Installation Guide
Mounting
The REE-1005 can be mounted directly to a control
box surface or in a 2 x 4" electrical handy box. To
conceal the module, add a blank cover.
Heat/Cool Changeover Relay Module
REE-1005
Connections and Wiring
Wire as shown in the examples for single duct heating/cooling changeover using one box to supply hot
or cold air to the space.
The factory setpoint is 77° F (25° C).
Terminal A is an optional auxiliary ow limit trigger signal (usually connected to Terminal A on a
CTE-1004, CTE-5104, or REE-1012). When the relay
module senses heating mode, terminal A goes high
(around 6.8 VDC with a 9.1 VDC supply or 13.8 VDC
with a 16 VDC supply). This terminal can also be
used to daisy chain more than one REE-1005 together
by wiring Terminal “A” to Terminal “Y” on the next
relay.
NOTE: See the CEP-4000 Series Applications
Guide and the CSP-5001/5002 Applications
Guide for additional information on
applications.
REE-1005 1 Installation Guide
Maintenance
Important Notices
No routine maintenance is required, however protection from extremes of humidity and dirt is recommended. Careful installation will also ensure long
term reliability and performance.
© 2013 KMC Controls, Inc. 811-019-01G
REE-1005 2 Installation Guide
The material in this document is for information
purposes only. The contents and the product it
describes are subject to change without notice.
KMC Controls, Inc. makes no representations or
warranties with respect to this document. In no event
shall KMC Controls, Inc. be liable for any damages,
direct or incidental, arising out of or related to the
use of this document.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com