KMC Controls REE-2005 User Manual

Installation Guide
Mounting
• The REE-2005 may be mounted directly to a
control box surface or in a 2" x 4" electrical handy box.
Voltage to Current Converter Module
REE-2005
Connections and Wiring
• Wire the module as illustrated.
• Supply the unit with either 24 VAC or 22–40 VDC. (See the note about maximum receiver loads for AC vs. DC power.)
• See the graph for output over a 0–10 VDC input range.
Maintenance
No routine maintenance is required. Each compo­nent is designed for dependable, long-term reliabil­ity, and performance. Careful installation will also ensure long-term reliability and performance.
*NOTE: If the unit is powered by 24 VAC, the
maximum receiver load is 650 ohms.
If the unit is powered by 22 to 40 VDC, the maximum receiver load in ohms is
determined by the formula:
(VDC – 13.1)
0.0184
KMC Controls, Inc.
19476 Industrial Drive, PO Box 497
New Paris, IN 46553
574.831.5250
www.kmccontrols.com; info@kmccontrols.com
© 2011 KMC Controls, Inc. 884-019-01G