Mounting
Solid-State Triac Relays (5 A)
REE-2103/2104
Installation Guide
The (one-output) REE-2104 and (discontinued,
four-output) REE-2103 solid-state relays (with
zero-crossing AC switching) may be mounted in any
position.
To mount:
1. Carefully remove the circuit board from the Snap
Track.
2 (51)
1-1/2
(38)
3-3/8
(86)
Dimensions in Inches (mm)
CAUTION
Do NOT bend or flex the circuit board.
2 Mount the Snap Track in the desired location.
3. Replace the circuit board on the track.
4 (102)
1-1/2
(38)
Snap Track (Supplied)
REE-2104
Maintenance
More Information
REE-2103
No routine maintenance is required. Each component
is designed for dependable, long-term reliability, and
performance. Careful installation will also ensure
long-term reliability and performance.
NOTE: For specications
and other
information, see
the REE-2104 Data
Sheet.
REE-2103/2104 Solid-State Triac Relays Installation Guide
Connections and Wiring
*
1. Remove and save the AUTO-MANUAL-OFF
jumper.
2. Wire the input(s) common ground to “GND” of
the INPUT terminal block.
3. Wire the individual (6–40 VDC or 24 VAC)
input(s) to the appropriate terminal(s) of the
INPUT block.
*NOTE: Puingthejumperintothe“MANUAL”
position turns on the triac relay (when no
triggering voltage is present on the input).
If “MANUAL” mode is to be used, wire
power (+ 6–40 VDC or 24 VAC) to the
“POWER” terminal of the INPUT terminal
block. This must have the same reference
(–) ground as the inputs.
4. Wire the individual output(s) to the appropriate
terminals of the OUTPUT terminal block.
NOTE: Triacs are for switching AC only. Output
rating is up to 5 A at 280 VAC. See the data
sheetforadditionalspecications.
5. The triac output must be in series with the load
and transformer output.
*NOTE: The jack on the board for a plug-in
transformer was discontinued on units built
after May 2013. Connect auxiliary (manual
override) power to the Power and Ground
terminals instead. If an older unit that uses
a plug-in transformer is being replaced,
cuttheplugothetransformercableand
connect the wires to the Power (+) and
Ground (–) terminals.
Important Notices
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice. KMC
makes no representations or warranties with respect
to this document. In no event shall KMC be liable for
any damages, direct or incidental, arising out of or
related to the use of this document.
6. Replace the jumper to the “AUTO” position.