KMC Controls KMD-5831 Installation & Operation Manual

Installation & Operation Guide
(Shown with optional Override Board Cover)
KMD-5831
Programmable Loop Controller PLC-28 Direct Digital Controller
902-019-04B
1
Introduction
For clarity we will focus on the KMD-5831 but all installation and operating instructions apply equally to the KMD-5821.
Illustration 1 shows the major controller components and their locations. The KMD-5821has fewer inputs and outputs.
Override
Board
Cover
Input Pull-Up
Switches
Input Terminal
Blocks
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O
A
1
O
A
2
O
A
3
O
A
4
O
A
5
O
A
6
O
A
7
O
A
8
Output Terminal
Blocks
Grounds
AC Power
Blank Cover
Input
RJ–12
Connector
Isolation
Lamps
RS–485
Connector
Status LEDs
Illustration 1. Controller Components
Note:
Additional components are located under the blank cover. We will cover these in detail later in this document.
2
Installation
Mounting
This section provides important instructions and guidelines for installing the KMD-5831 Programmable Loop Controller PLC-28 Direct Digital Controller. Carefully review this information prior to attempting installation.
Use the four mounting holes to securely mount the controller using #6 hardware inside a UL-approved Enclosed Energy Management Equipment Panel or other suitable protective enclosure. Refer to Illustration 2.
O-RSTATUSH
O
A
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
O-RSTATUSH
1
O
A
2
O
A
3
O
A
4
O
A
5
O
A
6
O
A
7
O
A
8
6.00"
Input Connections
Universal Inputs
Wiring connections are made depending on the intended application. Sixteen Universal Inputs are provided on the controller. Observe the following guide­lines. (Refer to Illustration 2.)
Connect device inputs to the input terminal connections (+).
Connect input grounds to the associated ground terminal (-).
6.00"
Illustration 2. Connector Detail
3
Installation KMD-5831 PLC-28 Direct Digital Controller Installation & Operation Guide
If input pull-ups are required, refer to “Configuration” later in this section.
Wiring terminals are suitable for up to two 12–22 AWG wires. If more than
two wires are required, use an external terminal strip for additional connec­tions.
Note:
Pulse inputs may be used under the following conditions:
If the pulse input does not use a voltage variation, then leave the input pull-up
in the “On” position.
If the pulse produces voltage peaks (up to +5 VDC max.), then the input pull-
up must be set to the “Off” position.
The maximum pulse rate is 8 HZ (8 pulse/sec).
Connecting Outputs
Twelve Universal Outputs are available for output connections labeled as 1–12 on the output terminal blocks. The outputs are grouped into three groups of four outputs each with a shared grounds (labeled “SC”) in each block.. Each output can produce 50 mA at +12 VDC. If a greater current is required, KMC recom­mends the use of Override Boards discussed later in this section.
A separate ground block provides six additional ground connections.
Network Connections
The controller provides connections for two types of RS–485 circuits.
RJ-12
The RJ–12 connector provides a six-wire RS-485 connection to a modem or PC using the KMD-5559 CommTalk Data Exchange Module. Simply connect a suitable RJ-12 cable between the devices.
RS-485 Inputs
A RS–485 terminal is available for connections to a network of controllers If the Controller is at the End-of-Line, refer to “Configuration” after connections are completed.
Detail
The End-of-Line connection will have only one wire attached to the A and B terminals.
For reliable operation, use Belden cable model #82760 or equivalent (18 gauge,
twisted, shielded, 50 picofarads or less) for all network terminal block connec­tions.
Connect the nodes of the network in a daisy-chain arrangement. This means:
Connect the A terminal in parallel with all other A terminals.
Connect the B terminal in parallel with all other B terminals.
Connect the shields of the cable together at each controller.
4
Loading...
+ 8 hidden pages