KMC Controls KMD-5831 Installation & Operation Manual

Page 1
Installation & Operation Guide
(Shown with optional Override Board Cover)
KMD-5831
Programmable Loop Controller PLC-28 Direct Digital Controller
902-019-04B
1
Page 2
Introduction
For clarity we will focus on the KMD-5831 but all installation and operating instructions apply equally to the KMD-5821.
Illustration 1 shows the major controller components and their locations. The KMD-5821has fewer inputs and outputs.
Override
Board
Cover
Input Pull-Up
Switches
Input Terminal
Blocks
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O
A
1
O
A
2
O
A
3
O
A
4
O
A
5
O
A
6
O
A
7
O
A
8
Output Terminal
Blocks
Grounds
AC Power
Blank Cover
Input
RJ–12
Connector
Isolation
Lamps
RS–485
Connector
Status LEDs
Illustration 1. Controller Components
Note:
Additional components are located under the blank cover. We will cover these in detail later in this document.
2
Page 3
Installation
Mounting
This section provides important instructions and guidelines for installing the KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller. Carefully review this information prior to attempting installation.
Use the four mounting holes to securely mount the controller using #6 hardware inside a UL-approved Enclosed Energy Management Equipment Panel or other suitable protective enclosure. Refer to Illustration 2.
O-RSTATUSH
O
A
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
1
O
A
2
O
A
3
O
A
4
O
A
5
O
A
6
O
A
7
O
A
8
6.00"
Input Connections
Universal Inputs
Wiring connections are made depending on the intended application. Sixteen Universal Inputs are provided on the controller. Observe the following guide­lines. (Refer to Illustration 2.)
Connect device inputs to the input terminal connections (+).
Connect input grounds to the associated ground terminal (-).
6.00"
Illustration 2. Connector Detail
3
Page 4
Installation KMD-5831 PLC-28 Direct Digital Controller Installation & Operation Guide
If input pull-ups are required, refer to “Configuration” later in this section.
Wiring terminals are suitable for up to two 12–22 AWG wires. If more than
two wires are required, use an external terminal strip for additional connec­tions.
Note:
Pulse inputs may be used under the following conditions:
If the pulse input does not use a voltage variation, then leave the input pull-up
in the “On” position.
If the pulse produces voltage peaks (up to +5 VDC max.), then the input pull-
up must be set to the “Off” position.
The maximum pulse rate is 8 HZ (8 pulse/sec).
Connecting Outputs
Twelve Universal Outputs are available for output connections labeled as 1–12 on the output terminal blocks. The outputs are grouped into three groups of four outputs each with a shared grounds (labeled “SC”) in each block.. Each output can produce 50 mA at +12 VDC. If a greater current is required, KMC recom­mends the use of Override Boards discussed later in this section.
A separate ground block provides six additional ground connections.
Network Connections
The controller provides connections for two types of RS–485 circuits.
RJ-12
The RJ–12 connector provides a six-wire RS-485 connection to a modem or PC using the KMD-5559 CommTalk Data Exchange Module. Simply connect a suitable RJ-12 cable between the devices.
RS-485 Inputs
A RS–485 terminal is available for connections to a network of controllers If the Controller is at the End-of-Line, refer to “Configuration” after connections are completed.
Detail
The End-of-Line connection will have only one wire attached to the A and B terminals.
For reliable operation, use Belden cable model #82760 or equivalent (18 gauge,
twisted, shielded, 50 picofarads or less) for all network terminal block connec­tions.
Connect the nodes of the network in a daisy-chain arrangement. This means:
Connect the A terminal in parallel with all other A terminals.
Connect the B terminal in parallel with all other B terminals.
Connect the shields of the cable together at each controller.
4
Page 5
KMD-5831 PLC-28 Direct Digital Controller Installation & Operation Guide Installation
r
Connect the shields to an earth ground (DO NOT use a chassis ground) only at
one end of the segment; tape back the shield ground at the other end.
Wiring Notes
Use approved shielded cable and the following principles when connecting a controller to a network:
Connect no more than 124 Tier 2 KMC addressable controllers or devices to
the RS-485 network.
Connect the nodes of the network in a daisy-chain arrangement. This means:
Connect the A terminal in parallel with all other A terminals.
Connect the B terminal in parallel with all other B terminals.
Connect the shields of the cable together at each controller.
Connect the shields to an earth ground at only one end of the segment; tape
back the shield ground at the other end.
