Typ eThermistor
Accuracy±0.36° F (±0.2° C)
Resistance10,000 at 77° F (25° C)
Operating range48° to 96° F (8.8° to 35.5° C)
Sensor Accuracy, KMD-1281
Typ eCMOS
Humidity
Range0 to 100% Relative humidity
Accuracy at 25°C±2% from 10–90% Relative humidity
Response timeLess than or equal to 4 seconds
Tem pe ra t ur e
Accuracy±0.9° F (±0.5° C) Offset from
40 to 104° F
(4.4 to 40.0° C) Offset is adjusted
through configuration software
Resolution±0.1°F (±0.1° C)
Operating range36 to 120° F (2.2 to 48.8° C)
Response time5 to 30 seconds
Environmental Limits
Operating Temperature34° to 125° F (1.1 to 51.6° C)
Shipping–40° to 140° F (–40°C to 60° C)
Humidity0 to 95% Relative humidity
non-condensing
Revision A3
Dimensions
A
C
D
E
B
F
KMC Controls
AB CDE F
3.25 in.5.16 in.2.58 in.3.25 in.0.87 in.1.07 in.
83 mm131 mm66 mm83 mm22 mm27 mm
Models
Temperature only
AlmondKMD-1261
WhiteKMD-1261W
Temperature and humidity
AlmondKMD-1281
WhiteKMD-1281W
Revision A4
NetSensor Installation and Operation
55
°
10 m
32.8 ft
10 m
32.8 ft
X
0°
10 m
32.8 ft
10 m
32.8 ft
0°
46.5
°
Y
Top view
Side view
RJ-12
Motion sensor range33 feet (10 meters)
Network cable preparation
Connecting a NetSensor to a controller requires a six-wire cable with
RJ-12 connectors on each end. KMC plenum-rated preassembled
cables are recommended. Cables made to length must meet the
following requirements:
◆ Cable length must be no longer than 75 feet (22.9 meters).
◆ Cable conductors must be no smaller than #24 AWG.
◆ Cable insulation must meet local building codes.
◆ Connectors must be appropriate for the cable in use and are
installed following the connector manufacturers instructions.
Cable details
Revision A5
KMC Controls
Caution
RJ-12
cable
Allen
screws
Mounting
base
Rough-in preparation
To prevent mounting screw heads from touching the circuit
board in the NetSensor, use only the mounting screws
supplied by KMC Controls. Using screws other than the
type supplied will damage the NetSensor.
Complete rough-in wiring at each sensor location prior to sensor
installation. This includes the following.
◆ Routing the network cable from the NetSensor to a controller.
◆ If required, installing the appropriate backplate. See Accessories
on page 3 for model numbers.
NetSensor mounting details
Revision A6
NetSensor Installation and Operation
Turn clockwise to
remove from base.
Installing the NetSensor
1. Turn the Allen screws in the base of the NetSensor clockwise
until they clear the cover. Swing the sensor away from the
mounting base to remove it.
Mounting screws
2. Route the RJ-12 cable through the mounting base.
3. Fasten the mounting base directly to a 2 x 4 inch outlet box or a
backplate with the Allen screws toward the floor.
4. Insert the RJ-12 cable coming from the base into the NetSensor.
5. Place the top of the NetSensor over the top of the mounting base
and swing it down over the Allen screw brackets. Be careful not
to pinch any wiring.
6. Back the Allen screws out of the brackets until they engage the
NetSensor cover and hold it in place.
Revision A7
KMC Controls
Setpoint
Operation
The following sections describe the controls and indicators found on
the NetSensor.
Display The temperature display contains four 0.375-inch, 7-segment
LCD digits that are visible across a normal size office. The display
provides time, temperature and on the KMD-1281 humidity
readouts. Room temperature is displayed until either setpoint button
is pressed and then the display changes to setpoint mode.
Controls Models KMD-1261 and KMD-1281 include eight push
buttons; six of which (button 1 and buttons 3-7) are user
programmable. The actual operation of the programmable buttons
depend upon the program in the controller to which the NetSensor is
connected.
NetSensor buttons
The arrow buttons adjust the programmed values up or down. Values
can be changed for all programmed buttons except the setpoint as
follows:
1. Press the button for the desired function.
2. Adjust the value up or down.
Setpoint Pressing either the up or down arrow buttons changes
the display from room temperature mode to setpoint mode. Each
additional time a setpoint button is pressed and released changes the
setpoint up or down.
Auxiliary function These NetSensors do not have auxiliary wires
found on earlier models. Press buttons 5 and 7 together and then
press an up arrow or down arrow button to change the auxiliary
function.
Revision A8
NetSensor Installation and Operation
Programming instructions
Programming instructions for NetSensors are included in Help
supplied with WinControlXL, BACstage, and TotalControl.
Maintenance
Remove dust as necessary from holes in top and bottom. Clean the
display and motion sensor cover with a soft, damp cloth and mild
soap.
Revision A9
KMC Controls
Important notices
The KMC logo, WinControlXL and NetSensor are registered
trademarks of KMC Controls, Inc.
TotalControl and BACstage are trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may be reproduced,
transmitted, transcribed, stored in a retrieval system, or translated
into any language in any form by any means without the written
permission of KMC Controls, Inc.
Printed in U.S.A.
Disclaimer
The material in this manual is for information purposes only. The
contents and the product it describes are subject to change without
notice. KMC Controls, Inc. makes no representations or warranties
with respect to this manual. In no event shall KMC Controls, Inc. be
liable for any damages, direct or incidental, arising out of or related to
the use of this manual.
KMC Controls. Inc.
19476 Industrial Drive
New Paris, IN 46553
TEL: 1.574.831.5250
FAX: 1.574.831.5252
E-mail: info@kmccontrols.com
Revision A10
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.