Required Tools
• digital voltmeter
• small phillips screwdriver
• small flatblade screwdriver
• 5/16" Allen wrench
Mounting
1. Set the MEP–1500 in the desired location.
2. Slide the MEP–1500 unit directly on to the standard 1/2" diameter (13 mm) damper shaft. See below for adaptor directions.
Rotary Electric Actuator
MEP–1500 Series
MEP–1500
Side View
4. Place the non-rotation bracket (supplied) on the non-rotation tab.
5. Attach the anti-rotation bracket to the mounting surface using #8 or #10 self tapping screws (not included)
How to use the HFO-0011 Adaptor
1. Mount the MEP–1500 actuator over the 3/8 " shaft
2. Slide the HFO-0011 over the shaft into the drive bushing of the actuator.
3. Align the adaptor slots with the set screws
4. Tighten the set screws.
Wiring
• Wire to “CW”, “CCW” and COM terminals as appropriate.
DO NOT remove motor leads from terminals and wire directly to the motor.
DO NOT connect power directly to motor unless a terminal strip is used.
HFO-0011 Adaptor
MEP–1500: Wiring Detail
Maintenance
No routine maintenance is required. The motors are permanently lubricated and all internal gear-train component are oil-impregnated. Careful installation will also ensure long term reliability and performance.