Use a KMD–5575 repeater between every 32 Tier 2 controllers or if the cable
length of the Tier 2 network exceeds 4000 feet (1220 meters). Use no more than seven repeaters per network.
Place a KMD–5567 surge suppressor in the cable where it exits a building.
Refer to Illustration 3 for an example of typical RS-485 connections.
Wiring
Shield
Wiring
Shield
Wiring
Shield
OR
KMC Controlle
Connections
Illustration 3. Typical RS-485 Wiring Configuration
5
Page 6
Installation KMD-5831 PLC-28 Direct Digital Controller Installation & Operation Guide
Override Cards
For large relays or devices that cannot be powered directly from a standard output, you will need to install an output override card. Override cards provide:
a wide choice of output signals.
a slide switch for automatic or manual control.
an LED for assessment of the output state.
The following Override Cards are available from KMC Controls.
rebmuNledoM epyTtuptuO
1076-OPH
2076-OPH
3076-OPH
4076-OPH
5076-OPH
Table 1. KMD-5831 Override Board Options
Note
Output cards must be powered with 24 VAC to enable the manual override (HAND) function. However, this connection must not be made until the default analog output jumper is removed.
Installing Override Boards
To install an Override Board:
.sselro
pmA1fosegatlovCAgnihctiwsrofdesu-yaleRcairT
gniriuqersnoitacilpparofdesU-edirrevOgolanA
.ecivedlortnocgolananafotnemtsujdalaunam
sdaolhctiwsotdesu-)AmroF(yaleRlacinahceM.O.N
anehwrostiucricCDgnihctiwsnehw,spmA2otpufo
FFOebtsumecivedehtdnaderiuqersitcatnocyrd
.devomersirewopnehw
launamgniriuqersnoitacilpparofdesu-Am02-4
.ecivedlortnocgolananafotnemtsujda
sdaolhctiwsotdesu-)AmroF(yaleRlacinahceM.C.N
anehwrostiucricCDgnihctiwsnehw,spmA2otpufo
nehwNOebtsumecivedehtdnaderiuqersitcatnocyrd
.devomersirewop
1. Remove the appropriate cover from the module. The upper cover is for out­puts 1–8 the lower for outputs 9–12.
2. Remove the jumper from the mounting header.
3. Press the override board onto the header pins. The “Hand-Off-Auto” selection switch is always positioned toward the output connections. (Refer to Illustra­tion 4.)
4. If required, set the selection switch on the Override Board.
6
Page 7
KMD-5831 PLC-28 Direct Digital Controller Installation & Operation Guide Installation
Caution
DO NOT connect active 24 VAC circuits to the output block unless the associ­ated jumper is removed first. Doing so will result in damage to the output and prevent it from working.
If the associated output will be an analog output, leave the jumper in place.
5. Connect output devices to the module.
6. Connect required power to the input module.
Illustration 4 gives an example of a typical output module configuration.
LED
Illustration 4. Override Board Instalaltion
Selection Switch
Remove jumper
before installing
board
OR
Remove jumper
prior to connecting
active 24 VAC circuits
to the associated
output terminals
Configuration
Using Separate Banks
The outputs are grouped into three banks that share a common switched-termi­nal. This connection is marked as “SC” on the output block. If you connect a circuit to this connector it then becomes common to all outputs in that bank.
Configuration settings may be required for the inputs or the RS-485 connection. If you must activate or deactivate pull-ups on the inputs or set the end-of-line termination for the RS-485 connection, refer to Illustration 1 to locate the input switches and Illustration 6 for the End-of-Line switches.
7
Page 8
Installation KMD-5831 PLC-28 Direct Digital Controller Installation & Operation Guide
Input Pull-ups
A 10K ohm resistor is available as a pull-up to a +5 VDC source voltage for passive or ‘dry” inputs on each input circuit. The resistor is switched “On” or “Off” using the two dip-switches at the top of the controller. The top switch is associated with the first 8 inputs and the lower switch is associated with the last 8 inputs. Illustration 5 shows on of these switches in greater detail.
OFF ON
OFF ON
Illustration 5. Typical Input Pull-Up Switch (1 of 2)
The default setting for each input is the “On” position. In this position, the controller will provide +5 VDC to the input device.
If the input is an active input, that is it has it’s own current source, the pull-up for that input must be switched to the “Off” position.
