KMC Controls REE-2104 User Manual

Mounting

Solid-State Triac Relays (5 A)
REE-2103/2104
Installation Guide
The (one-output) REE-2104 and (discontinued, four-output) REE-2103 solid-state relays (with zero-crossing AC switching) may be mounted in any position.
To mount:
1. Carefully remove the circuit board from the Snap Track.
2 (51)
1-1/2
(38)
3-3/8
(86)
Dimensions in Inches (mm)
CAUTION
Do NOT bend or flex the circuit board.
2 Mount the Snap Track in the desired location.
3. Replace the circuit board on the track.
4 (102)
1-1/2
(38)
Snap Track (Supplied)
REE-2104

Maintenance

More Information

REE-2103
No routine maintenance is required. Each component is designed for dependable, long-term reliability, and performance. Careful installation will also ensure long-term reliability and performance.
NOTE: For specications
and other information, see
the REE-2104 Data
Sheet.
REE-2103/2104 Solid-State Triac Relays Installation Guide

Connections and Wiring

*
1. Remove and save the AUTO-MANUAL-OFF jumper.
2. Wire the input(s) common ground to “GND” of the INPUT terminal block.
3. Wire the individual (6–40 VDC or 24 VAC) input(s) to the appropriate terminal(s) of the INPUT block.
*NOTE: Puingthejumperintothe“MANUAL”
position turns on the triac relay (when no triggering voltage is present on the input). If “MANUAL” mode is to be used, wire power (+ 6–40 VDC or 24 VAC) to the “POWER” terminal of the INPUT terminal block. This must have the same reference (–) ground as the inputs.
4. Wire the individual output(s) to the appropriate terminals of the OUTPUT terminal block.
NOTE: Triacs are for switching AC only. Output
rating is up to 5 A at 280 VAC. See the data
sheetforadditionalspecications.
5. The triac output must be in series with the load and transformer output.
*NOTE: The jack on the board for a plug-in
transformer was discontinued on units built after May 2013. Connect auxiliary (manual override) power to the Power and Ground terminals instead. If an older unit that uses a plug-in transformer is being replaced,
cuttheplugothetransformercableand
connect the wires to the Power (+) and Ground (–) terminals.

Important Notices

The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice. KMC makes no representations or warranties with respect to this document. In no event shall KMC be liable for any damages, direct or incidental, arising out of or related to the use of this document.
6. Replace the jumper to the “AUTO” position.
© 2014 KMC Controls, Inc. 872-019-01E
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com