topics for control technicians and engineers.
The configuration functions that are accessible through an STE-8000 series digital sensor
are all of the values and settings that are entered during the installation and commissioning
of a VAV terminal unit. Typically, these functions do not change after the installation and
commissioning process.
To set up the configuration functions, you will need the following items and information.
l Details about the VAV terminal unit including the configuration for fans and reheat.
l An STE-8001 orSTE-8201 digital sensor to use as a configuration tool.
l The building automation system plans for controllers connected to a network.
Users may change the active heating and cooling setpoints without accessing the
configuration functions. This procedure is covered in the topic Changing the room
setpoint on page 19.
Note:The instructions for the configuration functions cover all of the functions that a digital
sensor can set up in the SimplyVAV series of controllers. Not all functions are available on
every model of controller.
Configuration topics
Getting started with configuration21
Entering system temperature setpoints and limits23
Configuring the VAV Box options27
Set the airflow setpoints29
Advanced options33
Restore Application35
Getting started with configuration
For access to the configuration functions you will need the Password 2.
l If the controller has not been previously set up, no password is required.
l A new Password 2 can be entered or changed in the advance functions. See the topic
Advanced options on page 33.
Revision H21
72
12S1
Set
Point
PSW2
OOOO
CNFG
Section 4: Configuring the controllersKMC Controls, Inc.
Enter the configuration mode
ProcedureDetailed stepsSensor display
1 Starting display
2 Enter Password 2.
1. Start at the temperature display.
Press theandbuttons together.
2.
l If Password 2 is not required, the display
changes to CNFG.
l If required, enter Password 2. The display
changes to CNFG when Password 2 is correct.
Press theandbuttons together and hold them
1.
down until the display changes to PSW2.
Press theorbutton to change the first digit.
2.
Press the
3.
for all four digits.
4. When the button is pushed for the fourth correct digit,
the display changes to COMM.
button to select the next digit. Repeat
3 Select a configuration
function.
Note: If Password 2 has not previously been entered
the display will change to the CNFG display after
Step 1.
Access to the configuration functions always start at the
CNFG display.
22Revision H
72
12S1
PSW2
OOOO
Set
Point
Set
Point
CNFG
STPT
MIN
68O
SimplyVAVSection 4: Configuring the controllers
Entering system temperature setpoints and limits
The system temperature setpoints set the operational parameters and limits for the VAV
terminal unit.
The temperature setpoints include the following items.
l Minimum cooling and maximum heating setpoints
l Occupied and unoccupied cooling setpoints
l Occupied and unoccupied heating setpoints
l Changeover differential setpoint
l Standby differential setpoint
Setting the temperature setpoints requires entering Password 2 which is described in detail
in the topic Getting started with configuration on page 21.
Tip:Once the following procedure is started, all steps must be completed in order.
Procedure to set the temperature setpoints
ProcedureDetailed stepsSensor display
1 Start at the temperature
display.
1. Start at the temperature display.
Press theandbuttons together.
2.
l If Password 2 is not required, the display
changes to CNFG.
l If required, enter Password 2. The display
changes to CNFG when Password 2 is correct.
2 Select the setpoint display.
From the CNFG display, press theorbuttons to
1.
show STPT.
Press the
2.
button to select the CNFG options. The
display changes to STPT.
Press the
3.
button to select STPT. The display
changes to MIN.
3 Set the minimum cooling
Revision H23
setpoint.
This setpoint limits the lowest temperature that a user
can enter as the active setpoint.
Loading...
+ 52 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.