End-of-Line Switches
Illustration 6 shows the position of the End-of-Line switches associated with the RS–485 terminal. You must remove the lower blank cover to gain access to these switches
End-of-Line Switches
Illustration 6. RS–485 End-of-Line Switches
8
Page 9
KMD-5831 PLC-28 Direct Digital Controller Installation & Operation Guide Installation
Illustration 7 shows the switch in greater detail
ON
ON OFF
OFF
Illustration 7. RS-485 End-of-Line Switch Detail
If the controller is located at the end of the network segment the switches must both be placed in the default “ON” position. Otherwise, place the switches in the “OFF” position.
Power Connection
Connect the 24 VAC supply voltage to the power connectors above the RJ–11 connector on the output side of the controller. Power is applied to the controller when the power supply (or transformer) is plugged in, as long as the Power jumper is in place. Illustration 6 shows a typical connection diagram for the controller.
Configuration
Programming
Note:
The following guidelines apply.
In general, use a separate Class 2 24 VAC transformer with the smallest VA
rating that matches the specification.
If several controllers are mounted in the same cabinet, you can share a trans-
former between them PROVIDED the transformer does not exceed 100 VA
Prior to operating the controller, it must be configured using the Hardware Configuration Manager (HCM) application supplied with WinControl. Refer to the WinControl XL User’s Manual for additional information.
Note:
All controllers on the same network must be configured for the same baud rate.
Refer to the KMC Digital Applications Manual for information on how to pro­gram the controller.
9
Page 10
Operation
Once configured, programmed and powered up, the controller requires very little user intervention.
Controls and Indicators
The following sections describe the controls and indicators found on the card.
Alternately, you may remove the RS-485 terminal block from the card to isolate the card from the network without disrupting network communications to other controllers.
Status LEDs
Two Status LEDs are located on the bottom left side of the controller. They are used to indicate the following:
Communications – This yellow LED flashes whenever the controller is commu­nicating with other controllers over the RS-485 network connection.
Ready– This green LED indicates the controller has power and is operating normally. The LED will flash on and off at one second intervals.
Isolation Lamps
Two Isolation Lamps are located below the RJ–12 connector on the right side of the controller. These lamps serve three functions:
Removing the lamps will open the RS-485 circuit and isolate the controller
from the network.
If one, or both, lamps are lit, it indicates the network is improperly phased.
This means that the ground potential of the controller is not the same as other controllers on the network
If the voltage or current on the network exceeds safe levels, the lamps operate
as fuses to protect the controller from damage.
Power Jumper
The power jumper, shown in Illustration 8, can be used to remove power from the controller. This should be done anytime connections are made or changed on the controller. Removing the jumper opens the 24 VAC supply circuit.
Resetting the Controller
If the controller appears to be operating incorrectly, or is not responding to commands, you may need to reset the controller.
10
Page 11
KMD-5831 PLC-28 Direct Digital Controller Installation & Operation Guide Operation
Note
Resetting the controller will restore the factory default configuration. If the devices cannot communite with the controller, or the controller cannot commnicate with other controllers, it may be necessary to re-configure the controller with HCM to establish normal communications and operation. Repro­gramming may also be required.
To reset the controller, proceed as follows.
1. Remove the lower Override Board cover on the controller.
2. Locate the Reset button (see Illustration 8).
Power
Jumper
Watch Dog
Jumper
Reset Button
Illustration 8. RS-485 End-of-Line Switch Detail
3. Locate and remove the Power Jumper from the current position.
4. Depress and hold the Reset button.
6. Reinstall the Power Jumper. (
DO NOT release the Reset button.)
7. Continue to hold the Reset Button until the Communications LED flashes rapidly.
8. Release the Reset Button.
This completes the reset sequence for the controller.
11
Page 12
Disclaimer
The material in this document is provided for information purposes only. The contents and the product(s) described herein are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this document.
Important Notices
The KMC logo is a trademark of KMC Controls, Inc.©2003, KMC Controls, Inc. All rights reserved.
No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of KMC Controls, Inc.Printed in U.S.A.
Technical Support
If you have any questions about this technical document or need additional details, please call KMC Controls technical services at 574-831-5250 or e­mail us at techs@kmccontrols.com.
12
KMC Controls
P.O. Box 497
19476 Industrial Drive
New Paris, IN 46553
U.S.A. TEL: 574.831.5250 FAX: 574.831.5252
E-mail: info@kmccontrols.com
902-019-04B
Loading...